. . _ _ _ . . _ _ - - __ . _ _ ._

VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION ,

MONTHLY OPERATING REPORT MONTH OCTOBER YEAR 1981 (Revised 12-03-81)

-f

\

f 1

APPROVED:

J l

l J

STATION MANAGER /

'. l l

l T 8211030166 811218 '

DR ADDCK 05000338 PDR

_ . _ . - . - - . . _ . _ . _ . _ . . . _ , . _ . _ .m .

OPERATING DATA REPORT DOCKET NO. 50-339 DATE 12-03-81 COMPLETED BY L.L. Rogers _

TELEPHONE (703) 894-5151 X2510 OPERATING STATUS i Notes

  • Reflects corrected
1. Unit Name: North Anna 2 number of hours i
2. Reporting Period: October 1981 (Revised 12-03-81) generator on line. l
3. Licensed Thermal Power (MWt): 2775
4. Nameplate Rating (Gross MWe): 947
5. Design Electrical Rating (Net MWe): 907
6. Maximum Dependable Capacity (Gross NWe): 939
7. Maximum Dependable Capacity (Net HWe): 890
8. If Changes Occur in Capacity Ratings (Items No. 3 thru 7) Since Last Report, Give Reasons l Corrects re-evaluation of auxiliary load consumption dated May 1981.

l

9. Power Level To Which Restricted, If Any (Net NWe): N/A 1
10. Reasons For Restrictions, If Any: N/A l l

6el h it4 0 M r 9/ ~ 3 9 0

This Month Yr.-to-Date Cumulative ,

11. Hours In Reporting Period 745 7,296 7,728 i
12. Number of Hours Reactor Was Critical 733.2 5,524.3 5,953.2 l
13. Reactor Reserve Shutdown Hours 7/3, .4 17m1 1.358.5_ 1,638.5
14. Hours Generator On-Line Ok (*?!; 23 d5,362.M ,*5,775 >  !
15. Unit Reserve Shutdown Hours 88 4 0 0 . 0
16. Gross Thermal Energy Generated (MWH) 1,898,994 13,802,996 14,889,993
17. Gross Electrical Energy Generated (MWH) 643,948 4,653,876 5,022,307
18. Net Electrical Energy Generated (MWH) 611,338 4,402,998 4,752,642
19. Unit Service Factor *95.7 *73.5 *74.7
20. Unit Availability Factor *95.7 *73.5 *74.7  ;
21. Unit Capacity Factor (Using MDC Net) 92.2 67.8 69.1  !
22. Unit Capacity Factor (Using DER Net) 90.5 66.5 67.8 '
23. Unit Forced Outage Rate *4.3 *23.3 *22.2
24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

1 Refueling Outane 05-82 thru 05-14-82 l

25. If Shut Down At End Of Report Period, Estimated Date of Startup: N/A
26. Units In Test Status (Prior to Commercial Operation):

Forecast

\. Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

  • corrects duratica of shutdown 81-38' j

Page 1 of 2 I

i UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-339 UNIT NAME North Anna 2 DATE 12-03-81 REPORT MONTH OCTOBER (Revised) COMPLETED BY L. L. ROGERS TELEPHONE (703) 894-5151 X2510 2 Component Cause & Corrective No. Date Typel Duration Reason Method of Licensee System (Hours) Shutting Event Code Code Action to 3 4 5 Down Reactor Report # Prevent Recurrence 81-37 811001 F N/A F 5 N/A N/A N/A Reduced load to 90% due to "B" Transformer hi alarm and No. 4

, governor valve cycling.

81-38 811003 F *26.8 *A 3 N/A N/A N/ Reactor trip due to ENC line rupture on No.4 governor.

ld M

^

,( Closed No. 4 governor valve and Mk -

installed new supports l.

81-39 811004 F 5.0 . A 3 N/A N/A N/A Reactor Trip due to generator leads differential.

Reduced load to 91% due to "B" 81-40 811005 F N/A F 5 N/A N/A N/A Transformer hi temperature i alarm.

! 81-41 811006 F N/A F 5 N/A N/A N/A ' Reduced load to 90% due to "B" Transformer hi temperature alarm.

/

1 1 2 3 4 F: Forced Reason: Method: Exhibit F - Instructions 8: Scheduled A-Equipment Failure (Explain) 1-Manual for Preparation of Data i B-Maintenance or Test 2-Maiinh1 Scram. Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (LER) File l

D-Regulatory Restriction 4-Continuations (NUREG-0161)

E-Operator Training & License Examination 5-Load Reduction F-Administrative 9-Other

' G-Operational Error (Explain)

H-Other (Explain) Exhibit H - Same Source

_ _ - - _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _