– Comprehensive Engineering Team Inspection Report 05000395/2024011
ML24155A051
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 06/26/2024
From: James Baptist
NRC/RGN-II/DRS/EB1
To: Carr E
Dominion Energy
References
IR 2024011
Download: ML24155A051 (18)


Text

SUBJECT:

VIRGIL C. SUMMER - COMPREHENSIVE ENGINEERING TEAM INSPECTION REPORT 05000395/2024011

Dear Eric S. Carr:

On May 21, 2024, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Virgil C. Summer and discussed the results of this inspection with Mr. Robert Justice and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety Docket No. 05000395 License No. NPF-12

Enclosure:

As stated

Inspection Report

Docket Number:

05000395

License Number:

NPF-12

Report Number:

05000395/2024011

Enterprise Identifier:

I-2024-011-0020

Licensee:

Dominion Energy

Facility:

Virgil C. Summer

Location:

Jenkinsville, SC

Inspection Dates:

March 25, 2024, to May 21, 2024

Inspectors:

P. Braxton, Reactor Inspector

L. Colon Fuentes, Construction Inspector

J. Copeland, Reactor Inspector

C. Even, Sr. Reactor Inspector

R. Fanner, General Engineer

C. Franklin, Reactor Inspector

R. Smith, Reactor Systems Engineer

Approved By:

James B. Baptist, Chief

Engineering Branch 1

Division of Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a comprehensive engineering team inspection at Virgil C. Summer, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

===71111.21M - Comprehensive Engineering Team Inspection The inspectors evaluated the following components and listed applicable attributes, permanent modifications, and operating experience:

Structures, Systems, and Components (SSCs) (IP section 03.01)===

For each structure, system, or component sample listed below, the team reviewed licensing and design basis documents and a sampling of applicable operator actions, periodic testing results, corrective action program documents, internal and external operating experience, preventive and corrective maintenance work orders, modifications, and aging management programs. Additionally, the team performed walkdowns of the component or procedure and conducted interviews with licensee personnel.

The team used the attributes contained in IP 71111.21M, Appendix A, Component Review Attributes, such as those listed below as guidance. Specifically, the team evaluated these attributes in the course of applying 71111.21M, Appendix B, Component Design Review Considerations and 71111.21M, Appendix C, Component Walkdown Considerations.

(1) DC inverter (XIT5901/5902)
  • Design basis documents and calculations
  • Part 21/Operating Experience
  • Post Modification/Preventative Maintenance Testing
  • Material condition and configuration
(2) Turbine driven emergency feedwater pump discharge check valve (XVC01016-EF)
  • IST and TS required surveillances.
  • Hydraulic analysis, design pressures and flowrates, and minimum opening and closing differential pressure.
  • Environmental qualification
(3) Component cooling water heat exchanger B (XHE-2B-CC)
  • Compliance with UFSAR, TS and TS Bases
  • Design basis documents and calculations
  • Visual inspection during walkdown focusing on material condition
  • Surveillance testing and preventative maintenance records
  • Procedures and sampling requirements/records for chemistry and corrosion control
  • Setup calculation assumption agreement with installed configuration
(4) ESF Switchgear air handling unit and supporting equipment (XAH-8-VL)
  • Compliance with UFSAR, TS, and TS Bases
  • Visual inspection during walkdown
  • Setup calculation assumptions and agreement with installed configuration
  • Preventive and corrective maintenance records
  • Conformance with manufacturer instructions for installation, maintenance, testing and operation
  • Seismic qualification of air handling unit
  • Alarm response procedures
  • Air filter changeout requirement for differential pressure
  • Thermal performance testing
(5) Reactor building purge valves (XVB00002A/B-AH)
  • Compliance with UFSAR, TS, and TS Bases
  • Visual inspection during walkdown of various components in the system
  • Setup calculation assumption agreement with installed configuration
  • Periodic verification testing and post-test analyses
  • Surveillance testing & maintenance records
  • Conformance with manufacturer instructions for installation, maintenance, testing and operation
  • Evaluation of applicable operating experience relevant to sample
(6) Component cooling water pump motor A (MPP-1A-CC)
  • Compliance with UFSAR, TS, and TS Bases
  • Design bases documents and calculations
  • Setup calculation assumptions with installed configuration
  • Surveillance testing and maintenance records
  • Visual inspection during walkdown of motor and supporting components
  • Conformance with manufacturer instructions for installation, maintenance, testing, and operation
(7) Emergency diesel generator A fuel oil and transfer system (DF)
  • Compliance with UFSAR, TS, and TS Bases
  • Visual inspection during walkdown
  • Setup calculation assumptions and agreement with installed configuration
  • ASME Code surveillance testing & maintenance records for pump
  • Conformance with manufacturer instructions for installation, maintenance, testing and operation
  • Seismic qualification of pump and attached piping nozzle loads
  • Fuel oil tank LO and LO-LO level setpoints and instrument uncertainty calculations
  • Fuel oil delivery inspections (fuel quality)

