Forwards Draft Responses to Commission 821005 Request for Addl Info on Chapter 7 of Gessar II Sar.Responses Reflect Nrc/Ge Info Exchange 821014-15 Meetings in Bethesda,Md
ML20066H534
Person / Time
Site: 05000447
Issue date: 11/19/1982
From: Sherwood G
GENERAL ELECTRIC CO.
To: Eisenhut D
Office of Nuclear Reactor Regulation
References
NUDOCS 8211230297
Download: ML20066H534 (127)


Text

V GENER AL @ ELECTRIC NUCLEAR POWER SYSTEMS DIVISION GENERAL ELECTRIC COMPANY,175 CURTNER AVE., SAN JOSE, CALIFORNIA 95125 MFN 178-82 MC 682, (408) 925-5040 November 19, 1982 U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Washington, D. C. 20555 Attention: Mr. D. G. Eisenhut, Director Division of Licensing

SUBJECT:

IN THE MATTER 0F 238 NUCLEAR ISLAND GENERAL ELECTRIC STANDARD SAFETY ANALYSIS REPORT (GESSAR II) DOCKET N0. STN 50-447 Attached please find draft responses to the Commission's October 5, 1982 request for additional infonnation on Chapter 7 of GESSAR II. These responses reflect the NRC/GE infonnation exchange meetings held in Bethesda October 14 & 15, 1982.

Most questions are addressed in this transmittal. Draft responses will be provided for all remaining questions in early January 1983. An amendment is scheduled for mid-January 1983 to formalize the responses.

Sincerely, enn . oo , anager Nuclear Safety & Licensing Operation fo$

Attachments. ., h*

cc: M. J. Virgilio, NRC Ur~

M. D. Lynch, NRC (Without Attachments)

L. S. Gifford, GE-Bethesda (Without Attachments)

F. J. Miraglia (Without Attachments)

C. O. Thomas (Without Attachments) 8211230297 821119 PDR ADOCK 05000447 A PDR

421.01 OVESTION You indicate in Section 7.1.2.2, 7.1.2.3 and 7.1.2.4 of your FSAR that your statements regarding the applicability of the conformance of each of your proposed systems with the General Design Criteria (GDC), regulatory guides and the appropriate industry standards are included in Table 7.1-3 through 7.1-6.

However, Tables 7.1-3 through 7.1-6 are inconsistent with Table 7-1 of Section 7.1 of the Standard Review Plan (SRP).

Identify and deviations between Tables 7.1-3 through 7.1-6 of your FSAR an Table 7-1 of the SRP.

421.01 RESPONSE The existing tables (7.1-3 through 7.1-6) were arranged consistent with the previous SRP = NUREG 75/087, Table 7-1.

However, these tables are in process of being revised with headings consistent with NUREG 0800, Table 7-1. Since tht.re is actually less information required (ie, applicability of regulatory criteria is more specifically refined to appropriate systems), no deviations are anticipated. BTP applicability will not be indicated directly in the GESSAR II Tables. However a note will be provided to reference the response to question 421.02. Assessments for all BTP's in Table 7-1 will be provided in that response.

(

\

421.02 QUESTION

( In Section 7.1 of your FSAR, you do not address the Branch Technical Positions (BTP) relating to the instrumentation and control systems listed in Table 7-1 of the SRP and provided in Appendix A to Chapter 7 of the SRP. Provide a detailed discussion using drawings, schematics and P&ID's to demonstrate that your proposed design conforms to the guidance provided in the applicable BTP's, including Branch Technical Position ICSB 18 (PSB) contained in Appendix 8-A of the SRP.

s.

421.02 RESPONSE The following Table provides GE's assessments for all BTP's shown in Table 7-1 of the SRP and BTP ICSB 18 (PSB):

(Next~5 Pages)

(

l l

(

i 1 _ . . . . _ _ _- - . - - - . -- . - . - - - --- - - - - - - -

W .A P SRP ASS. sSMENT SRP NO. REv RESPONSE TO QUESTION 421.02 PAGE I OF 5 TITLE

! SRP ACCEPTANCE DEVIATION JUSTIFICATION i

(a) BTP ICSB 3: Isolation of low pressure See justification "B.2 and BTP ICSB 3: See Section 7.6.1.5; also systems from the High Pressure Reactor B.3" Otherwise, no Figures 6.3-6 (HPCS P&ID), 6.3-7 (LPCS FAID)

Coolant System. deviation.

B.1
Two valves are provided.

B.2 & B.3: Pressure interlocks are pro-vided in accordance with this requirement.

However, E!2-F042 (LPCI) and E21-F005 (LPCS) do not automatically close on high pressure (see 7.6.1.5.D).

B.4: Control Room valve position indica-tors are provided. -

B.5: HPCS utilizes 2 valves between the vessel and the HPCS, though return lines from HPCS to. suppression pool have one valve in each line.

(b) BTP ICSB 4: Requirements of MOVs in Not applicable to BWR plants. BTP ICSB 4: BWRs do not employ safety the ECCS accumulator lines (PWR injection tanks with MOIVs.

plants).

(c) BTP ICSB 12: Protection System, trip Not applicable to BWR plants. BTP ICSB 12: BWRs do not employ reactor point changes for operation with coolant pumps and safety setpoints are reactor coolant pumps out of service. fixed.

(d) BTP ICSB 13: Design criteria for Not applicable to BWR BTP ICSB 13: BWRs do not employ steam gen-auxiliary feedwater systems. plants . erators nor auxiliary feedwater systems.

(e) BTP ICSB 14: Spurious withdrawals of hot applicable to BWR BTP ICSB 14: SRP identified single-failure single control rods in PWRs. pl an ts . rod withdrawal problem unique to PWRs only.

  • Unless otherwise indicated, all references are in GESSAR II.

,r m O SRP ASS ,SMENT SRP NO. REv PAGE 2 op 5 RESPONSE TO QUESTION 421.02 (continued)

! TITLE J

SRP ACCEPTANCE CRITERI A DEVIATION JUSTIFICATION i

( f) BTP ICSB 16: Control Element Not applicable to GE BWRs. BTP ICSB 16: SRP identifies requirement Assembly (CEA) interlocks in Combus- unique to Combustion Engineering vendor. i tion Engineering reactors.

(fg) BTP ICSB 18 (PSB): Application of No Deviation. BTP ICSB 18: Valve operations have been the single-failure criterion to ,

evaluated in the design. If inadvertent manually-controlled electrically- operation has adverse safety consequences, operated valves. two valves are placed in series on the pipe ,

with logic separation such that no single electrical short can open both valves (e.g. ,

see valves F007 and F008 on Figure 6.7-la).

The power disconnect option is therefore unnecessary and is not used.

(g) BTP ICSB 20: Design of instrumenta- No Deviation BTP ICSB 20: It is not within the BWR tion and controls provided to operating design base, to transfer from accomplish changeover from injection injection to recirculation mode. The BTP to recirculation mode. is primarily a PWR concern. However, HPCS suction automatically transfers from its preferred source (condensate storage tank) to the suppression pool on receipt of low condensate water level _or_ high suppression pool water level signals. See 7.3.1.1.1.1.

C.1 and 6.3.2.2.1. Likewise, RCIC has similar transfer (automatically), as described in 7.4.1.1.D.6 and 5.4.6.1.

(h) BTP ICSB 21: Guideline for applica- No Deviation BTP ICSB 21: See analysis sections for tion of Regulatory Guide 1.47. each system for application of Regula- /

tory Guide 1-47. For example, 7.3.2.1.2. A.7 for ECCS.

B.1 & B.2 Individual system components meeting guide-lines B.1, 2 & 3 of Regulatory Guide 1.47 are annunciated at a single " system out of OUnless otherwise indicated, all references are in GESSAR II.

SRP ASS. ,SMENT SRP NO. REV PAGE 3 op 5 TITLE RESPONSE TO QUESTION 421.02 (continued)

^ ^

CR TERIA DEVIATION JUSTIFICATION (h) BTP ICSB 21: (Continued) No Deviation BTP ICSB 21: (Continued) service" window for each division. In addition, status lights identify which com-ponent causes the out-of-service condition.

Manual switches are provided to compliment administrative procedures which cover func-tions not automatically annunciated. Both annunciators and status lights are located in the Control Room immediately accessible to the operator.

B.3 The operator cannot cancel erroneous indi- .

cations. He can silence the horn, but cannot clear the window or status lights until the problem is cleared.

B.4 The annunciators and status lights are not safety related. However, no safety action is required by the operator based solely on annunciator indication.

B.5 Interfaces between annunciators and safety-related logic are optically isolated such that no annunciator failures could cause failures of essential safety functions.

Status lights are retained in the divisiona circuits and are qualified with the panels housing them. Compliance with Regulatory Guide 1.75 assures redundant safety system independence is not compromised.

'Unless otherwise indicated, all references are in GESSAR II.

s ,

~

SRP ASSusSMENT SR O. Ev PAGE OF TITLE RESPONSE TO QUESTION 421.02 (continued)

SRP ACCEPTANCE CRITERIA DEWATIM NSM N M (h) BTP ICSB 21: (Continued) No Deviation BTP ICSB 21:

(Continued)

B.6

'ATT indicating and annunciating functions can be tested during normal plant operation.

(This should be confirmed by applicant.)

(1) BTP ICSB 22: Guidance for application No Deviation of Regulatory Guide 1.22. BTP ICSB 22: RPS conformance to Regulartor)

Guide 1.22 1s addressed in Subsection 7.2.2.2.A.1. RPS conformance to IEEE-279 is addressed in Subsection 7.2.2.2.C.1.

Corresponding conformance sections for ECCS are 7.3.2.1.2. A.3 and 7.3.2.1.2.C.1 respectively.

(j) BTP ICSB 26: Requirements for Some RPS inputs come from Reactor Protection System anticipatory devices mounted on non- See Subsection 7.2.3; the analysis on the trips. use of RPS inputs from devices mounted on seismically qualified equip- nonseismically qualified equipment and/or ment and/or located in non- located in nonseismically qualified seismically qualified enclosures has been accepted per three enclosures, safety evaluation reports:

  • (1) NUREG-0124 (supplement to NUREG 75/110) " Safety Evaluation ~ Report, 1

GESSAR 238 Nuclear Island Standard Design Supplement 1", September 1976, pp. 7-78, 15-3,4.

(2) NUREG-0151, "SER, GESSAR 251, Nuclear Steam Supply System Standard Design",'

March 1977.

(3) NUREG-0124 Supplement 2, January 1977.

pp. 15-1,2. -

ess otherwise indicated, all references are in GESSAR II.

,h g- -

e%

SRP ASS. sSMENT SRP NO. REv ~

5 5 PAGE OF TITLE RESPONSE TO QUESTION 421.02 (continued)

^ ^"

CRITERI A DEVIATION JUSTIFICATION (j) BTP ICSB 26: (Continued) The above reports include data for ger,eric 238 and 251 BWR/6 designs. This analysis considers turbine trip, generator load rejection trip and recirculation pump trip (RPT).

Generally, GE requires all hardware con-tributing to scram be qualifled per IEEE-279 (7.2.2.2.C.1). Where exceptions are taken by customer /AE (i.e., TVA's turbine control valve fast closure and turbine stop valve closure and turbine stop valve closure sensors), isolation is provided to protect the integrity of the RPS.

  • Unless otherwise indicated, all references are in GESSAR II.

421.03 QUESTION In Section 7.1.2.10.18 of your FSAR, you provide information regarding the conformance of your proposed design with the '

guidance provided in Regulatory Guide 1.75. Discuss the details of your separation criteria fo. protection channel circuits, protection logic circuits and nonsafety-related circuits using one-line drawings, schematics or other drawings as appropriate, in light of the guidance provided in this regulatory guide.

421.03 RESPONSE Details of the separation methods and techniques are provided in GESSAR II, Chapter 8, as required by Regulatory Guide 1.70, revision 3 (See Subsections 8.3.1.1.5.1, 8.3.1.3 and 8.3.1.4).

Also, in conjunction with PGCC separation, see the tiRC approved topical report = NED0-10466-A, as referenced in GESSAR II, subsections 7.1.2.10.18.E,7.7.1.9.A,7.7.2.9.B,8.3.1.4.1.2(6),

and 8.3.1.4.2.3.2(8).

(

4 1

t 421.06 QUESTION We have recently issued Revision 2 to Regulatory Guide 1.97 reflecting a numbe of major changes in our position on post-accident instrumentation. Discuss your conformance with this revised regulatory guide.

421.06 RESPONSE A GE Assessment of Regulatory Guide 1.97 is provided in Appendix 1D as indicated in Subsection 1.1 of GESSAR II.

i L

421.07 QUESTION In footnote 2 to Appendix A of 10 CFR Part 50, we require the assumpution that: " single failures of passive components in electric systems should be assumed in designing against a single failure." Accordingly, discuss how you consider passive failures in all safety-related instrumentation and control systems in your proposed facility. Provide assurance that passive failures were included in a failure mode and effects analysis (FMEA) performed in response to the concerns identified in Question 421.08.

421.07 RESPONSE Single failures of passive components in electric systems are assumed in the design of safety systems. Passive components ,,,,,

used in safety systems are not requried to undergo mechanical 74L pe/WasWe motion or a change of state, however they are required to f w ided / fee' naintain the structural integrity. These components are '

des /s,of t=e qualified for safety application. Independent and redundant 54fets syste=o, component, loop or subsystem has been provided for active as well as passive components used for *all safety-related instru-mentation and control systems,lis based on the consideration of the single failures, For detail discussions see Section 7.1.2.11.8 of GESSAR II.

Passive electrical failures have been included in the GESSAR II FMEAs, in Appendix 15c. Passive mechanical failures (pipe break, vessel rupture, valve body failure, pump casing rupture) have not been included. The latter have not been included principally because of their low probability of occurance. In addition, if passive mechanical failures had been included in the FMEAs they would only have been included on a long term basis where their failure could affect safe shutdown. Once the reactor has reached cold shutdown, a passive mechanical failure can be compensated for in so many ways that analysis of such failures in the FMEAs l

was not felt to be very useful.

i i

l l

l i

l

\

421.08 QUESTION We state our position in Section 7.3.2 of Regulatory Guide 1.70 4

that a FMEA should be a detailed analysis demonstrating that tne appropriate regulatory requirements have been met. However, it is not clear in your FSAR if a FMEA addressing all credible failures has been performed. Verify that the appropriate FMEA's have been performed and address the following:

a. The FMEA is applicable to all ESF equipment.

421.08 a RESPONSE In accordance with Regulatory Guide 1.70, Appendix 15C provides for FMEAs on selected systems of Chapters 6,7 and 9. There are a total of 32 FMEAs; either completed in detail in Appendix 15C 1

or identified as requiring the Applicant to provide. In addition, several interfacing systems are identified as requiring FMEAs to be provided by the applicant. The combination of the FMEAs

, detailed in Appendix 15C and those identified to be provided by

! the applicant is applicable to all ESF equipment.

l 421.08 b QUESTION

b. The FMEA is applicable to all design changes and modifications to date.

421.08 b RESPONSE l As presented in Subsection 15C.0.6 the FMEA system-defining documents (electrical, instrumentation, and control drawings, and piping and instrumentation diagrams) utilized in conducting

the FMEAs are annotated versions of the corresponding documents i listed in Table 1.7-1. However, some of the Table 1.7-1 documents were revised (updated) after the FMEAs were completed. In each j case the impact of the document update (s) was assessed and it i

was detarmined that the FMEA results were still valid.

421.08 c QUESTION i

i c. Provisions exist to assure that future design changes or

modifications are included in the FMEA.

i 421.08 c RESPONSE i To assure that future design changes or modifications are included i in the FMEAs, a statement will be added to Subsection 15C.0.6 that i commits the Applicant to assess the impact of future design changes or modifications, on the validity of the FMEA results.

l This will also be added to section 1.9 as an interface requirement.

1 i

i i

ll l

l

. _ _ ___ _ _ _ _ _ -_ _ _ - ----.- _ . - . _ _ -.--- ~ _ ,- - - . -

421.09 QUESTION Identify any nonsafety-related electrical equipment which is assumed in Chapter 15 of your FSAR to successfully operate to mitigate the consequences of anticipated operational occurrences and accidents. For each piece of equipment identified, provide the corresponding anticipated operational occurrence (s) and accidents for which that equipment is expected to function.

421.09 RESPONSE Analyses in FSAR Chapter 15 make no assumptions concerning successful operations of any nonsafety-related equipment to mitigate the consequences of anticipated operational occurences and accidents.

l 1

421.10 OVESTION

( In Section 7.1 of your FSAR, you identify. systems designed and built by you and systems designed by you and built by others.

For the latter, discuss the design interface documents.

421.10 RESPONSE This issue was closed at the GE/NRC meeting October 14, 1982 in Bethesda, Maryland. It was agreed that GE will revise Table 7.1-1 to show GE involvement in both " Designer" and " Supplier" columns for all systems listed except the " Pressure Regulator and Turbine Generator System, which is both designed and supplied by the utility applicant. Interfaces are documented in the systems elementary diagrams: Appendix 7A.

