MONTHYEAR0CAN109902, Monthly Operating Repts for Sept 1999 for Arkansas Nuclear One,Units 1 & 2.With1999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Arkansas Nuclear One,Units 1 & 2.With ML20217G0361999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN099907, Monthly Operating Repts for Aug 1999 for Ano,Units 1 & 2. with1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Ano,Units 1 & 2. with ML20216E4941999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Jmfnp.With ML20212E7451999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Hcgs,Unit 1.With Summary of Changes,Tests & Experiments Implemented During Aug 1999.With ML20210R6031999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN089904, Monthly Operating Repts for July 1999 for Ano,Units 1 & 2. with1999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Ano,Units 1 & 2. with ML20209G0661999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With L-99-267, Monthly Operating Repts for June 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN079903, Monthly Operating Repts for June 1999 for Ano,Units 1 & 2. with1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Ano,Units 1 & 2. with L-99-023, Monthly Operating Repts for May 1999 for Jfnp Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Jfnp Units 1 & 2. with ML20196A0191999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Arkansas Nuclear One,Units 1 & 2.With L-99-020, Monthly Operating Repts for Apr 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN059903, Monthly Operating Repts for Apr 1999 for Ano,Units 1 & 2. with1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Ano,Units 1 & 2. with L-99-161, Monthly Operating Repts for Mar 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20205N0961999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20205R6351999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Ano,Units 1 & 2. with 0CAN039904, Monthly Operating Repts for Feb 1999 for Ano,Units 1 & 2. with1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Ano,Units 1 & 2. with ML20207M6421999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20203A2651999-01-31031 January 1999 Monthly Operating Repts for Jan 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20199E6591998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20199F0351998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Ano,Units 1 & 2 ML20198B2561998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20198D2441998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Ano,Units 1 & 2. with 0CAN119808, Monthly Operating Repts for Oct 1998 for Ano,Units 1 & 2. with1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Ano,Units 1 & 2. with ML20195C9681998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN109806, Monthly Operating Repts for Sept 1998 for ANO Units 1 & 2. with1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for ANO Units 1 & 2. with ML20154H6001998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20197C8991998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN099803, Monthly Operating Repts for Aug 1998 for ANO Units 1 & 2. with1998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for ANO Units 1 & 2. with 0CAN089804, Monthly Operating Repts for July 1998 for Ano,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Ano,Units 1 & 2 ML20237B1891998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Jm Farley Nuclear Plant,Units 1 & 2 ML20236M5981998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Jm Farley Nuclear Plant,Units 1 & 2 ML20236R0531998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Ano,Units 1 & 2 0CAN069802, Monthly Operating Repts for May 1998 for ANO Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for May 1998 for ANO Units 1 & 2 ML20236R0781998-05-31031 May 1998 Correction to Monthly Operating Rept for May 1998 for ANO, Unit 2 ML20248M3121998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Jm Farley Nuclear Plant,Units 1 & 2 0CAN059805, Monthly Operating Repts for Apr 1998 for Ano,Units 1 & 21998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Ano,Units 1 & 2 ML20247F3631998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Jm Farley Nuclear Plant,Units 1 & 2 ML20216D5941998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Joseph M Farley Nuclear Plant,Units 1 & 2 0CAN049802, Monthly Operating Repts for Mar 1998 for Arkansas Nuclear One,Units 1 & 21998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Arkansas Nuclear One,Units 1 & 2 ML20216D9811998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Jm Farley Nuclear Plant,Units 1 & 2 ML20217B1131998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 ML20202G4211998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Jm Farley Nuclear Plant,Units 1 & 2 0CAN029805, Monthly Operating Repts for Jan 1998 for Ano,Units 1 & 21998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Ano,Units 1 & 2 ML20217B1181998-01-31031 January 1998 Revised Monthly Operating Rept for Jan 1998 for Ano,Unit 1 ML20198L6191997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Jm Farley Nuclear Plant,Units 1 & 2 0CAN019804, Monthly Operating Repts for Dec 1997 for ANO Units 1 & 21997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for ANO Units 1 & 2 ML20203F6391997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Jm Farley Nuclear Plant,Units 1 & 2 ML20197J0851997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for ANO Units 1 & 2 1999-09-30