(8)7.2kV bus (XSW-1DB)

  • Compliance with UFSAR, TS, and TS Bases
  • Review of design basis and supporting calculations
  • Review of design changes
  • Performed field walkdowns of system components
  • Review of surveillance records
  • Evaluation of maintenance rule attributes
  • Review of procedures

Modifications (IP section 03.02) (3 Samples)

(1) ECR 50883 - Safety-Related Inverter Replacement, Revision 0
(2) ECR 50585 - Replacement of Chiller B, Revision W
(3) ECR 50944 - Core Subcooling Margin Monitor A Replacement, Revision 0 10 CFR 50.59 Evaluations/Screening (IP section 03.03) (8 Samples)

(1)10 CFR 50.59 Screening: ECR 50883 - Safety-Related Inverter Replacement, Revision 0 (2)10 CFR 50.59 Screening: VC-21-00010 - EDG A/B Voltage and Frequency Meters Replacement, Revision 4 (3)10 CFR 50.59 Evaluation: ECR 50585 - Safety-Related Chiller Replacement Activities - B Chiller Replacement, Revision 0 (4)10 CFR 50.59 Screening: VC-21-00004 - Adjustment of Breaker Settings for Battery Chargers, Revision 0 (5)10 CFR 50.59 Evaluation: ECR 50944 - Core Subcooling Margin Monitor A Replacement, Revision 0 (6)10 CFR 50.59 Screening: VC-23-00021 - B Chiller Compressor Replacement, Revision 0 (7)10 CFR 50.59 Screening: VC-22-00001 - Setpoint Accuracy Inconsistencies for IFS09015A/B and IFS09035A/B, Revision 0 (8)10 CFR 50.59 Screening: ECR 72545 - FWIV Obsolete Solenoid Replacement, Revision 0

Operating Experience Samples (IP section 03.04) (1 Sample)

(1) Information Notice 97-21: Availability of AC Power Source Designed for Station Blackout Event

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On May 21, 2024, the inspectors presented the comprehensive engineering team inspection results to Mr. Robert Justice and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

DC 08200-01

ESF Degraded Voltage Logic and Settings

Rev. 29

DC 08320-005

ESF Battery 1A & 1B Capacity

Rev. 15

DC 08320-006

300 Amp ESF Battery Charger Load Study

Rev.10

DC 08320-010

Class 1E Volt DC System Voltages & Voltage Drop

Rev. 19

DC 08320-016

Battery Service Test and Acceptance

Rev. 7

DC 08340-002

20V Class 1E Vital Ac System Design

Rev.10

DC-04310-021

Component Cooling Water Heat Exchanger Minimum Flow

vs Service Water Temperature

Rev. 2

DC-04310-045

Component Cooling Water Heat Exchanger Design Basis

Limiting Conditions (GL 89-13)

Rev. 13

DC-04330-061

Residual Heat Removal/Component Cooling Water/ Service

Water Analyses for 2900 MWT

Rev 4

DC-09310-066

Service Water from CC Heat Exchanger B Flow (IFT04490)

