ML20011A726

From kanterella
Jump to navigation Jump to search
RO 50-327/81120:on 811016,while re-evaluating Max post- Accident Water Level Inside Containment,Class IE Electrical Components 1-PT-68-68,1 & 2-TE-68-1/24/60/83 & Four Lower Containment Hydrogen Igniters Were Found Potentially Unsafe
ML20011A726
Person / Time
Site: Sequoyah Tennessee Valley Authority icon.png
Issue date: 10/16/1981
From: Mason C
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
RO-50-327-81120, NUDOCS 8110290356
Download: ML20011A726 (1)


Text

. _ - _

TE!ECOPY TO MRC October 16, 1981 2

n MS U.S. Nuclear Regulatory t h fselon a

Region II O

2-2" 101 Marietta Street, NW

[

>Q Suite 3100 o

Atlanta, Georgia 30303 yy y

ma SQED-50-327/81120 OEi h

ca o'

Reported under Technical Specification 6.9.1.12.h p.:

Date of Occurrence: 10/16/81 Time of Occurrence 1030 (c)

Technical Specification Inv ~ved:

6.9.1.12.h Condi_tions Prior to Occurrence Unit 1 Mode 5 0% Power Unit 2 V. ode 5 0% Power Identification _ _and Description o_f_ Occurr_ence While reevaluating the maximum post accident water level inside containment, the following Class IE electrical components were determined to have a potentially adverse safety impact if they failed because of post accident submergence.

1-PT-68-68, 1&2-TE-68-1/24/60/83, and four (4) lower containment hydrogen ignitors.

W rant Cause of Occurrence The r.aximum post accident water level was inaccurately modeled during initial design.

REGIONAL DIRECTOR DEPUTY D; RECTOR AS9STANT TO.D: RECTOR 0

Other Related E_ vents EC Oh, EC S 9

D! RECTOR, ENF/INV None.

DIRECTOR, ETl PUBLIC AFFAIRS OFFICER Corrective Action taken or Pinnned 1-PT-68-68 is presently being ralocated above the maximum flood level, 162-TE-68-1/24/60/83 have open terminals in the junction boxes which are being spliced and covered with waterpro6f sleeving, and the four (4) hydrogen igniters are being placed on a separate circuit so the remaining igniters will not be effected. These modifications will be completed prior to entry inco Mcde 4.

,s g

2 Power Plant Superintendent

/ (

3 i

?

Sequoyah Nucle.'r Plant

, u [ -/

g, :g j

7 F

3 j

v en O r ;;-

^

8110290356 811016 E5#Lnamert f&wveesw