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217L8931999-10-31031 October 1999 Rev 1 to BAW-10235, Mgt Program for Volumetric Outer Diameter Intergranular Attack in Tubesheets of Once-Through Sgs ML20217P0761999-10-0606 October 1999 Non-proprietary, Farley Units 1 & 2 LBB Calculation Results Due to SG Replacement & SG Snubber Elimination Programs ML20212L1141999-10-0101 October 1999 Safety Evaluation Granting Request for Exemption from Technical Requirements of 10CFR50,App R,Section III.G.2.c ML20217G0361999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN109902, Monthly Operating Repts for Sept 1999 for Arkansas Nuclear One,Units 1 & 2.With1999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Arkansas Nuclear One,Units 1 & 2.With ML20216J6271999-09-27027 September 1999 Rev 0 to CALC-98-R-1020-04, ANO-1 Cycle 16 Colr ML20212F5261999-09-22022 September 1999 SER Approving Request Reliefs 1-98-001 & 1-98-200,parts 1,2 & 3 for Second 10-year ISI Interval at Arkansas Nuclear One, Unit 1 ML20216E4941999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Jmfnp.With 0CAN099907, Monthly Operating Repts for Aug 1999 for Ano,Units 1 & 2. with1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Ano,Units 1 & 2. with ML20212E7451999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Hcgs,Unit 1.With Summary of Changes,Tests & Experiments Implemented During Aug 1999.With ML20211F4281999-08-25025 August 1999 Safety Evaluation Concluding That Licensee Provided Acceptable Alternative to Requirements of ASME Code Section XI & That Authorization of Proposed Alternative Would Provide Acceptable Level of Quality & Safety ML20210T2161999-08-0606 August 1999 Draft SE Supporting Proposed Conversion of Current TS to ITS for Plant ML20211B2011999-08-0404 August 1999 Informs Commission About Results of NRC Staff Review of Kaowool Fire Barriers at Farley Nuclear Plant,Units 1 & 2 & Staff Plans to Address Technical Issues with Kaowool & FP-60 Barriers ML20210R6031999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN089904, Monthly Operating Repts for July 1999 for Ano,Units 1 & 2. with1999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Ano,Units 1 & 2. with ML20210K8831999-07-29029 July 1999 Non-proprietary Addendum B to BAW-2346P,Rev 0 Re ANO-1 Specific MSLB Leak Rates ML20209G0661999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With L-99-267, Monthly Operating Repts for June 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With 0CAN079903, Monthly Operating Repts for June 1999 for Ano,Units 1 & 2. with1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Ano,Units 1 & 2. with ML20196J3791999-06-30030 June 1999 Safety Evaluation of TR WCAP-14750, RCS Flow Verification Using Elbow Taps at Westinghouse 3-Loop Pwrs. Rept Acceptable ML20207E7231999-06-0202 June 1999 Safety Evaluation Authorizing Proposed Alternative Exam Methods Proposed in Alternative Exam 99-0-002 to Perform General Visual Exam of Accessible Areas & Detailed Visual Exam of Areas Determined to Be Suspect L-99-023, Monthly Operating Repts for May 1999 for Jfnp Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Jfnp Units 1 & 2. with ML20196A6251999-05-31031 May 1999 Non-proprietary Rev 0 to TR BAW-10235, Mgt Program for Volumetric Outer Diameter Intergranular Attack in Tubesheets of Once-Through Sgs ML20196A0191999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Arkansas Nuclear One,Units 1 & 2.With ML20195D1991999-05-28028 May 1999 Probabilistic Operational Assessment of ANO-2 SG Tubing for Cycle 14 ML20206M7711999-05-11011 May 1999 SER Accepting Relief Request from ASME Code Section XI Requirements for Plant,Units 1 & 2 ML20206G7471999-05-0404 May 1999 Safety Evaluation Accepting Corrective Actions Taken by SNC to Ensure That Valves Perform Intended Safety Functions & Concluding That SNC Adequately Addressed Requested Actions in GL 95-07 L-99-020, Monthly Operating Repts for Apr 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20206C9461999-04-30030 April 1999 1:Final Cycle 16 Freespan ODSCC Operational Assessment 0CAN059903, Monthly Operating Repts for Apr 1999 for Ano,Units 1 & 2. with1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Ano,Units 