(

1

Table 7.1-1 DESIGN AND SUPPLY RESPONSIBILITY Systems Designer Supplier Reactor Protection System Reactor Protection System (RPS) GE GE Engineered Safety Featured Systems Emergency Core Cooling Spray (ECCS) GE GE High-Pressure Core Spray (HPCS) GE GE Automatic Depressurization System (ADS) GE GE Low-Pressure Core Spray (LPCS) GE GE z CO

." Low-Pressure Coolant Injection (LPCI) GE GE py Y Containment and Reactor Vessel Isolation Control GE GE/U $$

WW d System (CRVICS)

Main Steamline Positive Leakage Control System (MSPLCS) GE GE/U $U Containment Spray Cooling (CS-RHR) GE GE Suppression Pool Cooling (SPC-RHR) GE GE Suppression Pool Makeup System (SPMU) GE bf[U Containment Combustible Gas Control System (CCGCS) GE 6#/

/U Standby Gas Treatment System (SGTS) GE 66dJ j

Shield Building Annulus Mixing GE 66[U Secondary Containment Isolation Control System GE 66[U Containment Isolation Valve Leakage Control Systems u

Air Positive Seal (APS) GE 6f[U yy Water Positive Seal (WPS) GE 6E[U .o wS i

Table 7.1-1 DESIGN AND SUPPLY RESPONSIBILITY (Continued)

Systems Designer Supplier Standby Power System IIPCS Diesel Generator System GE 66[U Emergency Diesel Generator System GE 6E[U Diesel Generator Auxiliaries GE 6E[U Essential Service Water System (ESWS) GE GE[U ESF Area Cooling System GE GE[U w Pneumatic Supply System GE =

6E[U Main Control Room IIcating, Ventilating, and Air Conditioning GE GE/U $o

." System O@

Y $

a xx

RHRS/ Reactor Shutdown Cooling System GE GE/g Remote Shutdown System (RSS) GE U/GE Other Safety Systems Neutron Monitoring System (NMS)

Source Range Monitor (SRM)2 GE GE Intermediate Range Monitor (IRM) GE GE w xw Local Power Range Monitor (LPRM) GE GE @by w-8 1

J O O O

Table 7.1-1 DESIGN AND SUPPLY RESPONSIBILITY (Continued)

Systems Designer Supplier Average Power Range Monitor (APRM) GE GE Traversing Incore Probe (TIP) 2 GE GE Process Radiation Monitoring System (PRMS) GE GE,/gj Rod Pattern Control System (RPCS) GE GE

! High-Pressure / Low-Pressure Systems Interlock Function GE 64/U

! Recirculation Pump Trip (RPT) System GE GE/U N Fuel Pool' Cooling and Cleanup System GE 6([U Drywell/ Containment Vacuum Relief System GE 6([U

',r Q Containment and Reactor / Auxiliary / Fuel Building Ventilation GE GE[U N$

and Pressure Control System yy Containment Atmosphere Monitoring System GE/U U/GE ss as Suppression Pool Temperature Monitoring GE .66/jU Q Reactor Vessel Instrumentation (partial) GE GE $

Control Systems Not Required For Safety Reactor Vessel Instrumentation (partial) GE GE Rod Control and Information System l

Rod Movement Control GE GE Recirculation Flow Contro'l System GE GE Feedwater Control System GE U/GE w

. e t t L_ _)

.~ -

Table 7.1-1 DESIGN AND SUPPLY RESPONSIBILITY (Continued)

Systems Designer Supplier Pressure Regulator and Turbine Generator System U U Performance Monitoring System GE GE Reactor Water Cleanup (RWCU) System GE GE Radwaste System Gaseous Radwaste System GE M[U Liquid Radwaste System GE 6E/U w w

Solid Radwaste System GE 66[U m

-a Area Radiation Monitoring System ( ARMS) GE 67U 5o o ta g Leak Detection System GE GE/U yy E Containment Exhaust GE $$

O M/U Dryvell Purge GE TU ((

Suppression Pool Cleanup (SPCU) GE N[U h Fire Protection System GE/U 6E/U 6

-Breathing Air-Gystem-<-_ 4E - U -

Drywell Chiller GE 6E/U Instrument Air GE 66[U Display Control System GE GE Refueling Interlock Function GE GE w

NOTES mN

1. For mitigation of the rod drop accident only $D
  • O
2. The source range monitor and traversing incore probe are included in Neutron o m

Monitoring System discussion for completeness only; they are not safety sut:sys tems .

O e e

421.11 OVESTION

( Several recent issues related to the instrumentation and control systems have been addressed and resolved by the BWR Owners Group and/or the BWR Licensing Review Group II (LRG II). Revise Chapter 7 and the drawings in Section 1.7 of your FSAR to incorporate the resolution of thesa issues.

421.11 RESPONSE LRG II issues are addressed in Appendix IE of GESSAR II. Chapter 7 will be revised as necessary to incorporate relevant issues associated with Instrumentation and control .

i t

i

\

I 421.13 QUESTION In Table 7-2 of Section 7.1 of the SRP, we provide an applicability matrix for various sections of Chapter 7, including references to the appropriate NUREG documents. We note that you provide general information on this matter in Appendix A of your FSAR. You should be prepared to provide at a forthcoming meeting, more detailed information, using drawings as appropriate, indicating how your proposed design satisfies the following TM1 action items:

a. II.D.3, Relief and safety valve position indication.
b. II.E.4.2, Containment isolation dependability, Positions (4), (6) and (7).
c. II.F.1, Accident monitoring instrumentation, Positions (4),

(5) and (6).

d. II.F.3, Instrumentation for monitoring accident conditions (Regulatory Guide 1.97, Revision 2).
e. II.K.1.23, Reactor vessel level indication.
f. II.K.3.13, HPCS and RCIC initiation levels.
g. II.K.3.15, Isolation of HPCS and RCIC.
h. II .K.3.18, ADS actuation.
1. II.K.3.21, Restart of LPCS and LPCI.

J. II.K.3.22, RCIC automatic switchover.

Discuss the applicability of the resolution achieved by the BWR Owners Group for the items listed above, to your proposed design.

421.13 RESPONSE TMI action items are discussed, along with their applicability to GESSAR II, in Appendix 1A. Each of the issues are discussed in specific detail with reference to NUREG 0737, including mark-up prints as necessary. For example, see Figure 1A.24-1 in connection with Subsection 1A-24 (Item II.D.3). Please indicate specifically where more information is required above that which is already given by the Appendix 1A response for eacn itam.

i i

421.15 Provide an overview of the plant electrical distribution system with (7.1) e@hasis on vital buses and ' divisional separation which will be used (7.7) when addressing chapter 7 concerns in a forthcoming meeting. Use one-line diagrams or other drawings as appropriate.

1.

< sfcm . _.

hGb n/erence /c gue.sNon # 2/./5 w e direc/ your a/tenhon /c Grss4fl~

vo/u m e /8 ,

238 Nuc/ ear /slos?d i sechon 8. I. 2 .

4 h

~ h - e- g 4

8

  • -.-e

- - - -- - - ag , - , , ,

'~ "'

, 4 h 4

p m - +

y---------

7 rm g- ----,-.g- - . - -

r-. - - - - - - - . - - - . , , . ,7- -,--. - - m__- ,_,,,,._,------,-r--- ,

, ----.--.--,------y--- --r-

421.16 OUESTION I'

Identify any "first-of-a-kind" instruments used in, or providing inputs to, safety-related systems. Include any microprocessors, multiplexers or computer systems which are used in, or interface with, safety-related systems.

421.16 RESPONSE The GESSAR II design incorporates the Solid State Safety System which fundamentally replaces relays with solid-state devices.

All hardware components for GESSAR II are identical with those used in the Clinton plant, and also with those planned for TVA, Skagit, Black Fox and Allen's Creek. Therefore GESSAR II, of itself, does not have any first-of-a-kind equipment.

However, these solid-state plant designs employ three basic types of devices which are new compared with Grand Gulf, Perry, Riverbend and previous BWR's. Thses are listed and discussed as follows:

1. The logic itself is solid-state as mentioned above.

Functionally, this logic performs the same (i.e, has the same Boolean expressions) as other BWR 6 relay plants for all safety-related systems except the RPS. Solid-state

, RPS utilizes "2-out-of-4" channels to scram as compared

! with "I-out-of-2 twice" for relay plants.

2. The self-test feature is unique with the solid-state logic.

This feature is described in conjunction with protection system in-service testability in subsections 7.1.2.1.6 of GESSAR II.

3. Analog trip modules (ATM's) replace the more conventional Analog Comparitor Units ( ACU's) for solid-state plants.

Functionally, both types of trip units serve the same purpose, but ATM's are designed to interface with the sel f-test feature.

f

421.17 In Table 3.2-1 of four FSAR, your provided a "Q-List" of structures, (7.1) systems and components whose saf ety functions require conformance to (7.6) the applicable quality assurance requirements of Appendix B to 10 CFR Part d50. Verify that all safety-related instrumentation and controls (I&C) described in Section 7.1 thru 7.6 and other safety-related I&C equipment used in safety-related systems are subject to your QA program implementing the requirements of Appendix B. Indicate how we may determine which specific components shown in the electrical drawings ref erenced in Chapter 1.7 are classified as safety-related.