Rev. 1

DC00040-136

RWST Cases For Various Drain Times (Attachment 1

pages: 28, 29, 34 and 35)

Rev. 2

DC0011A-132

Component Cooling Water Pump Motor Life Extension

Rev. 3

DC0011E-077

Post-Accident Operability Time for Schulz Electric Medium

Voltage CCW Pump Motor Rewind

Rev. 1

DC0152A-019

Determination of the Limiting Line Pressure and Maximum

Expected Differential Pressure for Air-Operated Valves for

the AH System

Rev. 0

DC0152A-020

KVAP Analysis for Air-Operated Valves in AH System

Rev. 0

DC05220-091

EF Hydraulic Analyses

Rev. 4

DC05220-76

PROTO-FLO Model of Emergency Feedwater System

(EFW)

Rev. 4

DC06620-002

DG Emergency Fuel Oil Tank Capacity

Rev. 3

DC06630-004

DG Fuel Oil Transfer Pump NPSH Requirements and

System Pressure Loss

Rev. 4

DC07070-007

RB Purge Valve Qualification Without Outboard Flanges

Rev. 1

DC07230-006

IB Water Chiller Area/Pump Room Ventilation System Flow

Rates

Rev. 5

71111.21M

Calculations

DC07260-002

1B ESF Switchgear Room Cooling Loads

Rev. 4

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

DC07260-006

1B ESF Switchgear Room Cooling System Pressure Loss

Rev. 2

DC08360-006

Diesel Generator 1A and 1 B Load Study

Rev. 16

DC09620-004

DG Fuel Oil Storage Tank Calibration Data

Rev. 5

DC09620-014

DG Fuel Oil Storage Tank Level Instrument Uncertainties

and Setpoints

Rev. 2

DC09640-006

ESF SWGR 1DB Ambient Temperature Switch Setpoint

Rev. 1

DCO03490-003

Intermediate & Diesel Generator Building Flooding

Evaluation

2/18/2018

N3DBS-137

DG Fuel Oil Transfer Pump Seismic Analysis

2/1977

MPR Report

0310-0064-LTR-

001

VCS ESF Switchgear Room Cooling System-Preliminary

Analysis Results

Rev. 0

VC-CALC-000-

DC08050-002

ESF Load Study

06/14/2023

VC-CALC-000-

DC09610-048

Service Water Scaling for Component Cooling Water Heat

Exchanger Testing

Rev. 4

Condition Reports

(CRs)

23597, 1223850, 1223976, 1227275, 1223911, 1227330,

23768, 19-04308 (Action 3), 20-02968,

Corrective Action

Documents

Corrective Actions

(CAs)

11800994, 11818678, 11801000, 11789985, 11789984, 21-

000894, 1243311

CR1254829

FR-9287 indicated flow when there was no flow

03/27/2024

CR1254890

DC08320-010 loss of documentation issue

03/28/2024

CR1255883

Circuit information discrepancy

04/08/2024

CR1256046

SGTR time critical action was exceeded

04/09/2024

CR1256175

Drawing discrepancies for switchgear air handling unit

04/10/2024

CR1256177

Megger testing acceptance criteria incomplete in procedures

04/10/2024

Corrective Action

Documents

Resulting from

Inspection

CR1258836

XAH0008 design calculation/level of detail in calculation

05/08/2024

04-4461 SS-211-

108

Electrical Block Diagram, System VL, Local Vent & Cooling,

Sheet J15

Rev. E

04-4461-SS-211-

108

Electrical Block Diagram, System VL, Local Vent & Cooling,

Sheet C5

Rev. H

04-4461-SS-211-

108

Electrical Block Diagram, System VL, Local Vent & Cooling,

Sheet J23

Rev. A

Drawings

04-4461-SS-211-

Electrical Block Diagram, VL System, Local Vent and

Rev. B

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

108

Cooling Sheet C19

1MS-14-023

CS PAM TEWAC Motor Outline

Rev. 8

1MS-14-083

Component Cooling Pump Curve

Rev. 0

1MS-25-1129

Tilting Disc Check Valve

Rev. 3

1MS-25-276-7

4" 1500# Swing Check Valves

Rev. G

25-1-8

ESF SWGR Room 1DB Cooling Unit No. XAH-8-VL

Rev. 1G

D-302-085

P&ID Emergency Feedwater

Rev. 53

D-302-351

Diesel Generator-Fuel Oil

Rev. 17

D-912-10

R. B. PURGE SUPPLY & PURGE EXHAUST SYSTEMS

Rev. 25

D-912-157

Intermediate Building ESF SWGR Rooms and Speed Switch

Rooms Cooling Systems

Rev. 12

E-206-005

PLANT ELECTRICAL DISTRIBUTION

Rev. 33

E-206-062

Elec. One Line and Relay Diagram, Engineered Safety

Features Vital AC Sys.

Rev. 41

E-207-014

Electrical Three Line Diagram 7200V SWGR

Rev. 18

E-304-089

Emergency Feedwater Isometric Drawing

Rev. 27

E-917-158

Air Handling Unit XAH-8-VL, Extension Plans, Section, and

Detail

Rev. 0

E-922-411

Intermediate Building-Plan Above EL. 436-0

Rev. 2

MS-54-06

36" CLASS 150/150 WOG WELD END VALVE ASSY. &

MATRYX 45102 SR80

Rev. 12

SKO3676LC-1

Component Cooling Water Pump Motor Calculated Starting

Performance

2/24/1976

SKO3676LC-3

Component Cooling Water Pump Motor Calculated Speed-

Torque Curves

2/24/1976

SKO3676LC-4

Component Cooling Water Pump Motor Calculated Speed-

Torque Curves

2/24/1976

VCS-ITM00499A-

IC

Instrument Loop Diagram - RC Subcooling Monitor A

Rev. 3

DC05220-078

EFW Design Flag Pressures

Rev. 1

DC05220-078

EFW Design Flag Pressures

Rev. 0

ECR-50585

Safety Related Chiller Replacement

Rev. Al

Engineering

Changes

ECR-50585

Safety Related Chiller Replacement

Rev. AK

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

ECR-50585

Safety Related Chiller Replacement

Rev. AN

ECR-50585

Safety Related Chiller Replacement

Rev. AN

ECR-50919

Cable Bus Conductor Replacement

5/10/2017

ECR-50944

Core Subcooling Margin Monitor A Replacement

Rev. 5

ECR-50944

Core Subcooling Margin Monitor A Replacement

(Supporting Documentation)

Rev. 6

ECR-70153

XVB00001&2-AH

Rev. 0

ERC-50585

Safety Related Chiller Replacement

Rev. W

VC-20-00006

EF Check Valves and System Improvement

Rev. 3

VC-23-00021

Design Change Package for "B" Chiller Compressor

Replacement

Rev. 0

Design Basis

Document

HEATING, VENTILATION, AND AIR CONDITIONING

(HVAC)

Rev. 11

DSP-542-044461-

000

Design Specification for Purge System isolation Valves

ASME B&PV Code,Section III Division 1 Class 2

10/21/1976

EIR-82160A

GL 89-13 Heat Exchanger Performance Testing Flow

Conversion Equations

Rev. 2

QR-351029703-6

Pressure Transducers, Oil Level Switch, and Relay

Rev. 2

QR-351029703-9

Chiller Equipment

Rev. 0

TR08620-034

Fire Response Abnormal Operating Procedures Technical

Basis Document

Rev. 2

TR08620-036

NFPA 805 Recovery Actions, FEASIBILITY/RELIABILITY

STUDY

Rev. 2

VC-SDBD-000-

CC

Design Basis Document for Component Cooling Water

System

Rev. 13

Engineering

Evaluations

VC-SDBD-000-

SW

Design Basis Document for Service Water System (SW)

Rev. 20

Virgil C. Summer Nuclear Station - Generic Letter 82-28

NUREG-0737 Item II.F.2

08/03/1984

Condition Monitoring (CM) for Total Containment Leakage

(Maintain the total leakage of ALL penetrations, including

hatches, less than 0.6 La over a rolling 18 month period)

