PHIPPS BEND NUCLEAR PLANT NCR CEB 79-17 REPORT NO. 2 (INTERIM)

TENSILE ANC90R CAPACITIES LOWER THAN ASSUMED IN DESIGN ALLOWABLES Description of Deficiency Progressive cracking of the heat affected zone of welded stud anchors in flexible plate connections has occurred in TVA general research and development program tests. This results in lower tensile anchor capacities than assumed in establishing design allowables.

Interim Progress _

TVA has completed its testing program The data is for weldedbeing presently stud evaluated anchors with flexible plate connections. We anticipate and corrective action will be taken as necessary. b 21, 1979.

transmitting the final report to the NRC on or before Decem er 704i 213 790828cGu