Summary of Telephone Conference Held on September 22, 2004, Between the U.S. Nuclear Regulatory Commission and the Tennessee Valley Authority Concerning Browns Ferry Nuclear Plant, Units 1, 2 and 3, LRA
ML042990519
Person / Time
Site: Browns Ferry  
Issue date: 10/21/2004
From: Yoira Diaz-Sanabria
NRC/NRR/DRIP/RLEP
To:
Tennessee Valley Authority
DIAZ-SANABRIA, Y /NRR/DRIP/RLEP 415-1594
References
TAC MC1704, TAC MC1705, TAC MC1706
Download: ML042990519 (10)


Text

October 21, 2004 LICENSEE:

TENNESSEE VALLEY AUTHORITY FACILITY:

BROWNS FERRY NUCLEAR PLANT UNITS 1, 2 AND 3

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCE CALL HELD ON SEPTEMBER 22, 2004, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND THE TENNESSEE VALLEY AUTHORITY CONCERNING BROWNS FERRY NUCLEAR PLANT, UNITS 1, 2 AND 3, LICENSE RENEWAL APPLICATION (TAC NOS. MC1704, MC1705 AND MC1706)

The U.S. Nuclear Regulatory Commission staff and representatives of Tennessee Valley Authority (TVA or the applicant) held a telephone conference call on September 22, 2004, to discuss questions related to Sections 2.3.2 and 2.3.3 of the Browns Ferry Nuclear Plant (BFN) license renewal application.

The conference call was useful in clarifying the intent of the staffs questions. On the basis of the discussion, the applicant was able to understand the staff's questions. The NRC staff acknowledged the applicants discussion and indicated that the clarification was understood. No staff decisions were made during the telephone conference call. In some cases, the applicant agreed to provide information for clarification. contains a listing of the questions discussed with the applicant. Enclosure 2 provides a list of the telephone conference call participants. The applicant has had an opportunity to comment on this summary.

/RA/

Yoira K. Diaz Sanabria, Project Manager License Renewal Section A License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket Nos. 50-259, 50-260 and 50-296

Enclosures:

As stated cc w/encls: See next page

October 21, 2004 LICENSEE:

TENNESSEE VALLEY AUTHORITY FACILITY:

BROWNS FERRY NUCLEAR PLANT UNITS 1, 2 AND 3

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCE CALL HELD ON SEPTEMBER 22, 2004, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND THE TENNESSEE VALLEY AUTHORITY CONCERNING BROWNS FERRY NUCLEAR PLANT, UNITS 1, 2 AND 3, LICENSE RENEWAL APPLICATION (TAC NOS. MC1704, MC1705 AND MC1706)

The U.S. Nuclear Regulatory Commission staff and representatives of Tennessee Valley Authority (TVA or the applicant) held a telephone conference call on September 22, 2004, to discuss questions related to Sections 2.3.2 and 2.3.3 of the Browns Ferry Nuclear Plant (BFN) license renewal application.

The conference call was useful in clarifying the intent of the staffs questions. On the basis of the discussion, the applicant was able to understand the staff's questions. The NRC staff acknowledged the applicants discussion and indicated that the clarification was understood. No staff decisions were made during the telephone conference call. In some cases, the applicant agreed to provide information for clarification. contains a listing of the questions discussed with the applicant. Enclosure 2 provides a list of the telephone conference call participants. The applicant has had an opportunity to comment on this summary.

Yoira K. Diaz Sanabria, Project Manager License Renewal Section A License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket Nos.: 50-259, 50-260 and 50-296

Enclosures:

As stated cc w/encls: See next page ADAMS Accession No.: ML042990519 DISTRIBUTION:

See next page Document Name:E:\\Filenet\\ML042990519.wpd OFFICE PM:RLEP LA:RLEP SC:RLEP NAME Y. Diaz-Sanabria Y. Edmonds S. Lee DATE 10/21/04 10/21/04 10/21/04 OFFICIAL RECORD ONLY

DISTRIBUTION: Dated: October 21, 2004 Accession No: ML042990519 HARD COPY:

RLEP RF Y. Diaz-Sanabria (PM)

R. Subbaratnam (PM)

E-MAIL:

RidsNrrDrip RidsNrrDe RidsNrrDssa RidsNrrDipm C. Li Y. L. (Renee) Li RLEP Staff K. Jabbour C. Julian (RII)

S. Cahill (RII)

A. Hodgdon C. Carpenter D. Coe E. Kleeh A. Howe J. Raval R. Goel BROWNS FERRY NUCLEAR (BFN) PLANT, UNITS 1, 2 AND 3 LICENSE RENEWAL APPLICATION DRAFT REQUEST FOR ADDITIONAL INFORMATION (D-RAI)