Rev. 0

DG Fuel Oil Transfer Pump XPP304B, IST Trend Data

01/10/2024

Miscellaneous

1MS-92-3404

Seismic Analysis Report E6188-82A

2/22/1977

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

1MS-94B-0453

Posi-Seal Wafer Trunnion Valves (Maintenance Manual)

11/13/1972

1MS-94B-1290

1500 LB TILT DISC CHECK VALVES

Rev. 0

1MS-94B-1290

1500 LB TILT DISC CHECK VALVES

Rev. 1

1MS-94B-1571-1

Instruction Manual for 280 Ton Custom Chillers

Rev. 2

1MS-94B-1844

Gutor: 10KVA Type PXW UPS

Rev.0

20118

Rooms IB-463-01 and IB-436-01 Require Additional Cooling

06/26/1987

AB-17

REACTOR BUILDING VENTILATION SYSTEM (Ops

Training Handout)

Rev. 22

AH

The Air Handling System provides building ventilation &

cooling, local instrumentation and equipment cooling,

maintains

Control Room and Reactor Building pressure, and filters air

contaminants. [HVAC DBD & AH SYSTEM DESCRIPTION]

Rev. 0

ARG-1

Abnormal Response Guideline Loss of RHR While

Operating at Mid-Loop Conditions

Rev. 3

ARG-2

Shutdown LOCA

Rev. 3

ARG-3

Steam Generator Tube Leak

Rev. 3

Bulletin No. B-

1305-5G

Farr 30/30 Medium Efficiency Disposable Filters

CCL Report No.A-

114-77-01

Seismic Analysis Report of Air Handling Units for VCS

06/01/1978

DBD-ED

25V DC Electrical System

Rev. 6

LICENSEE

EVENT REPORT

(LER 1999-005-

01)

ENGINEERED SAFETY FEATURES (ESF) COMPONENTS

POTENTIALLY OUTSIDE THE DESIGN BASIS OF THE

PLANT

09/07/2000

NUREG/CR-6794

Evaluation of Aging and Environmental Qualification

Practices for Power Cables Used in Nuclear Power Plants

1/nd/2003

OGSS: 11501

Safety Classification Of XPN 7218 Core Subcooling

Monitors "A" and "B"

10/17/1983

OLC-D1/K1

LODAM Optical Level Controlling Devices Technical Manual

Version 3.0

OLC-D1/K1

LODAM Optical Level Controlling Devices Data Sheet

Ver. 9.0

PA-PSC-0590

Emergency Response Guidelines Revision 3 Validation

Report

04/01/2014

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

PWROG-17014-P

Shutdown LOCA Basis: Feasibility Analysis Summary

Report for the Babcock and Wilcox, Combustion

Engineering, and Westinghouse NSSS Designs

Rev. 0

RC-07-0074

VIRGIL C. SUMMER NUCLEAR STATION (VCSNS)

DOCKET NO. 50/395 OPERATING LICENSE NO. NPF-12

90-DAY RESPONSE TO NRC GENERIC LETTER 2007-01

INACCESSIBLE OR UNDERGROUND POWER CABLE

FAILURES

THAT DISABLE ACCIDENT MITIGATION SYSTEMS OR

CAUSE PLANT TRANSIENTS

05/04/2007

RG 1.218

Condition-Monitoring Techniques for Electric Cables Used in

Nuclear Power Plants

06/nd/2010

SP-0951

Engineering Services Specification: Replacement Water

Chillers

Rev. 3

SP-1044

Class 1E Inverters

Rev. 4

System 99

Containment Isolation Pseudosystem

Rev. 0

TR01520-005

Check Valve Condition Monitoring Program (CVCMP)

Rev. 2

TR08200-003

Compliance to NRC Rule 10 CFR 50.63 'Station Blackout'

