Semantic search

Jump to navigation Jump to search
 Issue dateTitleTopic
ML20207E08826 February 1999Notice of Violation from Insp on 990201-05.Violation Noted: on 990201,NRC Inspectors Identified That Area with Dose Rates Greater than 1000 M/H Not Provided with Locked or Continously Guarded Doors to Prevent Unauthorized EntryHigh Radiation Area
ML20198L77124 December 1998Notice of Violation from Insp on 981207-11.Violation Noted: on 950630,licensee Made Change to Emergency Plan Without Commission Approval
ML20196F1141 December 1998Notice of Violation from Insp on 980920-1031.Violation Noted:From 980521 Through 981015,conditions Adverse to Quality Identified in Condition Rept 1998-0014 Not Promptly Corrected
ML20248E75028 May 1998Notice of Violation from Insp on 980405-0516.Violation Noted:On 980421,inspectors Found Back Doors on Diesel Generator Control Cabinet 1H22-p400 in Div 1 Standby Diesel Generator Room Standing Wide Open & UnattendedScaffolding
IR 07100019/20110295 December 1997Notice of Violation from Insp on 971019-1129.Violations Noted:Scaffold 08-779 Was Assembled to Contain Insulation on Small Gauge Pipe Just Down Stream of Containment Atmosphere Sample Inlet Valve 1P33F572AScaffolding
ML20199L94125 November 1997Notice of Violation from Insp on 970804-22.Violation Noted: on or About Period of 970117-29,approved FP Program as Described in UFSAR Was Not Fully Implemented.Emergency Light 1T92S222A Was Not Capable of Performing FunctionSafe Shutdown
Emergency Lighting
Fire Protection Program
ML20198Q02931 October 1997Notice of Violation from Insp on 970907-1018.Violation Noted:As of 971011,security Patrols Had Not Reported Dark Areas in Temporary Covered Maint Work Area in Protected Area
ML20216J20812 September 1997Notice of Violation from Insp on 970803-0906.Violation Noted:As of 970811,duplex Filter Selection Levers for HPCS & Div 1 Standby DGs Were in Both Position Such That Two Strainers/Filters Were Selected
ML20210N07619 August 1997Notice of Violation from Insp on 970622-0802.Violation Noted:On 970630,inspectors Identified Extension Ladder Supported on safety-related Cable Tray & No Engineering Evaluation Had Been Completed
ML20216A8416 August 1997Notice of Violation from Insp on 970714-18.Violation Noted: on 970717,compensatory Measures Not Implemented at Two Trailers within Protected Area Where Lighting Did Not Meet Required 0.2 Footcandles
ML20151L9365 August 1997Notice of Violation from Insp on 970714-17.Violation Noted:Individual Entered High Radiation Area W/O Monitoring Devices on 970123 & 0707High Radiation Area
ML20148E23329 May 1997Notice of Violation from Insp on 970310-27.Violation Noted: Licensee Had Not Updated FSAR to Assure That Info Included Contains Latest Matl DevelopedUltimate heat sink
ML20148D44527 May 1997Notice of Violation from Insp on 970323-0510.Violation Noted:On 970424,licensee Failed to Ensure That Qualified Individual Was Available to Respond for Er Organization Position of Offsite Emergency Coordinator
ML20140E63524 April 1997Notice of Violation from Insp on 970209-0322.Violation Noted:On 970227,design Engineer Failed to Implement Requirements of Procedure 01-S-03-10
ML20134P35825 November 1996Notice of Violation from Insp on 960929-1109.Violation Noted:Five Required Channel Checks for Fuel Handling Area Pool Sweep Exhaust Radiation High High Instrumentation Not Performed;Work Order 00159564 Not Revised
ML20059B92415 December 1993Notice of Violation from Insp on 931122-23.Violation Noted:Licensee Shipped Container of Resins to Chem-Nuclear Waste Disposal Site Found,By Disposal Site Operator,To Contain 0.7% of Free Standing LiquidProcess Control Program
ML20059B48610 December 1993Notice of Violation from Insp on 931024-1127.Violation Noted:On 931007,operators Hanging Clearances 933749 & 933750 Failed to Adequately Verify Inverter 1Y96 Was Being Supplied from Normal Power Supply
ML20058J49919 November 1993Notice of Violation from Insp on 930919-1023.Violation Noted:Undervessel Maint Personnel Disconnected 39 Addl LPRM Detectors Not Specified in Maint Work Order
ML20059E64026 October 1993Notice of Violation from Insp on 930927-1001.Violation Noted:On 930930,plant AO Entered Turbine Bldg Through Back Door of Control Room W/O Radiation Work Permit or self-reading Dosimeter
ML20059G26315 October 1993Notice of Violation from Insp on 920627-0731.Violation Noted:Licensee Determined That Records Required to Be Maintained by Commission Regulations or License Conditions Not Complete & Accruate in All Matl Respects
ML20059A3878 October 1993Notice of Violation from Insp on 930815-0918.Violation Noted:Instruction 07-S-13-60 Inadequate in That Instruction Did Not Adequately Address Setpoint of Slaved Trip Units Which Caused Unplanned RCIC Injection on 930914
ML20125C68824 November 1992Notice of Violation from Insp on 921001-1107.Violation Noted:Lubrication Requirements for Plant Equipment Determined by Use of Uncontrolled Document