1 & 2. with ML20206F0691999-04-29029 April 1999 Safety Evaluation Accepting Licensee Re ISI Plan for Third 10-year Interval & Associated Requests for Alternatives for Plant,Unit 1 ML20205M6941999-04-12012 April 1999 Safety Evaluation Granting Relief for Second 10-yr Inservice Inspection Interval for Plant,Unit 1 L-99-161, Monthly Operating Repts for Mar 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20205N0961999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20205R6351999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Ano,Units 1 & 2. with ML20205D6061999-03-31031 March 1999 Safety Evaluation Supporting Licensee Proposed Approach Acceptable to Perform Future Structural Integrity & Operability Assessments of Carbon Steel ML20205D4711999-03-26026 March 1999 SER Accepting Util Proposed Alternative to Employ Alternative Welding Matls of Code Cases 2142-1 & 2143-1 for Reactor Coolant System to Facilitate Replacement of Steam Generators at Arkansas Nuclear One,Unit 2 ML20204D7271999-03-15015 March 1999 ISI Refueling 15,Interval 2,Period 3,Outage 3 for Jm Farley Nuclear Generating Plant,Unit 1 ML20204B1861999-03-15015 March 1999 Safety Evaluation Authorizing Licensee Request for Alternative to Augmented Exam of Certain Reactor Vessel Shell Welds,Per Provisions of 10CFR50.55a(g)(6)(ii)(A)(5) 0CAN039904, Monthly Operating Repts for Feb 1999 for Ano,Units 1 & 2. with1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Ano,Units 1 & 2. with ML20207M6421999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20212G6381999-02-25025 February 1999 Ano,Unit 2 10CFR50.59 Rept for 980411-990225 ML20203E4891999-02-11011 February 1999 Rev 1 to 97-R-2018-03, ANO-2,COLR for Cycle 14 ML20203A2651999-01-31031 January 1999 Monthly Operating Repts for Jan 1999 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20199D8611999-01-12012 January 1999 SER Accepting Relief Request for Inservice Insp Program for Plant,Units 1 & 2 ML20199E6591998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Jm Farley Nuclear Plant,Units 1 & 2.With ML20206C8081998-12-31031 December 1998 Alabama Power 1998 Annual Rept ML20199F0351998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Ano,Units 1 & 2 ML20198M7841998-12-29029 December 1998 SER Accepting Util Proposal to Use ASME Code Case N-578 as Alternative to ASME Code Section Xi,Table IWX-2500 for Arkansas Nuclear One,Unit 2 ML20198K4091998-12-18018 December 1998 COLR for Jm Farley,Unit 1 Cycle 16 1999-09-30
[Table view] |
Text
I
~.: Southern Nuciser Operating Company
, . Post Offico Box 1295 BirminDham, Alabama 35201 T,eliphon. (205) 868 5131 l . .
o.v. uor.y Southern Nudear Operating Company l Vice President Farley Project the southem electoc system -
August 9, 1996 l
l Docket Nos. 50-348 l 50-364
- l. U. S. Nuclear Regulatory Commission
- l. ATTN: Document Control Desk Washington, D C 20555 l
Joseph M. Farley Nuclear Plant Monthly Operating Report l Ladies and Gentlemen:
Attached are the July 1996 Monthly Operating Reports for Joseph M. Farley Nuclear Plant Units 1 and 2, as required by Section 6.9.1.10 of the Technical Specifications.
l If you have any questions, please advise.
Respectfully submitted, l lLt"W Dave Morey RWC:(mor)
Attachments cc: Mr. S. D. Ebneter, Region 11 Administrator
- Mr. B. L Siegel, NRR Senior Project Manager Mr. T. M. Ross, FNP Resident Inspector i 9608130309 960731
! PDR ADOCK 05000348 R PM
- 1*6T(050 i
i L
l b\
! l
i 4
Joseph M. Farley Nuclear Plant Unit 1 Narrative Summary of Operations July 1996 l
i At 1800 on July 13,1996, with the unit operating in mode 1 at 100% reactor :
power, the unit was ramped down to 33% reactor power to repair service j water leaks in Containment Coolers l A & 1C. ;
All repairs were completed and the unit was returned to 100% reactor power at 0104 on July 15,1996.
There was no major safety related maintenance performed during the month.
i I
t 4
4 i
i 1
1 I
OPERATING DATA REPORT DOCKET NO. 50-348 l
DATE August 5,1996 COMPLETED BY M. W. McAnulty_
TELEPilONE (334) 899-5156, ext.3640 OPERATING. STATUS J
- 1. Unit Name: Joseph M. Farley - Unit 1 Notes 1
- 2. Rcporting Period: July 1996 1) Cumulative data since 12-01-77, l
- 3. Licensed Thermal Power (MWt): 2,652 date of commercial operation. I
- 4. Nameplate Rating (Gross MWe): 860 l
- 5. Design Electrical Rating (Net MWe): 829 j
- 6. Maximum Dependable Capacity (Gross MWe): 855.7 )
- 7. Maximum Dependable Capacity (Net MWe): 812 j
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) 5mee Last Report, Give Reasons: N/A
- 9. Power Level To Which Restricted, If Any (Net MWe): N/A
- 10. Reasons For Restrictions,If Any: N/A i
i I
This Month Yr. to Date Cumulative l
- 11. Hours in Reporting Period 744.0 5,111.0 163,631.0
- 12. Number Of Hours Reactor Was Critical 744.0 5,082.3 131,771.7 !