Rev. 10

VC-SDBD-000-EF

Emergency Feedwater System Design Basis Document

Rev. 18

VCSPS UFSAR

V.C. Summer Power Station Updated Final Safety Analysis

Report

Rev. 23.02

1MS-94B-0453

Posi-Seal: Purge Steam Isolation Valves

Rev. 2

1MS-94B-1073-3

Heavy Duty Limit Switches

01/09/1989

1MS-94B-1208

Installation of EC210 Electrical Receptacles and Connector

and Cable Assemblies into Various Control Devices

Rev. 2

1MS-94B-639

Fisher Control: Control Valve

Rev. 16

Alarm Response,

Panel XCP-6210-

LCB7,

Annunciator Point

8-27

High Room Temperature, Origin ITS09861

Rev. 0

AOP 101.1

Loss of Coolant Not Requiring SI

Rev. 5

AOP-112.1

ARG-2, Shutdown LOCA

Rev. 7

Procedures

AOP-117.1

LOSS OF SERVICE WATER

Rev. 6

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

AOP-118.1

LOSS OF COMPONENT COOLING WATER

Rev. 4

AOP-304.1B

LOSS OF BUS 1DB WITH THE DIESEL NOT AVAILABLE

Rev. 5

AOP-501.2

Loss of Chilled Water

Rev. 3

AOP-600.1

CONTROL ROOM EVACUATION

Rev. 4

AOP-900.01

FIRE RESPONSE INITIAL ACTIONS

Rev. 4

AOP-900.02

CONTROL ROOM EVACUATION DUE TO FIRE

Rev. 5

CM-AA-SAR-101

Updating Safety Analysis Report (SAR)

