ML20046A534

From kanterella
Jump to navigation Jump to search
Special Rept 93-09 Provides Detail Re 19 Fire Protection Barriers,Detection Sys & Water Suppression Sys Being Impaired for Period Greater than TS Allowable Timeframe
ML20046A534
Person / Time
Site: Sequoyah  
Issue date: 07/19/1993
From: Fenech R
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9307290002
Download: ML20046A534 (5)


Text

%

s__

j i

i i

Tennessee vaney Authonty, Post Othee Box 2000. Soddy Damy, Tennessee 37379&JO l

i 1

f Robert A. Fenech Vce President Sequoyah Nuclear Plant July 19, 1993 4

U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Gentlemen:

4 In the Matter of

)

Docket Nos. 50-327 Tennessee Valley Authority

)

50-328 SEQUOYAH NUCLEAR PLANT (SQN) - UNIT 1 - FACILITY OPERATING LICENSES DPR-77 AND DPR TECHNICAL SPECIFICATIONS (TS) 3.7.12, i

3.7.11.2, AND 3.3.3.8, SPECIAL REPORT 93-09 The enclosed special report provides details concerning 19 fire protection barriers, detection systems, and water suppression systems being impaired for a period greater than the TS allowable timeframe. The impairments were necessary to support two modifications to the' auxiliary building heating and ventilation system (HVAC).

This report is being submitted in accordance with TS 3.7.12 Action i

Statement (a), and 3.7.11.2 Action Statement (a), and 3.3.3.8 Action Statement (b).

l If you have any questions concerning this submittal, please telephone U. II. Whittemore at (615) 843-7210.

Sincerely,

&hW h&L Robert A. Fenech i

Enclosure cc: See page 2 9307290002 930719-Ik PDR -ADOCK 05000327 S.

~

PDR'

-.O 4

j U.S. Nuclear Regulatory Commission Page 2 July 19, 1993-j cc (Enclosure):

Mr. D. E. LaBarge, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North.

11555 Rockville Pike Rockville, tiaryland 20852-2739

.,a NRC Resident Inspector-f Sequoyah. Nuclear Plant 2600 Igou Ferry Road-Soddy-Daisy, Tennessee 37379-3624

~

Regiona1' Administrator U.S. Nuclear Regulatory Commission Region II 101 Marietta Street, NW, Suite 2900 l

Atlanta, Georgia 30323-2711' l

f

i l

L w

me-rgu.-

m g-ga r--

r

,w

-3g, v

e

j ENCLOSURE

l SEQUOYAH NUCLEAR P1 ANT UNITS 1 AND 2 SPECIAL REPORT 93-09 In support of the activities associated with two modifications to the L

nuxiliary building heating and ventilation system, the following 19 active and passive fire protection impairments were. intentionally initiated and carried out.

Appropriate compensatory measures were established and maintained in each case. The impairments were maintained E

for a period of time that exceeded the allowable technical s'pecification (TS) timeframe.

i The two modifications will provide an A-train ventilation source to the i

A-train vital inverters and battery chargers located in the Unit 1, 480-volt (V) board room (1B) and Unit 2, 480-V board room (2B).

These conditions are being reported in accordance with TS Action Statements 3.7.12.a 3.7.11.2.a, and 3.3.3.8.b.

I.

EIRE _It00RSJ-1fLO.i_.A-194. AND A-1M i

Door A-180 is the adjoining door between the Unit 1, 480-V Board Rooms 1-A and 2-A in the auxiliary building on Elevation 749.0.

This door was breached for ventilation and traffic movement.

Door A-194 is the door accessing the Unit 2, 125-V Vital Battery-Room IV in the auxiliary building on Elevation 749.0.

This door l

was breached for_ ventilation and traffic movement.

]

Door A-195 is the door accessing the Unit 2, 1250-V Vital Battery Room-III in the auxiliary building on Elevation 749.0.

This door-was breached for ventilation and traffic movement.

II.

SERINKLER_SXSIIMS Unit _1 _125-V Vital Bat _t. cry Rooms I. II. III. and IV These rooms are in the auxiliary building on Elevation 749.0.

The sprinkler systems for these rooms were made nonfunctional (isolated) to permit rerouting of the fire protection lines and relocation of the associated sprinkler heads to effectively accommodate the additional heating, ventilating, and i

air-conditioning (HVAC) ductwork being installed in the rooms.

III.

IIRE_ DETECTION Unit _2._125-V Vital. Bat.tery_Eneas III and IV The Unit 2, 125-V Vital Battery Rooms III and IV are in the

{

auxiliary building on Elevation 749.0.

The smoke detectors for these rooms (Fire Zones 253, 254, 255, and 256) were made nonfunctional to prevent false alarms that may be initiated because-l of the welding and other fumes being generated during the

-i modification activities.

i i

- IV.

EIRE _EARRIER_ HALLS A.

A. hole was cut in an auxiliary building reinforced masonry wall serving as a fire barrier. This wall is located in the S column on Elevation 749.0 between Columns A-10 and A-11.

A HVAC duct and fire damper will be installed in the wall.

B.

A hole was cut in an auxiliary building reinforced masonry wall serving as a fire barrier. This wall is located in the R column on Elevation 749.0 between Columns A-10 and A-11.

A HVAC duct and fire damper will be installed in the wall.

.i C.

A hole was cut in an auxiliary building reinforced masonry wall'

{

serving as a fire barrier.

This wall is located in the S column on Elevation 749.0 between Columns A-8 and A-10.

A

.i HVAC duct and fire damper will be installed in the wall.

D.

A hole was cut in an auxiliary building reinforced masonry wall serving as a fire barrier.

This wall is located in the j

A-12 column on Elevation 749.0 between Q and R column lines. A HVAC duct and fire damper will be installed in the wall.

E.

A hole was cut in an auxiliary building reinforced masonry wall serving as a fire barrier. This wall is located in the A-11 column on Elevation 749.0 between Q and R column lines. A j

HVAC duct and fire damper will be installed in the wall.

i F.

A hole was cut in an auxiliary building reinforced masonry wall serving as a fire barrier. This wall is located in the S column on Elevation 749.0 between A-6 and A-8 column lines.

)

A HVAC duct and fire damper will be installed.in.the wall.

G.

A hole was cut in an auxiliary building reinforced masonry wall serving as a fire barrier. This vall is located in the i

S column on Elevation 749.0 between A-3 and A-4 column lines.

A HVAC duct and fire damper will be installed in the wall.

l 1

H.

A hole was cut in an auxiliary building reinforced masonry wall separating the Vital Board Rooms III and IV on Elevation 749.0.

This wall is located in Column A-ll between Columns Q and R.

The hole was necessary to reroute a fire protection line supplying the sprinkler system.

i l

J s

1 l

i 1

I i

i

  • d. IS01AT10lLVALVES_D-26-996 AND_0-26-932 These isolation valves isolate the vital battery rooms' sprinkler system and are normally. closed to prevent the inadvertent spraydown of the vital batteries.

These valves were verified closed and

" hold order tags" are attached to the valves to prevent operation of the valves. The valves were taken out-of-service to isolate the fire-suppression lines to permit the existing lines and -sprinkler heads in the. rooms to be cut out and relocated. Rerouting the lines and relocating the sprinkler heads are necessary because the installation of the HVAC ductwork associated with the modifications interferes with the effectiveness of the existing fire suppression system.

a i

i i

r l

i j

_..