- 13. Reactor Reserve Shutdown Hours 0.0 0.0 3,650.0 i
- 14. Hours Generator On-line 744.0 5,067.0 129,742.7 1
- 15. Unit Reserve Shutdown Hours 0.0 0.0 0.0
- 16. Gross Thermal Energy Generated (MWH) 1,930,947.7 13,225,667.3 333,980,040.2
- 17. Gross Electrical Energy Generated (MWH) 624,089.0 4,334,617.0 107,826,771.0
- 18. Net Electrical Energy Generated (MWH) 591,753.0 4,116,179.0 101,855,831.0
- 19. Unit Senice Factor 100.0 99.1 79.3
- 20. Unit Availability Factor 100.0 99.1 79.3_
- 21. Unit Capacity Factor (Using MDC Net) 98.0 99.2 76.7
- 22. Unit Capacity Factor (Using DER Net) 95.9 97.1 75.1
- 23. Unit Forced Outage Rate 0.0 0.0 5.7
, 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
mm
- 25. If Shut Down at End Of Report Period, Estimated Date of Startup: N/A
- 26. Units In Test Status (Prior To Commercial Operation): Forecast Achieved
, Initial Criticality 08/06/7_7 08/09/77 Initial Elcetricity 08/20/77 08/18/77 Commercial Operation 12/01/77 12/01/77
4 UNIT SilUTDOWNS AND POWER REDUCTIONS '
DOCKET NO. 50-348 UNIT NAME J. M. Farley - Unit 1 DATE August 5,1996 COMPLETED BY M. W. McAnulty i REPORT MONTil July TELEPIIONE 1334) 899-5156, ext.3640 7 _
R M E E S i
T A T Y '
Y S 11 SC
, P o O TO CAUsE AND CORRECTIVE E DURATION N D ED COMPONENT ACTION TO
! No. DATE (1) (llOURS) (2) (3) LER # ME CODE (5) PREVENT RECURRENCE in mode I at 100% reactor power, the unit was l ramped down to 33% reactor power to repair service water leaks in Containment Coolers 1 A and IC. The leaks were due to corrosion <
at the tube end area of one section on each i
, cooler. The leaks were stopped by installing jblind flanges on the leaking section of eaca cooler.
All repairs were completed and the unit was returned to 100% reactor power at 0104 on 960715.
I I
.-_t_- _ _ _ - - . - - -
1: 2: 3: EVENTS REPORTED i
[ F: Forced Reason Method INVOLVE A s: scheduled A - Equipment Failure (Explain) 1 - Manual GREATER TilAN 20%
i D Maintenance or Test 2 - Manual Scram REDUCTION IN
! C Refueling 3 - Automatic scram AVERAGE DAILY D - Regulatory Restriction 4 - Other (Explain) POWER LEVEL FOR E - Operator Training & License Examination TIIE PRECEDING 24 f Administrative llOURS.
G OperationalError(Explain) 11-Other(Explain)
DOCKET NO. 50-348 UNIT 1
. . DATE August 5,1996 :
COMPLETED BY M. W. McAnulty I TELEPHONE (334) 899-5156 ext 3640 MONTII July l l
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net) 1 818 17 816 !
2 817 18 817 :
3 815 19 815 4 819 20 810 ,
?
5 817 21 809 ,
6 815 22 811 7 814 23 813 !
t
- 8 816 24 814 9 812 25 817 ,
r l 10 817 26 817 ,
11 816 27 815 12 819 28 817 ,
13 738 29 820 t
! 14 269 30 818 i
I 15 814 31 816 16 817 1
, 1 INSTRUCTIONS On this format, list the average daily unit power level in MWe-Net for each day in the reponing period. Compute to the nearest whole megawatt.
i
1 l
l
{
l Joseph M. Farley Nuclear Plant Unit 2 Narrative Summary of Operations July 1996 There was no major safety related maintenance perfonned during the month.
