[ p nREc,

o

'o, UNITED STATES

$'

. # J- %

NUCLEAR F _GULATORY COMMISSION

'

'"d/ L [E

$.'-

REGION 11

'

hi 101 MARIETT A sT., N W., sulTE 3100 o,

p.

% ' N,- f ATLANTA, GEORGIA 30303

  • ....

Report No. 50-395/79-15 Licensee:

South Carolina Electric & Gas Company P. O. Box 764 Columbia, South Carolina 29218 Facility Name: Summer Docket No.

50-395 License No.

CPPR-94 Inspection at V. C. Summer site near Columbia, South Carolina Inspector:

[4

  1. Sc'/7'/

D.

K'.

Wa l't e r st Ddte Signed

[ff

/

Approved by:

.

ryan Section Chief, RCES Branch Dite Sign'ed SUMMARY Inspection on May 8-11, 1979 Areas Inspected This routine, unannounced inspection involved twenty-five inspector-hours onsite in the areas of safety-related 7200 volt switchgear and 480 volt load center installations; safety-related wireway and wireway support installations; follow-up inspection of unrecolved item 395/79-09-02, inspec+or follow-up items 395/78-30-02 and 395/79-09-01, and licensee identified item 395/79-02-01.

Results e

Of t'e areas inspected, no apparent items of noncompliance or deviations were

.

identified.

'71) 0 7 2,6 0 W (

<

r *0

,

DETAILS 1.

Persons Contacted

..

Licensee Employees

  • J. F Algar, Site Manager
  • D. Moore, Director, Surveillance Systems
  • E. Evans, QA Svoarvisor
  • M. W. Eddins, Assistant Site Manager M. Garrett, Elec^ rical QC Supervisor D. A. Lavigne, QA Surveillance Specialist Other organization Daniel Construction Company
  • C. C. Wagoner, Project Manager, DCC
  • W. L. West, Projo.t QA Manager, DCC
  • G. Curtis, QC Supervisor, DCC
  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on May 11, 1979 with those persons indicated in Paragraph I above.

3.

Licensee Action on Previous Insr-ction Findings Unresolved item 395/79-02: Protection of cable raceways. The licensee has performed the following actions.

Revision 2 has been issued to procedure WP-XII-01, " Cable Pulling".

a.

b.

Signs have been posted to alert personnel to keep off trays.

Craft personnel have been briefed on cable tray requirements at c.

safety meetings.

Revision 2 to Procedure WP-XII-01 was not considered adequate because this revision authorizes one person to be in a tray section under difficult conditions, but does not address the potential damage to installed cables which could result. This item will remain unresolved pending licensee completion of action and future inspection.

4.

Unresolved Items

.

_.

Unresolved items were not ideatified during this inspection.

G62 M

459 013

.

-2-5.

Licensee Identified Items (50.55;c))

(0 pen) Item 395/79-02-01:

Insufficient cable slack to class 1E electrical equipment. The licensee has issued nonconformance notice 640E for this item and completed a QC inspection on all applicable cable that had been terminated before January 8, 1979. Of the cables identified as having

,,

insuf ficient slack during ti.e inspection, there are 14 remaining which require final inspection and replacement, if necessary.

This item will remain open pending licansee completion of wc rk and future inspection.

6.

Inspector Follow-up Items (0 pen) Item 395/79-09-01:

Separation conflict documentation. Revision 4 to procedure FQCP 7.1.6, " Installation of exposed conduit and conduit supports" has been issued for review and comment.

This item will remain open pending licensee concpletion of resolution and action.

(Closed) Item 395/78-30-02:

In-place storage and house keeping. The licensee has closed Construction Action Request (CAR) 041 based on corrective actions, taken by the contractor and results of recent licensee surveillances.

Corrective actions included the following.

Procedure DCC CAP VIII-03, " Cleaning, Handling and Preservation",

a.

has been revised and implemented.

b.

A surveillance group has be<.a established to inspect plant areas twice daily and to ensure that required periodic preventive maintenance is performed and documented on the Plant Equipment Maintenance Log (PEML).

