Special Rept 1-SR-90-001:on 900103,technician Opened Cabinet Door to 4,160 Volt Contactor Cabinet for motor-driven Fire Pump,Resulting in Operating Fire Pump Trip.Technician Immediately Closed Cabinet Door.Power Supplies Reenergized
ML20005G146
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 01/04/1990
From: Harness J
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
1-SR-90-001, 1-SR-90-1, BSEP-90-0006, BSEP-90-6, NUDOCS 9001180193
Download: ML20005G146 (1)


Text

_ _ _ _ _ _

w w ,

A l-r .

Carolina Power & Light Company Brunswick Nuclear Project "

P. O. Box 10429 Southport, NC 28461-0429 M 4 1990 FILE: B09-135100 SERIAL: BSEP/90-0006 U.S. Nuclear Regulatory Commission A'ITN: Document Control Desk Washington, DC 20555 ,

BRUNSWICR STEAM ELECTRIC PLANT UNIT 1 ,

DOCKET NO. 50-325 LICENSE NO. DPR-71 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.7.1 AND PURSUANT TO TECHNICAL SPECIFICATION 6.9.2 (1-SR-90-001)

Gentlemen:

In accordance with Technical Specification 3.7.7.1, Action b.3.and per telecom with Bob Carrol, NRC Region II Administrator, on January 3, 1990, at 1500, this special report is being submitted.

The diesel-driven fire pump was under clearance for performance of yearly maintenance. :After completing a preventative maintenance evolution on a low

' pressure switch for the diesel-driven pump, an Instrumentation and Control F -(160). technician opened the cabinet door to the 4160 volt contactor cabinet

.for the motor-driven fire pump to locate its associated low pressure switch.

4--

The preventative maintenance evolution was scheduled for the motor-driven switch the next day and the technician was verifying-its location. At the time the door was opened, the motor-driven fire pump was operating to support flushing of tho' hydrants and lines. Upon opening the cabinet door, a safety interlock tripped the operating fire pump. . The 150 technician immediately closed the cabinet door. The power supplies to the motor-dr!.ven pump were deenergized at,1106 until it was confirmed that the door was safely secured.

At 1116,.the power supplies were reenergized and the motor-driven fire pump was restored'to operable status. Operations personnel in the area investigated the cause of the trip and informed the Unit 1 Shift Foreman of the event.

Very truly yours, t