Rev. 13

CMP-700.013

Inspection of Electrical Manholes

Rev. 3

CSPP-045

CYBER SECURITY PLAN PROCEDURE: EVALUATE AND

MANAGE CYBER RISK

Rev. 1

EMP-245.021

Diesel Generator B XEG0001B Preventive Maintenance

Rev. 6

EMP-280.013

ESF Transformer XTS0004 and XTF0005 Service Test

Rev. 8

EMP-280.12

Emergency Auxiliary Transformer Service Test XTF-31 and

XTF-32

Rev. 6

EMP-295.004

Inspect and PM of Electric Motors

Rev. 16

EOP-1.0

E-0, Reactor Trip or Safety Injection

Rev. 33

EOP-1.1

ES-0.1 REACTOR TRIP RESPONSE

Rev. 25

EOP-1.2

ES-1.1, Safety Injection Termination

Rev. 22

EOP-12.0

F-0, MONITORING OF CRITICAL SAFETY FUNCTIONS

Rev. 17

EOP-13.0

FR-S.1, RESPONSE TO ABNORMAL NUCLEAR POWER

GENERATION

Rev. 25

EOP-2.0

E-1, LOSS OF REACTOR OR SECONDARY COOLANT

Rev. 18

EOP-2.2

ES-1.3, TRANSFER TO COLD LEG RECIRCULATION

Rev. 19

EOP-3.0

E-2, Faulted Steam Generator Isolation

Rev. 14

EOP-4.0

E-3, STEAM GENERATOR TUBE RUPTURE

Rev. 27

EOP-6.0

ECA-0.0, LOSS OF ALL ESF AC POWER

Rev. 41

ER-AA-NDE-ET-

501

Eddy Current Examination of Non-Ferromagnetic Tubing

Rev. 1

ES-0514A

Maintenance Rule - Scoping

Rev. 2

MMP-445.048

Anchor Darling/Flowserve Tilting Disc Check Valve

Maintenance Manual

Rev. 3

MMP-460.022

Inspect, Clean, and Lubricate Fan Coil Units

Rev. 16

MMP-460.024

Perform Air Balance

2/27/1995

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

MMP-460.025

Inspection And Replacement of Filters in Air Handling

Systems

Rev. 17

OAP-101.3

VALIDATION AND VERIFICATION OF TIME CRITICAL

OPERATOR ACTIONS

Rev. 3

Parr Station

Supplying VCS On Blackstart and Restoration

Rev. 1

PI-AA-200

Corrective Action

Rev. 42

SAP-107

10CFR50.59 And 10CFR72.48 Review Process

Rev. 8

SAP-1163

Control of Documents Required for Licensing

Rev. 7

SAP-1282

Electrical Cable Reliability Monitoring Program

Rev. 0

SAP-153

Component/Condition Verification

Rev. 2

SAP-207A

OPERATIONS EMERGENCY PROCEDURES

MAINTENANCE PROGRAM

Rev. 7

SOP-114

REACTOR BUILDING VENTILATION SYSTEM

Rev. 24

SOP-118

COMPONENT COOLING WATER

Rev. 19

SOP-124

A

Rev. 11

SOP-304

115KV/7.2KV OPERATIONS

Rev. 15

SOP-410

CORE SUBCOOLING MONITOR SYSTEM

Rev. 6

SOP-503

Operation of Standby ESF SWGR Room Cooling

Rev. 12

STP-118.004

REACTOR BUILDING PURGE ISOLATION VERIFICATION

Rev. 7

STP-125.004B

Diesel Generator B Load Rejection Test

Rev. 4

STP-125.021

Periodic Testing of the Alternate AC Power Supply

Rev. 5

STP-130-005B

AH Valve Operability Testing (Mode 5)

04/07/2023

STP-130.003A

Emergency Feedwater Check Valve Testing

Rev. 4

STP-130.005B

AH Valve Operability Testing (Mode 5)

11/01/2021

STP-215.002A

Penetration XRP0101 Valve Leakage Test (XVB00002A/B-

AH )

11/09/2021

STP-215.002A

Penetration XRP0402 Valve Leakage Test (XVB00001A/B-

AH )

11/09/2021

STP-215.002A

Penetration XRP0402 Valve Leakage Test (XVB00001A/B-

AH )

05/07/2023

STP-215.002A

Penetration XRP0101 Valve Leakage Test (XVB00002A/B-

AH )

05/07/2023

STP-229.001

HVAC Chilled Water Pump Test

Rev. 11

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

STP-340.001

RCS LOOP A WIDE RANGE HOT LEG TEMPERATURE

INSTRUMENT ITE00413 CALIBRATION

Rev. 12

STP-345.045A

ITM00499A, RCS CORE SUBCOOLING MARGIN

MONITOR CALIBRATION A TRAIN

Rev. 3

STP-401.006

IST and Code Check Valve Operability Test

Rev. 9

STP0125.013A

DG A Semi-Annual Operability Test

03/07/2022

TR01520-002

Air Operated Valve Program Scoping and Categorization

(Attachment 3)

03/14/2024

TRP-011

(TECHNICAL

REQUIREMENTS

PACKAGE)

Core Subcooling Margin Monitors

Rev. 5

VC-PROC-000-

ES-0505

Service Water System Corrosion Monitoring and Control

Program

Rev. 6

VC-PROC-000-

MMP-255.001

General Heat Exchanger Cleaning and Tube Plugging

Rev. 16

VC-PROC-000-

OAP-106.1

Operating Rounds

Rev. 19

VC-PROC-000-

PTP-173.001

Backflushing Service Water Side of Component Cooling

Heat Exchanger

Rev. 4

VC-PROC-000-

SOP-501

HVAC Chilled Water System

Rev. 21

Shipping Records

BOM for Purge

System Isolation

Butterfly

Pneumatic

Operating Valves

Heating, Ventilation, Air Conditioning and Air Handling

System, V C Summer Nuclear Station Unit 1

04/18/1977

Work Orders

Work Orders

(WO)

201691020, 88201696050, 88201690090, 88101176558,

201690812, 88201690883, 88201691017, 88101019987,

88101020004, 88101030435, 88101030477, 88101030497,

88101030514, 88101030538, 88101030554, 88101030577,

88101030596, 88101030683, 88101032356, 88101109833,

201708248, 88201709420, 88201710619, 1711383,

88101052818, 88101024774, 88101100649, 88101112398,

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

201680552, 2012768-001, 2012769-001, 88101031917,

88101034472, 88101035186, 88101034166, 88101035116,

201686319, 881010038047, 88201696834, 88101045160