ML20059L4006 September 1990Notice of Violation from Insp on 900721-0817.Violation Noted:Surveillance Procedure 06-IC-1C34-M-0001 Inadequate & Resulted in Feedwater TransientReactor Vessel Water Level
ML20247G67912 September 1989Notice of Violation from Insp on 890715-0825.Violation Noted:Filter Used for Determining Tech Spec Iodine Activity for Fuel Handling Area Vent Not Installed During 890719-26 & Semiannual Instrument Air Sample for 1989 Not Obtained
ML20248C95628 July 1989Notice of Violation from Insp on 890616-0714.Violations Noted: on 890620,operators Failed to Implement RCIC Sys Operating Instruction 04-1-01-E51-1 When Returning Sys to Standby Condition Following Maint
ML20246B26727 June 1989Notice of Violation from Insp on 890520-0616.Violations Noted:Licensee Failed to Procedurally Control Settings Which Resulted in Isolation When Damping Setting Not Made to New Circuit Boards Installed During Last Refueling Outage
ML20245F53813 June 1989Notice of Violation from Insp on 890415-0519.Violation Noted:Sys Operating Instruction 04-1-01-N21-1, Feedwater Sys Inadequate for Operation of Reactor Feedwater Pump Turbine Manual Speed Changer
ML20244E04931 May 1989Notice of Violation from Insp on 890329-31 & 0419-21. Violations Noted:On 890328,contract Worker Observed Entering Room in High Radiation Area W/O Being Provided W/Or Accompanied by One or More of Listed RequirementsHigh Radiation Area
ML20247E73216 March 1989Notice of Violation from Insp on 890114-0217.Violation Noted:Failure to Initially Perform Written Safety Evaluation Prior to Storage of Ecodex Resin in Containment
ML20235K45813 February 1989Notice of Violation from Insp on 890110-12.Violation Noted: Licensee Failed to Document All Emergency Preparedness Training Provided or Ensured to Offsite Support Agencies
ML20204E9816 October 1988Notice of Violation from Insp on 880820-0923.Violation Noted:Failure to Follow Administrative Procedure 01-5-06-1 to Evaluate Whether Opening Breaker Had Any Effect on Other Equipment & Plant Operation
ML20153E6663 May 1988Notice of Violation from Insp on 880319-0415.Violation Noted:Failure to Perform 10CFR50.59 Evaluation to Determine That Manual Operation of Pot Drain Valves on RCIC Supply Pipe Line Does Not Constitute Unreviewed Safety Question
ML20151C1265 April 1988Notice of Violation from Insp on 880220-0318.Violation Noted:Jumpered Terminals 9 to 10 on Ground Overcurrent Relay on Breaker 152-1609 Instead of 152-1606 & Failure to Document Installation of Equipment in Condenser Offgas Sys
ML20150E55525 March 1988Notice of Violation from Insp on 881214-18.Violation Noted: Licensee Installed Commercial Grade Parts on Equipment Requiring Environ Qualification W/O Adequate Evaluation of Suitability for Use in safety-related Applications
ML20196K4413 March 1988Notice of Violation from Insp on 880116-0219.Violation Noted:Licensee Failed to Follow Procedure 04-1-01-C11-1 to Properly Store Nitrogen Bottle Inside Containment
ML20150C06922 February 1988Notice of Violation from Insp on 871219-880115.Violation Noted:Dp for LPCS & LPCI Sys Not Determined & ECCS Header Delta Pressure Instrumentation Verified to Be 1.2 Plus/Minus 0.1 Psid from Calculated Dp
IR 07100114/201201820 January 1988Notice of Violation from Insp on 871114-1218.Violation Noted:Failure to Provide Necessary Controls to Ensure That Work & Testing Accomplished & Plant Conditions Maintained
ML20195H7036 January 1988Notice of Violation from Insp on 871214-17.Violation Noted: Dec 1987 Chemical Cleaning of Loops a & C of Standby Svc Water Sys Conducted W/O Adequate Safety Evaluation of Effect on Weld Matls & Crevice Regions in Piping
IR 07100017/201101325 November 1987Notice of Violation from Insp on 871017-1113.Violation Noted:Cold Weather Protection Procedure Had Been Signed Off as Completed & Portable Heaters or Grating Covers Not Installed
ML20236M27427 October 1987Notice of Violation from Insp on 870919-1016.Violation Noted:Failure to Document & Evaluate Test Discrepancies Noted on 870910 & 11 During Standby Liquid Control Sys Testing
ML20237H15628 August 1987Notice of Violation from Insp on 870718-0821.Violation Noted:Failure to Notify NRC within 1 H of Failure of Claiborne County Sirens & Tone Activated Receivers to Activate During Alert Notification Test
ML20235H8708 July 1987Notice of Violation from Insp on 870615-19.Violation Noted: Failure to Provide Required Training to Two Members of Emergency Organization
ML20234E7731 July 1987Notice of Violation from Insp on 870516-0619
ML20214A11830 April 1987Notice of Violation from Insp on 870314-0417Unanalyzed Condition
ML20212R34716 January 1987Notice of Violation from Insp on 870115-1219
ML20215F55717 December 1986Notice of Violation from Insp on 861018-1114
ML20213G2147 November 1986Notice of Violation from Insp on 860908-1017
ML20214U67319 September 1986Notice of Violation from Insp on 860811-15Safe Shutdown
Continuous fire watch
Fire Watch
Hourly Fire Watch
ML20214L27825 August 1986Notice of Violation from Insp on 860715-0808
ML20205D44028 July 1986Notice of Violation from Insp on 860613-0714