MONTHYEARML0419603922004-07-0909 July 2004 Request for Additional Information, Revising the Licensing Bases to Utilize the Alternate Source Term Project stage: RAI ML0515205422005-06-0101 June 2005 Notice of Meeting with Florida Power and Light, St. Lucie, Units 1 & 2, Alternate Source Term and Related Licensing Actions Project stage: Request ML0517405162005-07-0707 July 2005 Summary of Public Meeting with FPL Regarding Alternate Source Term Amendment Requests Project stage: Meeting ML0526405242005-09-22022 September 2005 Ltr., Withdrawal of Amendment Request for Utilizing Alternative Source Term for Revising License Bases (Tac No. MC0882 and MC0883) Project stage: Withdrawal 2005-06-01
[Table View] |
|
---|
Category:Meeting Summary
MONTHYEARML23166A0042023-06-15015 June 2023 Summary of Meeting Concerning 2023 Annual Assessment of the Saint Lucie and the Turkey Point Nuclear Plants ML23107A2312023-04-18018 April 2023 Summary Meeting with Florida Power and Light/Nextera on Improved Technical Specification Conversion License Amendment Requests ML23097A1642023-04-17017 April 2023 Summary of March 23, 2023, Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specifications Conversion License Amendment Requests ML23066A0872023-03-15015 March 2023 Summary of Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specifications Conversion License Amendment Requests ML23069A0282023-03-15015 March 2023 Summary of January 31, 2023, Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specifications Conversion License Amendment Requests ML23044A4172023-03-0606 March 2023 Summary of January 17, 2023, Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specifications Conversion License Amendment Requests ML22357A0742023-01-19019 January 2023 Summary of December 1, 2022, Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specification Conversion License Amendment Requests ML22350A7082023-01-17017 January 2023 Summary of November 21, 2022, Presubmittal Meeting with Florida Power and Light on St. Lucie License Amendment Request to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems, and Components ML22327A2402022-12-0808 December 2022 Summary of October 27, 2022, Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specification Conversion License Amendment Requests ML22263A0122022-09-27027 September 2022 Summary of August 29, 2022, Meeting with Florida Power and Light on St. Lucie and Turkey Point Improved Technical Specification Conversion License Amendment Requests (EPID Nos. L-2021-LLI-0000 and L 2021 Lli 0002) ML22144A0022022-09-14014 September 2022 Summary of February 16, and May 18, 2022, Meetings with Nextera Energy/Florida Power & Light Company Regarding Planned Submittal of License Amendment Request for a Common Fleet Emergency Plan ML22229A5252022-08-24024 August 2022 Summary of August 11, 2022, Mtg. with Florida Power & Light/Nextera on St. Lucie and Turkey Point Improved Technical Specification Conversion License Amendment Request (EPIDs L-2021-LLI-0000 & -0002) ML22145A3932022-05-25025 May 2022 Public Meeting Summary 2021 Annual Assessment Meeting 20220434 ML22020A4032022-02-0707 February 2022 Summary of November 17, 2021, Meeting with Florida Power and Light/Nextera on Improved Technical Specification Conversion License Amendment Requests (EPIDs L-2021-LLI-0000 and L-2021-LLI-0002) ML22020A4052022-01-24024 January 2022 Summary of January 14, 2022, Teleconference with Florida Power & Light Co. Regarding Verbal Authorization of Request for Alternative to the Requirements of ASME Code for Examination of Closure Head CEDM Housing 27 Canopy Seal Weld ML21342A3752022-01-0606 January 2022 Summary of Meeting with Florida Power and Light/Nextera on Proposed Improved Technical Specification Conversions ML21337A1962021-12-16016 December 2021 Public Scoping