Ro:Fire Door A62,located in Auxiliary Bldg Was Determined Nonfunctional in Excess of 7 Days.Caused by Damaged Door Frame,Preventing Door from Completely Closing & Latching. Fire Watch Coverage Ordered,Pending Repair
ML20009G097
Person / Time
Site: Sequoyah Tennessee Valley Authority icon.png
Issue date: 06/19/1981
From: Green H
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8108030323
Download: ML20009G097 (2)


Text

---

n .

-r

~ Oppyg,iT..

i; i &

1750 Chectnut Street Tower II June 19, 1981 '5*

Mr. James P. O'Reilly, Director U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

TENNESSEE VALLEY AUTHORITY - SEQUOYAH NUCLEAR PLANT UNIT 1 - DOCKET No. 50-327 - FACILITY OPERATING LICENSE DPR SPECIAL REPORT 81-5 The enclosed special report provides information concerning a fire door being non-functional for a period in excess of seven days. This report is submitted .a accordance with Sequoyah unit 1 Technical Specification 3.7.12.

Very truly yours, ,.

TENNESSEE VALLEY AUTHORITY d 1? ~/

x 0: .

[ sA\

l A

f. G e
iW '(

9

-j \ QVL I. J. Gree irector of Nuclear Power .

4 "iW, ,

sg6 12 o .4 /

Enclosure (3) cc (Enclosure):

d gW Director (3)

Office of Management Information and Program Control U.S. Nuclear Regulatory Commission Washington, DC 20555 Director (40)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 Mr. Bill Lavallee Nuclear Safety Analysis Center Palo Alto, California 94303 NRC Inspector, Sequoyah bl 8108030323 810619 DR ADOCK 05000

_ . - . . . _ - - ~ . , _ _ _ _ . _ _ _ . . _ . _ . ._

c- -

SEQUOYAB SUCLEAR PLANT SPECIAL REPORT 81-5 UNIT 1 Event Description Door A62, located in the Auxiliary Building between the Unit 1 valve gallery and the Component Cooling Pump area, has been non-functional for a period in excess of seven (7) days.

Prni,able j Cause The firedoor forms part of the Interim t.uxiliary Building Secondary Containment Enclosure (IABSCE) boundary which remains in effect until completion of Unit 2 construction. During periods of preoperational testing on Unit 2, the dP across the door is extremely high and the direction of the dP is not consistent. During these periods of high dP, the door cannot be closed without causing damage. At present, the door frame ha been damaged beyond repair and prevents the door from ccmpletely closing and latching.

Corrective Actions Fire watch coverage was initiated in accordance with limiting condition for oparation 3./.12.a and will remain in ef fect until the door is repaired. A new door frame has been ordered and the door will be repaired upon delivery.

The periods of high dP cannot be alleviated until preoperational testing of Unit 2 is completed.

.