PNO-III-86-104, on 860923,unit Shutdown at 4:08 Am,To Investigate Cause of High Bearing Temp on One of Recirculation Pumps.Vendor Insp Determined That Some Cells, Which Supply Control Power to Hpic Sys Valves Be Degraded

From kanterella
(Redirected from ML20212E682)
Jump to navigation Jump to search
PNO-III-86-104:on 860923,unit Shutdown at 4:08 Am,To Investigate Cause of High Bearing Temp on One of Recirculation Pumps.Vendor Insp Determined That Some Cells, Which Supply Control Power to Hpic Sys Valves Be Degraded
ML20212E682
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 09/23/1986
From: Boyd D, Guldemond W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
References
PNO-III-86-104, NUDOCS 9711040021
Download: ML20212E682 (1)


e p;

- PRELIMINARY NOTIFICATION OF EVENT-OR UNUSUAL OCCURRENCEePNO-!!!-86404 Date'Septemb6 23,1

  • This preliminary notification constitutes EARLY notice of events of-POSSIBLE safety The information is as initially received without verification _or evaluation, and is basically all that-is- known by. the Region !!!-

y [ Nystaffonthisdate.-

a or public' interest _significancei _

Facility:; Iowa Electric Light:& Power Co.H Licensee Emergency Classification:-

Duane Arnold Energy Center. Notification of.an Unusual Event

=Palo,-I C 52324 Alert Site Area Emergency Docket No. 50-331- General Emergency T Not Applicable

Subject:

-SHUTDOWNFORRECIRCl4ATIONPUMPBEARINGPROBLEM- ,

Theunitwasshutdownat4:08a.m._(CDT), September 23, 1986, to investigate the cause of high bearing temperatures on one of the recirculation pumps. During the shutdown, other maintenance will be performed including replacement of a recirculation valve in the High

. Pressure Coolant Injection-(HPCI) System and the evaluation and possible replacement of -

12 cells in the 250-volt battery bank. A vendor inspection determined some cells, which supply control power to HPIC System valves, to be degraded and the-HPCI system was

' declared-inoperable. Other Emergency Core Cooling Systems were operable, and the HPCI-

problem therefore did not require shutdown. -

The outage is expected to last longer than 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.

The State of Iowa will-be notified.

Region !!!-(Chicago) was informed that the' unit was shutting down at 4 p.m. (CDT),

September 22, 1986, and additional information was provided by the Resident' Inspector._ This .

'> information is current as of 11 a.m.,_ September 23, 1986.

k CONTACT: D. C. Boyd W. G. Guldemond-FTS 388-5546 FTS 388-5574 C/R Distribution: Chm, Cmrs,

.. S,GC,CA,ACRS. Historian, yy v ')

SECY, Records.

C

'OISTRIBUTION: SP: O W P2 d3S N' H. St. ,

EDO _NRR E/W " Willste Mail: ADM:DMB Chairman Zech PAL IE . NMSS u DOT:Trans only Conn. Roberts ELD OIA RES 30 Comm. Asselstine AE00 Conni. Bernthal

- Conn. Carr 5P~ Regional-Offices

-ACRSc ~

-SECY. INP01 MSAC R. _ ne: (Corp. Office.-R9actorLic.Only) -

,9 '

\' Region III

, .Rev. November 1985

~

(M d_2 D -

9711040021 6 NO-I 96-104 PDR _ , _

i_

=

. _ _ - _ _ - _ _ _ _ _ _ m