Meeting Summary for the Environmental Review of the Subsequent License Renewal Application for St. Lucie Plant, Units 1 and 2 ML21337A2062021-11-0303 November 2021 Environmental Scoping Meeting Related to the St. Lucie Plant, Units 1 and 2, Subsequent License Renewal Application ML21173A2922021-07-0909 July 2021 5-20-21 St. Lucie Plant Units 1 & 2 Subsequent License Renewal Environmental Pre-Application Meeting Summary ML21176A0552021-06-29029 June 2021 Subsequent License Renewal Application - 2nd Public Meeting Summary of Pre-Submittal Meeting ML21159A1352021-06-0808 June 2021 Public Meeting Summary Regarding the Saint Lucie Nuclear Plant, Units 1 and 2, Docket No. 50-335 and 389, and the Turkey Point Nuclear Generating Station Units 3 and 4, Docket No. 50-250 and 50-251; Meeting Number 20210505 ML21127A2182021-05-11011 May 2021 Subsequent License Renewal Application - Public Meeting Summary of Pre-Submittal Meeting ML21092A1022021-04-13013 April 2021 Summary of Pre-Application Meeting to Discuss Planned License Amendments Regarding Conversion to Improved Technical Specifications for the Turkey Point Nuclear Generating, Unit Nos.3 and 4 and St. Lucie Plant, Unit Nos. 1 and 2 Facilities ML20044E6802020-02-20020 February 2020 Summary of February 10, 2020, Teleconference with Florida Power and Light Company St, Lucie, Unit 2 - Regarding Verbal Authorization of Request to Use ASME Code Case N-513-4 for Alternate Repair of Intake Cooling Water System ML20034F2862020-02-0303 February 2020 Summary of January 29, 2020, NRC-NMFS Teleconference Regarding St. Lucie Endangered Species Act Consultation ML19221B6742019-08-13013 August 2019 Summary of Teleconference with Florida Power & Light Company Regarding Verbal Authorization of Request for Alternative Repair of the 2B Boric Acid Makeup Pump ML19149A5942019-07-0808 July 2019 Summary of March 13, 2019, Meeting with Florida Power & Light Company Regarding a Planned License Amendment Request for St. Lucie Plant, Unit 2 ML19121A6102019-05-0101 May 2019 Public Meeting Summary - St Lucie Nuclear Plant, Docket Nos. 50-389 and 50-335 ML18242A3552018-09-21021 September 2018 Summary of Meeting with Florida Power & Light Company Regarding Planned License Amendment Requests for Turkey Point Nuclear Generating Unit Nos. 3 and 4 and St. Lucie Plant, Unit Nos. 1 and 2 ML18135A2462018-05-31031 May 2018 Summary of April 24, 2018, Meeting with Florida Power & Light Company/Nextera Energy Regarding Planned Submittal of License Amendment Request to Adopt Standard Technical Specification 3.0.6 ML18136A9052018-05-31031 May 2018 Summary of April 25, 2017, Meeting with Florida Power & Light Company/Nextera Energy Regarding Planned Submittal of Exemption Requests to Support Closure of NRC Generic Safety Issue 191/NRC Generic Letter 2004-02 ML18144A1452018-05-24024 May 2018 Public Meeting Summary - St. Lucie Nuclear Plant Docket Nos. 50-335 and 50-389 ML18122A1952018-05-17017 May 2018 Summary of Meeting with Florida Power & Light Company Regarding a Planned License Amendment Request for St. Lucie Nuclear Plant Unit 2 ML17310B2062017-11-20020 November 2017 Summary of September 20, 2017, Meeting with Florida Power & Light Company and NextEra Energy Regarding Closure of NRC Generic Safety Issue 191/NRC Generic Letter 2004-02 ML17291A0452017-11-0606 November 2017 Summary of Meeting with Florida Power and Light Company, Regarding Planned License Amendment Requests for St. Lucie Plants, Units 1 and 2 and Turkey Point Nuclear Generating Unit Nos. 3 and 4 ML17216A1732017-09-0707 September 2017 Notice of Meeting with Florida Power & Light Company and NextEra Energy to Discuss Closing Out Generic Safety Issue-191 and Generic Letter 2004-02 ML16097A1302016-04-0404 April 2016 March 29, 2016 Summary of Public Meeting - 2015 Annual