RESPONSE

All safety-related instrumentation and control (I&C) equipment described in Chapter 7 Sections 1 through 6 and other safety-related I&C equipment used in safety-related systems are subject to quality assurance programs which implement the requirements of 10CFR50 AppendixB, per Table 3-2-1, and Chapter 17.

i Electrical drawings identified in Chapter 1, Section 7 that contain safety-related components are so indicated on the drawing. Specific safety-related components are identified by saf ety division classifications or special symbols as shown in Chapter 1, Figures 1-7-la and 1.7-4.

i 421.18 Provide a detailed discussion of your methodology to establish the (7.1) trip setpoint and allowable value for each RPS and ESF channel, (7.3) including the following additional information:

a. The trip value assumed in your analyses in Chapter 15 of your FSAR.
b. The margin between the combined channel error allowance and the total channel error allowance assumed in the accident' analyses.
c. The values assigned to each corrponent of the coinbined channel error allowance (e.g. , process measurement accuracy, sensor calibration accuracy, sensor drift, sensor environmental -

allowances and instrument rack drift), the basis for these values and your methodology to sum these errors.

d. The degree of your conformance with the guidance provided in Positions C.1 through C.6 of Regulatory Guide 1.105. ,

5:

  • VAh
  • W^ *  ?* t t

l

ATTACHMENT 1

( Instrument Setpoint Methodology The method employed to establish adequate margins for instrument setpoint drift, inaccuracy and cslibration uncertainty as discussed in NRC Regulatory Guide 1.105 is explained by reference to Figure 1. Because of the generic nature of this figure it is not drawn to any scale and is used solely to illustrate the qualitative relationships of the various margins.

Starting with a Safety Limit as indicated at the extreme right hand of the figure, the first' margin extends to the point marked Analytic Limit. This margin is there to account for uncertainties in the calculational model used but excludes allowances for instrumentation. Thus the calculational model can assume ideal or perfect instruments. The next margin is between the Analytical Limit and the Allowable Value of the parametric setpoint, and accounts for instrument errors and calibration capability for the specific instrumentation. The remaining margin which is of interest from a safety standpoint is that shown between the Allowable Value and the Instrument Setpoint. This margin is that which is deemed adequate to cover instrument drift which might occur during the established surveillance period. It follows that if during the surveillance period an instrument has drifted from its setpoint in a non-conservative direction but not beyond the allowable value, then the instrument performance is still within the requirements of the plant safety analysis. In this case, a Licensing Event Report (LER) would not be required.

For completeness Figure 1 shows further margin between the Instrument Setpoint and the Maximum (Licensed) Operating Point for the plant. During plant operation transient overshoots i may occur for certain parameters and instrument" noise" may be l present. The instrument setpoint may also drift in a conservative manner. There must be sufficient margin between the instrument setpoint and the maximum operating point to avoid spurious l reactor scrams or unwarranted system initiations.

l Not all parameters (functional units) have an associated analytical limit, and a Design Basis (DB) limit is indicated. In general, the analytic limit is employed in those cases where a functional unit setpoint is directly associated with an analyzed abnormal

! plant transient or accident as described in the FSAR, Section 15.

l Where a design basis limit is used it is not always possible to provide simple quantification of the lirit, e.g., IRMs are only required to overlap in range with portions of the SRM and APRM ranges. A similiar situation occurs with the main steam I

line radiation sensors which have a setpoint based essentially on previous operating experience.

For further explanation of the methodology details used in establishing the instrument setpoints giver ir ttA4522A", refer to Paragraph 3.L9 and the notes accompanying Table 1 of e tTack ed

  • i

O,

. ~

Figure 1 INSTRUMENT SETPOINT SPECIFICATION BASIS e

I .

i l SETPOINTILIMITS WOP TS AV AL MAX OPERATING SL

. POINT ALLOWA9LE ANALYTICAL SAPf?Y TRIP SETPOINT VAINE - LIMIT (TECH SPEC)

LIMITA:RITERfA (TECH SPEC)

OPERA-

  • MARGINS FOR: 4- TIONAL PROctSS $APETY AVAILABILITY > c - NON LER RANGE - F C READOUT TRANSIENTS 5ll% .

ACCURACY 44.- A NA LYSIS 4 TRANSIENTS FACTORS DETERMINfNO MARGINS:

A. PERTURS ATIONS A. SENSOR AND SIGNAL DURING PLANT A. SENSOR AND S10NAL A. SENSOR AND A. LHitlTING CONDITIONING DRIFTS CONDITIONINO DRIFTS COMPONENT MANEUVERS. TRANSIENT BETWE EN SURVEILLANCE SETWEEN SURVEILLANCE ACCURACY.