SCOPING AND SCREENING RESULTS OF MECHANICAL SYSTEMS SECTIONS 2.3.2 AND 2.3.3 Containment System: Reactor Building Ventilation Subsystem D-RAI 2.3.2.1-1 For Browns Ferry Nuclear Plant, Units 1, 2 and 3 Containment System (Reactor Building Ventilation System), described in license renewal application (LRA) Section 2.3.2.1 and on LRA Drawings 1-47E865-1-LR, 1-47E865-3-LR, 2-47E2865-12-LR, 2-47E610-64-1-LR, 3-47E865-12-LR, and 3-47E610-64-1-LR, LRA Table 2.3.2.1, Containment System and LRA Table 3.2.2.1, Containment System-Summary of Aging Management Evaluation do not contain all the components of the reactor building ventilation system as highlighted on the drawing. For example, while the tables list bolting, ductwork, fittings, etc., they do not list housings for air cooling units, dampers and damper housings, cooling coil housings, nor valve bodies, just to name a few. Clarify whether these components and all other applicable components of the system, are within the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If these components are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate LRA tables. If these components are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

For BFN Units 1, 2, and 3 LRA, none of the air intake or exhaust structures except for LRA Section 2.3.3.8, Ventilation System, include intake and exhaust screens within the scope of license renewal. Clarify whether screens for air intake and exhaust structures, for those systems described in LRA Section 2.3.2.1 are in the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If screens for intake and exhaust structures are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate tables. If screens for intake and exhaust structures are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

Discussion: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI 2.3.2.1-1.

Standby Gas Treatment System D-RAI 2.3.2.2-1 For BFN Units 1, 2 and 3 Standby Gas Treatment System, described in LRA Section 2.3.2.2 and on LRA Drawing 0-47E865-11-LR, LRA Table 3.2.2.2, Standby Gas Treatment System and LRA Table 2.3.2.2, Standby Gas Treatment System-Summary of Aging Management Evaluation do not contain all the components of the system as highlighted on the drawing. For example, while the tables list bolting, ductwork, fittings, etc., they do not list fan housings, filter housing, damper housing nor valve bodies, just to name a few. Clarify whether these components and all other applicable components of the system, including duct sealants, wall sealants, pressure boundary sealants, etc., are within the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If these components are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate LRA tables. If these components are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

Also, provide clarification for the following LRA Drawing 0-47E865-11-LR that shows an interface (incoming arrow) at location H-3 indicating that incoming flow is from 1-47E865-1 at location F8, while interface drawing 1-47E865-1 shows Detail 1F1 at location F-8 with incoming flow from 0-47E865-1, H-2.

For BFN Units 1, 2, and 3 LRA, none of the air intake or exhaust structures except for LRA Section 2.3.3.8, Ventilation System, include intake and exhaust screens within the scope of license renewal. Clarify whether screens for air intake and exhaust structures, for those systems described in LRA Section 2.3.2.2 are in the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If screens for intake and exhaust structures are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate tables. If screens for intake and exhaust structures are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

Discussion: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI 2.3.2.2-1.

Containment Inerting System D-RAI 2.3.2.6-1 The containment inerting system is described in LRA Section 2.3.2.6 and depicted on LRA Drawings 1-47E860-1-LR, 2-47E860-1-LR, and 3-47E860-1-LR, respectively, for BFN Units 1, 2 and 3. However, the system components including piping, valves and equipments between (1) FCV76-17 and PCV 67-14 including downstream bypass line after BYV-76-542, and (2) between CKV-76-653 and CKV-76-659 are not shown within the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If these components are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate LRA Tables 2.3.2.6 and 3.2.2.6. If these components are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

Discussion: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI 2.3.2.6-1.

Ventilation System: Radioactive Waste Building and Diesel Generator Ventilation Systems D-RAI 2.3.3.8-1 Subsystem and Diesel Generator Ventilation Subsystem. For BFN Units 1, 2 and 3 Ventilation System, described in LRA Section 2.3.3.8 and on LRA Drawings 3-47E865-8-LR, 0-47E865-6-LR and 0-47E865-8-LR, LRA Table 2.3.3.8, Ventilation System and LRA Table 3.3.2.8, Ventilation System-Summary of Aging Management Evaluation do not contain all the components of the system, as highlighted on the drawings. For example, while the tables list bolting, ductwork, fittings, etc., they do not list damper housings including fire damper housings, fan housings, air intake or exhaust structures including screens, nor supply and exhaust grills just to name a few. Clarify whether these components and all other applicable components of the system are within the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If these components are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate LRA tables. If these components are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

Discussion: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI 2.3.3.8-1.

