4 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-V-87-08 Date: 02/03/87

.This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public int. rest significance. The information presented is as initially received without virification or evaluation and is basically all that is known by Region V staff on this date.,

FACILITY: Sacramento Municipal Utility District Emergency Classification Rancho Seco Nuclear Power Plant Notification of Unusual Event {

Sacramento County, California Alert Docket No. 50-312 Site Area Emergency General Emergency X Not Applicable

SUBJECT:

INADVERTENT, LEAKAGE FROM LOWER CONTAINMENT SPRAY RING AT RANCHO SECO

~

On Monday, February 2,1987, licensee maintenance personnel were performing maintenance work (MOVATS testing) on the motor operated block valve operator for the "A" train containment spray system. An electrical clearance had been issued, but no mechanical clearance. This valvo however was the only fluid boundary between the reactor coolant system and the centainment spray rings.

During the work activity, the valve stem moved and opened the valve which permitted less than 50 gallons of primary coolant to enter the spray system and flow out the lower spray header

(

ring. The "A" spray pump did not start during this work activity.

Na personnel were contaminated during the spray. The upper spray rings are higher than the

-static head of water available at the time of the activity and therefore did not spray water out the upper spray rings.

Th3 licensee is currently decontaminating areas affected in the the containment lower level.

Ths reactor has been shut down since December 26, 1985, and is currently being cooled by the Decay Heat Removal System which was maintained without loss of flow or heat removal capability during the spray.

This information is current as of 10:00 a.m. (PST), February 3, 1987.

CONTACT: T. D'Angelo L. Miller, Jr.

(209)748-2791 FTS 463-3869 DISTRIBUTION H St. MNBB Phillips E/W Willste Air Rights Mail:

Chairman Zech ED0 NRR IE NMSS ADM:DMB Comm. Bernthal PA OIA RES COT:Trans Only Comm. Roberts MPA AE0D Comm. Asselstine OGC Comm. Carr Regions: 7.yg SECY INP0 W95 NSAC F.n ACRS Licensee:

CA (ReactorLicensees) REGION V: FORM 211 PDR Resident Inspector 1 9 f (Revised 3/14/83) _

g21g31 PNO-V-87-oO8 870203 PDR 4 ff 0/444neu cE47zy2. 7 W [h J