1 I
I I
OPERATING DATA REPORT DOCKET NO. 50-364 DATE August 5,1996 l
COMPLETED BY M. W. McAnulty_
l TELEPIIONE (334) 899-5156, ext.3640 i
l OPERATING STATUS l
- 1. Unit Name: Joseph M. Farley - Unit 2 Notes
- 2. Reporting Period: _ July 1996 1) Cumulative data since 07-30-81,
- 3. Licensed Thermal Power (MWt)- 7652 date of commercial operation.
- 4. Nameplate Rating (Gross MWe): 860
- 5. Design Electrical Rating (Net MWe): 829 l 6. Maximum Dependable Capacity (Gross MWe): 863.6
- 7. Maximum Dependable Capacity (Net MWe): 822 j
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Smce Last Report, Give Reasons: N/A i
- ~
- 9. Power Level To Which Restricted, if Any (Net MWe): N/A ,
- 10. Reasons For Restrictions, If Any: N/A j This Month Yr. to Date Cumulative
- 11. Ilours in Reporting Period 744.0 5,111.0 _
131,544.0 l
- 12. Number Ofliours Reactor Was Critical 744.0 5,111.0- 114,014.4 l
- 13. Reactor Reserve Shutdown llours _
0.0 0.0 138.0_ l
- 14. liours Generator On-line 744.0 5,111.0 112,321.2
- 15. Unit Reserve Shutdown liours 0.0 0.0 0.0
- 16. Gross Thennal Energy Generated (MWli) 1,973,088.0 13,165,403.3 286,139,193.7
- 17. Gross Electrical Energy Generated (MWii) 640,955.0 4,322,390.0 93,784,869.0 l 18. Net Electrical Energy Generated (MWII) 610,259.0 4,112,314.0 88,925,965.0_
- 19. Unit Service Factor 100.0 100.0 85.4
- 20. Unit Availability Factor 100.0 100.0 85.4
- 21. Unit Capacity Factor (Using MDC Net) 99.8 97.9 82.5
- 22. Unit Capacity Factor (Using DER Net) _
98.9 _
97.1 81.5
- 23. Unit Forced Outage Rate 0.0 0.0 3.8 l 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
l Refueling Outage scheduled for October 12,1996 with a duration of 48 days l 25. If Shut Down at End Of Report Period, Estimated Date of Startup: N/A
- 26. Units In Test Status (Prior To Commercial Operation): Forecast Achieved Initial Criticality 05/06/81 05/08/81 Initial Electricity 05/24/81 05/25/81 Commercial Operation 08/01/81 07/30/81 i
, i UNIT SHUTDOWNS AND POWER REDUCTIONS
. 1 I
. - . DOCKET NO. 50-364 UNIT NAME .I. M. Farley - Unit 2 DATE August 5,1996 COMPLETED BY M. W. McAnuity REPORT MONTil - July TELEPilONE (334) 899-5156, ext.3640 R M E E S T A T Y Y S II SC P O O TO CAUSE AND CORRECTIVE E DURATION N D ED COMPONENT ACTION TO NO. DATE (1) (IIOURS) (2) (3) LER # ME CODE ($) PREVENT RECURRENCE I L. -
_ _.d There were no Shutdowns Or power reductions during the month.
1 I
4 l
I i: 2: 3: EVINTS REPORTED F: Forced Reason Method INVOLVE A S: Scheduled A - Equipment failure (Explain) 1 - Manual GREATER TilAN 20%
B - Maintenance or Test 2 - Manual Scram REDUCTION IN C Refueling 3 - Automatic Scram AVERAGE DAILY D - Regulatory Restriction 4 Other(Explain) POWER LEVEL rOR E - Operator Training & License Examination TIIE PRECEDINO 24 F- Administrative llOURS. j G Operational Error (Explain)
II-Other(Explain) !
.- i l
DOCKET NO. 50-364
- UNIT 2 August 5,1996
. _ ,, DATE COMPLETED BY M. W. McAnuity l TELEPHONE (334) 899-5156 ext 3640 l
MO'4TH July l DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net) j I 822 17 821 ,
2 820 18 820 3 820 19 819 l
l 4 824 20 814 l
l 5 821 21 814 l
6 819 22 816 7 817 23 818 )
8 821 24 820 9 817 25 823 10 823 26 823 11 _
822 27 820 12 823 28 823 13 820 29 826 I
14 818 30 823 15 820 31 822_
16 822 INSTRUCTIONS On this format, list the average daily unit power level in MWe-Net for each day in the reporting period. Compute to the nearest whole megawatt.