 Issue dateTitleTopic
PNO-III-99-024, on 990416,licensee Commenced Controlled Power Reduction to Approx 10% to Identify & Repair Main Generator Field Ground.Troubleshooting Efforts Are Still in Progress. Ris Monitored SD & Troubleshooting & Will Review Activities19 April 1999PNO-III-99-024:on 990416,licensee Commenced Controlled Power Reduction to Approx 10% to Identify & Repair Main Generator Field Ground.Troubleshooting Efforts Are Still in Progress. Ris Monitored SD & Troubleshooting & Will Review Activities
PNO-III-98-045, on 980914,empty Type B Shipping Cask Received with Removable Contamination Levels of Approx 40,000 Dpm Per 100 Square Centimeters.Licensee Decontaminated Cask16 September 1998PNO-III-98-045:on 980914,empty Type B Shipping Cask Received with Removable Contamination Levels of Approx 40,000 Dpm Per 100 Square Centimeters.Licensee Decontaminated Cask
PNO-III-97-077, on 970909,licensee Began Reactor Shutdown After Steam Leak Identified in Steam Tunnel.Leak Was on Capped Drain Line Off a Main Steam Line,Between Two Main Steam Isolation Valves.State of IA Will Be Notified10 September 1997PNO-III-97-077:on 970909,licensee Began Reactor Shutdown After Steam Leak Identified in Steam Tunnel.Leak Was on Capped Drain Line Off a Main Steam Line,Between Two Main Steam Isolation Valves.State of IA Will Be Notified
PNO-III-90-046, on 900709,partial Loss of Offsite Power Occurred During Refueling Outage.Determined That Technician Failed to Insert Relay Logic Block.Licensee Reviewing Controls on Switchyard Activities.State of IA Notified11 July 1990PNO-III-90-046:on 900709,partial Loss of Offsite Power Occurred During Refueling Outage.Determined That Technician Failed to Insert Relay Logic Block.Licensee Reviewing Controls on Switchyard Activities.State of IA Notified
PNO-III-89-066, on 890919,during Routine Maintenance,Licensee Identified Two Environmentally Unqualified AMP Butt Splices on Recirculation Sys Sample Line Valve in Drywell.Licensee Instituted two-phase Program to Correct Addl Splices3 October 1989PNO-III-89-066:on 890919,during Routine Maintenance,Licensee Identified Two Environmentally Unqualified AMP Butt Splices on Recirculation Sys Sample Line Valve in Drywell.Licensee Instituted two-phase Program to Correct Addl Splices
PNO-III-89-018, on 890305,reactor Scrammed While Licensee Was Adjusting Main Steam Line Radiation Monitors to Perform Hydrogen Injection Testing6 March 1989PNO-III-89-018:on 890305,reactor Scrammed While Licensee Was Adjusting Main Steam Line Radiation Monitors to Perform Hydrogen Injection Testing
PNO-III-86-152, on 861212,radwaste Shipment,Consisting of Spent in-core Nuclear Detectors & Control Rod Blades, Totalling 20,000 Ci,Misrouted Into State of Mn.Dot Notified19 December 1986PNO-III-86-152:on 861212,radwaste Shipment,Consisting of Spent in-core Nuclear Detectors & Control Rod Blades, Totalling 20,000 Ci,Misrouted Into State of Mn.Dot Notified
PNO-III-86-143, on 861209,plant Shut Down Due to Discovery That 200 AMP Electrical Splices Supplied by GE May Not Meet Environ Qualification Requirements.Special Region III Insp Will Review Splice Problem & Licensee Corrective Action9 December 1986PNO-III-86-143:on 861209,plant Shut Down Due to Discovery That 200 AMP Electrical Splices Supplied by GE May Not Meet Environ Qualification Requirements.Special Region III Insp Will Review Splice Problem & Licensee Corrective Action
PNO-III-86-116, on 861015,while Operating at 95 Percent Power,Licensee Declared Unusual Event After Both Trains of Control Room Ventilation Sys Rendered Inoperable.Caused by Test Procedures Failed to Require Control Valve Be Reset17 October 1986PNO-III-86-116:on 861015,while Operating at 95 Percent Power,Licensee Declared Unusual Event After Both Trains of Control Room Ventilation Sys Rendered Inoperable.Caused by Test Procedures Failed to Require Control Valve Be Reset
PNO-III-86-104, on 860923,unit Shutdown at 4:08 Am,To Investigate Cause of High Bearing Temp on One of Recirculation Pumps.Vendor Insp Determined That Some Cells, Which Supply Control Power to Hpic Sys Valves Be Degraded23 September 1986PNO-III-86-104:on 860923,unit Shutdown at 4:08 Am,To Investigate Cause of High Bearing Temp on One of Recirculation Pumps.Vendor Insp Determined That Some Cells, Which Supply Control Power to Hpic Sys Valves Be Degraded