The surveillance group also ensures that equipment is adequately protected and preserved.

The in place storage of safety-related 7200 volt switchgear identified as XSW-IDB-ES, 480 volt load center identified as XSW-1DB2-ES, and three motor operated valves were observed to meet procedural requirements.

This item is closed.

7.

Independent Inspection Effort The installation of safety-related 7200 volt switchgear XSW-IDB-ES and 480 volt load center XSW-IDB2-ES circuit breakers were inspected to ensure that installations were in accordance with the following drawings.

DRAWING NO.

TITLE IMS-33-006-01-01 Arrangement of Electric Equipment, Electrical Eqpt - Intermediate and Diesel Generator Buildings above El.

436'-0"

'

IMS-33-006-01-01 Metal Clad Switchgear

%

M

=

.

459 014

- -

- - - - - - - - - - - -. - - _ _ - _ - - _ _ _ _ _ _ _ _ _ _. _ _ _ _ _ _ _.._..

. _..

.

..

-3-

.

IMS-33-006-02-02 Metal Clad Switchgear IMS-33-006-03-01 Metal Clad Switchgear IMS-33-006-04-02 Metal Clad Switchgear

..

E206022, R7 One Line and Relay Diagtam-7200 Volt Switchgear Busses IDA, IDB, IEA & IEB E20634, R7 One Line and Relay Diagram-480/277 Volt Switchgear Busses IDA1, IDA2, IDB1, IDB2, IEA1 and IEB1 IMS-34-007-06-08 Indooi S2c Substation Single Ended 1000/? ^ KVA 7200 volt - 480 y/ 277 volt, 5 phase, 4-wire, 60hz.

Within the areas examined, no items of noncompliance or deviations were identified.

8.

Electrical (Cables and Terminations II) - Observation of Work and Work Activities and Review of Quality Records The safety-related cable tray sections and associated cable tray supports identified below were selected for inspection.

Section No.

Associated Supports 4330 220-1(2), 220-2, 220-3,42-200, 10-216 4152 37-301,37-300, 9-300, 9-307 1033 11-336,11-337, 11-338 The installation of the tray sections and supports were inspected to ensure compliance with the requirements of procedure FQCP-7.1.7,

" Installation of Cabic Trays, Supports, Electrical Noise and Fire Barriers" and the drawings identified below.

DRAWING NO.

IITLE E214-541, R7 Electrical, Cable Tray, Conduit and Cable Supports, Control Building - West - Above Ei.

412'-0".

E214-631, R7 Electrical, Cable Tray, Conduit and Cable Supports, Intermediate Building-West Above El.

412'-0"

- 360 M 459 015

- - - - _ _ - _ - _ - _ _ _

. _

.

-4-

E21,'-635, R5 Electrical, Cable Tray, Conduit and Cable Supports, Intermediate Building-West Above El.

436'-0" E214-702, R9 Elecorical, Cable Tray Supports, Sections and Details

--

E214-707, R3 Electrical, Caile Tray Supports, Sections and Details E214-708, R6 Electrical, Cable Tray Supports, Sections and Details E214-756, R5 Electrical, Cable Tray Supports, Material List-Control Building E214-757, R5 Electricsl, Cable Tray Supports, Material List-Control Building E214-758, R4 Electrical, Cable Tray Supports, Material List-Control Building E512-117, R5 Auxiliary Building - Miscellaneous Steel, Suppe t. r annection Details E512-118, R6 Aurliar y Building - Miscellaneous Stee. Support Connection Details E512-119, R3 Auxiliary Building - Miscellaneous Steel, Support Connection Details E512-120, R5 Auxiliary Building - Miscellaenous Steel, Support Connection Details 55-214-711 Electrical Cable Tray Supports (Support Number)

Installation inspections had been performed and documented per the require-ments of procedure FQCP-7.1.7 and FQCP-6.1.5, " Visual Inspection of Miscellaneous / Structural Steel Welding".

Within the areas examined, there were no items of noncompliance or deviations identified.

.- 7 / O 7C7-ai

~vr 459 0!6