Heating, Ventilation, and Air Conditioning System (HVAC)

D-RAI 2.3.3.9-1 For BFN Units 1, 2 and 3 HVAC System, described in LRA Section 2.3.3.9 and on LRA Drawings 0-47E865-2-LR, 0-47E865-4-LR, 0-47E865-15-LR, 0-47E866-3-LR, 1-47E1865-4-LR, 2-47E2865-4-LR, 3-47E865-4-LR, and 3-47E3865-4-LR, 3-47E865-8-LR, LRA Table 2.3.3.9, Heating, Ventilation, and Air Conditioning System and LRA Table 2.3.3.9, Heating, Ventilation, and Air Conditioning System-Summary of Aging Management Evaluation do not contain all the components of the system as highlighted on the drawings. For example, while the tables list bolting, ductwork, fire dampers, fittings, flexible connectors, etc., they do not list fan housings, filter housings, cooling coil housings, damper housings including fire damper housings, metal lath screens, nor valve bodies, supply and return grills just to name a few.

Clarify whether these components and all other applicable components of the system, including duct sealants, wall sealants, pressure boundary sealants, etc., are within the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If these components are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate LRA tables. If these components are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

For BFN Units 1, 2, and 3 LRA, none of the air intake or exhaust structures except for LRA Section 2.3.3.8, Ventilation System, include intake and exhaust screens within the scope of license renewal. Clarify whether screens for air intake and exhaust structures, for those systems described in LRA Section 2.3.3.9, are in the scope of license renewal in accordance with 10 CFR 54.4(a), and subject to aging management review in accordance with 10 CFR 54.21(a)(1). If screens for intake and exhaust structures are in the scope of license renewal, update the LRA by providing the applicable information in the appropriate tables. If screens for intake and exhaust structures are excluded from the scope of license renewal and not subject to an AMR, provide justification for the exclusion.

Discussion: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI 2.3.3.9-1.

Turbine building HVAC System D-RAI 2.3.3.9-2 Final Safety Analysis Report (FSAR) Section 10.12.5.2, Turbine building, is included as part of the HVAC systems but not included in the LRA. Provide justification for the exclusion of turbine building ventilation system from the scope of the license renewal in accordance with 10 CFR 54.4, and subject to an AMR in accordance with 10 CFR 54.21.

Discussion: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI 2.3.3.9-2.

LIST OF PARTICIPANTS FOR TELEPHONE CONFERENCE TO DISCUSS BROWNS FERRY NUCLEAR PLANT, UNITS 1, 2 AND 3 LICENSE RENEWAL APPLICATION DRAFT REQUESTS FOR ADDITIONAL INFORMATION September 22, 2004 Participants Affiliation Yoira Diaz U.S. Nuclear Regulatory Commission (NRC)

Raj Goel NRC Janak Raval NRC Ram Subbaratnam NRC Ken Brune Tennessee Valley Authority (TVA)

Don Arp TVA Roger Jennings TVA Valarie Smith TVA

Tennessee Valley Authority BROWNS FERRY NUCLEAR PLANT cc:

Mr. Karl W. Singer Chief Nuclear Officer and Executive Vice President Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Ashok S. Bhatnagar, Senior Vice President Nuclear Operations Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. James E. Maddox, Vice President Engineering & Technical Services Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Michael D. Skaggs, Site Vice President Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL 35609 General Counsel Tennessee Valley Authority ET 11A 400 West Summit Hill Drive Knoxville, TN 37902 Mr. John C. Fornicola, Manager Nuclear Assurance and Licensing Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Kurt L. Krueger, Plant Manager Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL 35609 Mr. Jon R. Rupert, Vice President Browns Ferry Unit 1 Restart Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL 35609 Mr. Robert G. Jones Browns Ferry Unit 1 Plant Restart Manager Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL 35609 Mr. Mark J. Burzynski, Manager Nuclear Licensing Tennessee Valley Authority 4X Blue Ridge 1101 Market Street Chattanooga, TN 37402-2801 Mr. Timothy E. Abney, Manager Licensing and Industry Affairs Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL 35609 Mr. Bobby L. Holbrook Senior Resident Inspector U.S. Nuclear Regulatory Commission Browns Ferry Nuclear Plant 10833 Shaw Road Athens, AL 35611-6970 State Health Officer Alabama Dept. of Public Health RSA Tower - Administration Suite 1552 P.O. Box 303017 Montgomery, AL 36130-3017 Chairman Limestone County Commission 310 West Washington Street Athens, AL 35611

Tennessee Valley Authority BROWNS FERRY NUCLEAR PLANT cc:

Mr. Fred Emerson Nuclear Energy Institute 1776 I St., NW, Suite 400 Washington, DC 20006-2708 Ken Brune, Manager Browns Ferry License Renewal Project Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801