Assessment Regarding Saint Lucie ML15188A3402015-07-13013 July 2015 Summary of Closed Meeting with Florida Power and Light Company and Areva Regarding Request for Additional Information for the License Amendment and Exemption Requests Re. the Transitioning to Areva Fuel ML15086A2232015-03-27027 March 2015 Summary of Meeting Concerning the Annual Assessment of St. Lucie Nuclear Plant, Units 1 and 2 ML14163A6522014-06-19019 June 2014 Summary of May 29, 2014, Public Meeting with NextEra Energy, Inc. and Florida Power & Light Company Regarding Proposed Amendment to Transition Fuel Type at St. Lucie Unit 2 ML13225A2932013-08-12012 August 2013 7/23-24/2013, Summary of Meeting 2013 U.S. Nuclear Regulatory Commission (NRC) Initial Exam Writers' Workshop ML13107B4002013-04-17017 April 2013 Summary of Public Meeting, Florida Power & Light, St. Lucie Nuclear Plant ML13095A3472013-04-11011 April 2013 3/14/2013 - Summary of Meeting with Florida Power & Light Co., to Discuss Insights About the Performance of the Steam Generators at St. Lucie Plant, Unit No. 2 After Three Operating Cycles ML13084A0302013-04-0404 April 2013 9/13/2012 - Summary of Conference Call with Florida Power & Light Co. Re. the Findings of the Fall 2012 Steam Generator Tube Inspections at Saint Lucie Plant, Unit No. 2 ML13077A4482013-03-27027 March 2013 7/27/11 Summary of Conference Call with Florida Power and Light Co. Re Findings of the Spring 2011 SG Tube Inspections for St. Lucie Unit 2 ML12326A8162012-11-21021 November 2012 11/9/2012 - Summary of Meeting with the Florida Power and Light Company Regarding the St. Lucie Nuclear Plant ML12258A0802012-09-14014 September 2012 NRC Conference Call St. Lucie Unit 2 Steam Generator Inspection September 13, 2012 ML12171A3082012-06-18018 June 2012 E-mail Re Draft Summary of 05-31-12 Phone Call ML12150A2992012-06-0505 June 2012 May 17, 2012, Summary of Teleconference Held Between the U.S. Nuclear Regulatory Commission, U.S. Fish and Wildlife Service, and Florida Power & Light Co. to Discuss the Terms of the Biological Opinion at the St. Lucie Plant, Units 1 and 2 ML12171A1932012-05-23023 May 2012 5/16/2012 - Public Meeting Summary - Category 3- Annual Assessment Meeting - St. Lucie Nuclear Plant 2023-06-15
[Table view] |
Text
July 7, 2005 LICENSEE: Florida Power and Light Company FACILITY: St. Lucie Plant, Units 1 and 2
SUBJECT:
SUMMARY
OF JUNE 14, 2005, PUBLIC MEETING WITH FLORIDA POWER AND LIGHT COMPANY ON ALTERNATE SOURCE TERM AMENDMENT REQUESTS (TAC NOS. MC0882 AND MC0883)
On June 14, 2005, a Category 1 meeting was held among the U.S. Nuclear Regulatory Commission (NRC) and representatives of the Florida Power and Light Company (FPL) and its contractor (NAI) at NRC Headquarters, One White Flint North, 11555 Rockville Pike, Rockville, Maryland. The purpose of the meeting was to discuss the status of proposed license amendments to adopt the alternate source term (AST) at St. Lucie Units 1 and 2. The meeting was open to the public as stated in the meeting notice dated June 1, 2005 (ML051520542).
There were no members of the public present. Enclosure 1 is a list of attendees.
The Project Manager reviewed the status of the requests, which had been submitted in September 2003. An extensive Request for Additional Information (RAI) was issued in July 2004 and responded to in September 2004, but there were still many open issues that needed to be resolved. Work on the full amendment requests was effectively suspended in the fall of 2004 so that the NRC and FPL staffs could concentrate on the portion of the Unit 2 request needed to support issuance of a steam generator (SG) tube plugging amendment for the January 2005 outage. Partial approval of AST for Unit 2 was included in the January 31, 2005, amendment approving the increase in SG tube plugging.
Following a discussion of the status and scope of work remaining, there was general agreement that resuming review of the current submittals would probably not be the most effective approach, given the number of open issues and the need for additional RAIs before review could resume. Also, completion of the review would involve the same NRC and FPL staff resources needed to focus on other higher priority licensing actions required to support upcoming outages, including a proposed amendment to further increase the SG tube plugging limit at St. Lucie Unit 2.
The FPL staff stated that they would recommend to their management that the requests be withdrawn and resubmitted after completing the higher priority work. Prior to the next submittal, the NRC and FPL staffs agreed to meet to clarify the relevant current licensing bases and discuss staff expectations for review. Withdrawal of the requests would not affect the portion of the Unit 2 AST that was approved in January 2005.
2 Please direct any inquiries regarding the June 14, 2005, meeting to me at (301) 415-3974 or btm3@nrc.org.
/RA/
Brendan T. Moroney, Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-335 and 50-389
Enclosure:
List of Attendees cc w/encl: See next page
ATTENDANCE LIST NUCLEAR REGULATORY COMMISSION STAFF MEETING WITH FLORIDA POWER AND LIGHT COMPANY AT NRC HEADQUARTERS JUNE 14, 2005 NRC FPL M. Marshall T. Patterson B. Moroney G. Madden J. Arroyo J. Kabadi R. Dennig C Wasik A. Drozd V. Rubano M. Blumberg H. Walker FPL Consultant J. Harrell, NAI ENCLOSURE
ML051740516 NRC-001 OFFICE PDII-2\PM PDII-2\LA PDII-2\SC NAME BMoroney BClayton DPickett for MMarshall DATE 07/05/05 06/27/05 07/07/05 Florida Power and Light Company ST. LUCIE PLANT cc:
Mr. J. A. Stall Mr. William Jefferson, Jr.
Senior Vice President, Nuclear and Site Vice President Chief Nuclear Officer St. Lucie Nuclear Plant Florida Power and Light Company 6351 South Ocean Drive P.O. Box 14000 Jensen Beach, Florida 34957 Juno Beach, Florida 33408-0420 Mr. G. L. Johnston Senior Resident Inspector Plant General Manager St. Lucie Plant St. Lucie Nuclear Plant U.S. Nuclear Regulatory Commission 6351 South Ocean Drive P.O. Box 6090 Jensen Beach, Florida 34957 Jensen Beach, Florida 34957 Mr. Terry L. Patterson Craig Fugate, Director Licensing Manager Division of Emergency Preparedness St. Lucie Nuclear Plant Department of Community Affairs 6351 South Ocean Drive 2740 Centerview Drive Jensen Beach, Florida 34957 Tallahassee, Florida 32399-2100 David Moore, Vice President M. S. Ross, Managing Attorney Nuclear Operations Support Florida Power & Light Company Florida Power and Light Company P.O. Box 14000 P.O. Box 14000 Juno Beach, FL 33408-0420 Juno Beach, FL 33408-0420 Marjan Mashhadi, Senior Attorney Mr. Rajiv S. Kundalkar Florida Power & Light Company Vice President - Nuclear Engineering 801 Pennsylvania Avenue, NW. Florida Power & Light Company Suite 220 P.O. Box 14000 Washington, DC 20004 Juno Beach, FL 33408-0420 Mr. Douglas Anderson Mr. J. Kammel County Administrator Radiological Emergency St. Lucie County Planning Administrator 2300 Virginia Avenue Department of Public Safety Fort Pierce, Florida 34982 6000 Southeast Tower Drive Stuart, Florida 34997 Mr. William A. Passetti, Chief Department of Health Bureau of Radiation Control 2020 Capital Circle, SE, Bin #C21 Tallahassee, Florida 32399-1741