Ro:On 800819,fire Support Group Tripped Fire Protection Deluge Valve on 50-ft Elevation of Diesel Generator Bldg in Ventilation Intake Fan Room.Valve Actuator Arm Facing Seal Found Cracked & Actuator Solenoid Relay Misadjusted
ML19338D567
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 09/15/1980
From: Tollison A
CAROLINA POWER & LIGHT CO.
To:
References
BSEP-80-1501, NUDOCS 8009230459
Download: ML19338D567 (1)


Text

-

gpm Carolina Power & Light Company Company correspondence Brunswick Steam Electric Plant P. O. Box 10429 Southport. N. C. 28461 September 15, 1980 FILE: B09-13516 SERIAL: BSEP/80-1501 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II, Suite 310D 101 Marietta Street Atlanta, Georgia 30303 BRUNSWICK STEAM ELECTRIC PLANT, U' NIT NCS. 1 & 2 LICENSE NOS. DPR-71 AND DPR-62 DCCKET NOS. 50-325 AND 50-324 Special Report Per Technical Soecification 6.9.2d

Dear Mr. O'Reilly:

As required by Technical Specificatiot.s 3.7.7.5a and 6.9.2d, Carolina Power and Light Company is submitting the following special report.

On August 19, 1980, the' plant fire support group accidently tripped a fire pro-tection deludge valve on the 50-foot elevation of the diesel generator building )

in the ventilation intake fan room, while attempting to clear a fire protection l alarm annunciator. An examination of the valve revealed the valve actuator arm l facing seal was cracked and the actuator solenoid relay misadjusted. The seal was replaced and the solenoid relay properly aligned, the valve was reset, and ,

the syste= vas returned to service. '

Very truly yours,

/

A. C. Tollison, Jr., General Manager Brunswick Steam Electric Plant MJP/ meg ec: Mr. R. A. Hartfield Mr. V. Stello, Jr. / 3