PNO-III-85-074, on 850822,both Diesel Generators Technically Inoperable.Caused by Simultaneous Rather than Sequential Transfer of Power for Four RHR & Two Core Spray Pumps from Standby Transformers.Switches Placed in Test Position23 August 1985PNO-III-85-074:on 850822,both Diesel Generators Technically Inoperable.Caused by Simultaneous Rather than Sequential Transfer of Power for Four RHR & Two Core Spray Pumps from Standby Transformers.Switches Placed in Test Position
PNO-III-85-022B, on 850719,scheduled Maint & Refueling Outage Concluded.Inservice Insp Revealed through-wall Cracks & Crack Indications on Welds in Recirculating Sys Piping. Repairs Made by Weld Overlay Method19 July 1985PNO-III-85-022B:on 850719,scheduled Maint & Refueling Outage Concluded.Inservice Insp Revealed through-wall Cracks & Crack Indications on Welds in Recirculating Sys Piping. Repairs Made by Weld Overlay MethodWeld Overlay
Hydrostatic
PNO-III-84-092, on 841104,explosion & Fire Occurred in Auxiliary Transformer.Caused by Internal Short Circuit. Essential Loads Picked Up by Standby Transformer.Hpci,Rcic & Transformer Deluge Sys Started5 November 1984PNO-III-84-092:on 841104,explosion & Fire Occurred in Auxiliary Transformer.Caused by Internal Short Circuit. Essential Loads Picked Up by Standby Transformer.Hpci,Rcic & Transformer Deluge Sys Started
PNO-III-83-032, on 830426,scram Circuitry Failed to Operate Properly When Mode Switch Moved from Refuel Position to Shutdown Position.Caused by Three Loose Wires in Rectifier Bridge27 April 1983PNO-III-83-032:on 830426,scram Circuitry Failed to Operate Properly When Mode Switch Moved from Refuel Position to Shutdown Position.Caused by Three Loose Wires in Rectifier Bridge
ML20249A02813 December 1978PNS-78-060:on 781212,security Guard at Duane Arnold Energy Ctr Received Telcon from Male Caller Who Said, Listen & Listen Good.Plant Will Blow Up Tonight. No Search Instituted,But Security Personnel Deployed
PNO-III-78-193, on 781109,received Allegation Re Qualification of Welders Performing Safe End Repair Work at Plant.State of IA Informed15 November 1978PNO-III-78-193:on 781109,received Allegation Re Qualification of Welders Performing Safe End Repair Work at Plant.State of IA Informed
ML20248F22030 June 1978PNO-78-129:on 780630,licensee Notified Region III That on 780603,contract Worker Collapsed While Working in Refueling Floor Area.Victim Taken to Hospital.Hospital Detected Minor Contamination on Individuals Cheek & Back
ML20248F17129 June 1978PNO-78-125A:on 780627,licensee Reported That Nondestructive Testing of Remiaining Seven Recirculation Sys Inlet Nozzle Transition Pieces Revealed That Five of Seven Have Crack Indications That Will Require RepairNondestructive Examination
ML20248F16119 June 1978PNO-78-125:on 780617,licensee Notified Region III That 3 Long Crack Found in ten-inch Recirculation Sys Line.Crack Appears to Be in Inconel Transition Piece Between Pipe & Vessel Nozzle.State of Iowa Being Notified
ML20248J78827 March 1978PNO-78-062:on 780325,during Insp of Drywell,Pipe Crack Was Detected in Primary Coolant Sys four-inch Cleanup Line. Reactor Currently Shutdown for Refueling.Licensee Evaluating Methods for Repair.State of IA Notified
ML20151U43610 May 1977PNO-77-076:during Routine Tour of Plant,Radiation Technician Noticed Smoke Coming from 480V Motor Control Ctr.Small Fire Was Noted in Supply Breaker.Fire Was Extinguished.Plant Presently Shutdown for Refueling
ML20151U68431 March 1977PNO-77-050:on 770329,notified Region III of Failure of Four Six Automatic Relief Valves During Testing.Licensee Stated Manual Relief Fuction of Six Valves Satifactorily Tested at Site.Region III Following Matter Closely
ML20249B8694 November 1976PNO-76-181:during Conduct of Routine Monthly Diesel Generator Surveillance Test on 761104,fuel Oil Leak Developed Due to Cracked Fitting in Fuel Line.Fuel Oil Sprayed on Exhaust Manifold & Fire Ignited.Inspector Onsite
ML20236F41724 June 1976PNS-76-028:on 760623,secretary in General Ofc of Iowa Electric Light & Power Co Received Telephonic Bomb Threat.Search of Facility Was Conducted.No Bomb Was Found
ML20236U8934 September 1975PN-75-086:licensee Reported That Strike of Operating & Maint Bargaining Unit Personnel Would Take Place on 750904.Plant Will Be Operated by Site & Corporate Supervisory Personnel IAW Contingency Plan
ML20236U17411 June 1975PN-75-035:on 750610,Region III Ofc Was Notified by Licensee That Fuel Bundle Had Dropped Into Reactor Vessel During Fuel Movement Operation.Plans in Progress to Determine How to Secure Bundle,Positioned Upright & Leaning Against Wall