8. PROCFSS NOISE. ICAtl8RATIONI TESTS. S. CONSIDER

' ICAllDRATIONI TESTS. 8. SENSOR ANO

' C. CONSIDER INSTRU. INSTRUMENT

- COMPONENT

  • TIME RESPONSE.

! MENT TlVE RESPONSE.

C Allell AT*3N C. ALLOWANCE CAPA EILITY. FOR CALCULA.

TSONAL MODEL UNCERTAINTIES t

5 MUMEAR ENEROY

_ BUSINESS OPERATIONS GEN ER AL C ELECTRIC k

3.1.9 In s t rumen t a t ion 3.1.9.1 Table 1 gives system instrumentation requirements for technical specification and non-technical specification instruments.

3.1.9.2 For response time requirements on Nuclear Boiler System instruments that provide signals to the Reactor Protection System (RPS) refer to the RPS Design Specification Data Sheet referenced in Paragraph 2.1.2.a.

. 3.1.9.3 The values presented are considered to bound the instruments performance with equal to or greater than 95 percent probability assuming a normal distribution. Technical specification instrument setpoints are calculated as follows:

Technical Specification Limit = Analytical Limit i Accuracy + enlibration Nominal Trip Setpoint = Technical Specification Limit i Drif t

(

i

(

b M20 se? A (nuv. t eles) 9

TABLE I INSTRUMENT SPECIFICATION REQUIREMENT MPL NO TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CAllBRATION, OPERATING SCALE LIMIT. MAX. DESIGN POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10; B21-NOO4 TEMP ELEMENT S/R VALVE LEAKAGE REFER N/A +/- G N/A 135 0-600 THERMOWELL DETECTION IN TO DEG F DEG F DEG F SUPP ELEN DISCHARGE B21-NG14 PIPING B21-NOG 1 TEMP ELEMENT RPV HEAD VENT REFER N/A *i- G N/A 135 0-GOO THERMOWELL LEAKAGE TO DEG F DEG F DEG F SUPP W/ELEM DETECTION B21-NG14 B21-RG14 TEMP RECORDER REFER TO 220 N/A 1 % FS N/A 135 AND 0-600 B21-NOO4 DEG F (RECORD) DEG F DEG F ALARM SWITCH AND B21-NOG 1 2 % FS .

(ALARM) 821-NO29 ................................................................................................. .................

TEMP ELEMENT RPV CLOSURE HEAD REFER TO N/A +/- G N/A 550 0-G00 FLANGE STUD TEMP B21-NG48 DEG F DEO F DEG F . -

ETC B21-NO30 ...................................................................................................................

THERMOCOUPLE RPV SKIN TEMP REFER TO N/A +/- G N/A 528 O-GOO AT BOTTOM HEAD B21-NG48 DEO F DEO F REGION DEG F ETC 821-H050 ...................................................................................................................

THIRMOCOUPLE RPV HEAD SHELL REFER TO N/A +/- G N/A 550 0-600 FLANCE TEMP (TCP) B21-NG48 DEG F DEG F DEG F

. ETC

  • ------*........................................g ...gggg,, ,, , ,,, ,,

m -

m A *

'iy w.. ) , i TABLE ontinued) '

MPL NO TYPE FUNCTION NONINAL TECH. SPEC ACCURACY CAllBRATION, OPERATING SCALE LIMIT, MAX.DESION POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 101 B21-NG48 TEMP SWITCH RPV TEMP 75 N/A +/- 6 N/A B21-NG49 W/ ALARM AND REFER TO O-600 (REFER TO DEO F DEO F B21-NO29 DEO F B21-NG50 TEMP RECORDER B21-NO29 D21-NG52 B21-NO30 B21-R643 (LOW B21 ,NO30 B21-N050 TEMP ALARM) B21-N050) .

B21-RG43 TEMP RECORDER RPV TEMP REFER TO N/A +/- 6 N/A REFER TO O-600 REFER TO B21-NG48 DEO F B21-NO29 B21-NO29 DEO F ETC B21-NO30 B21-NO30 B21-N050 B21-N050 B21-NO40 TEMP ELEMENT MONITOR STEAM N/A N/A +/- 1, 5 s N/A 544 400-550 THERMOWELL LINE TEMPERATURE DEO F DEO F SUPP ELEM DEO F W/D21-NG01 A#B B21-NG01 TEf1P XHTR MAIN STEAM LINE N/A N/A +/- 1.5e N/A AaB W/B21-NO40 544 400-550 TEMP DETECTION DEO F DEO F DEO F (TEST JACK)

BDI-NOGO TEMP ELEMENT STEAM LINE DRAIN N/A N/A +/- 6 N/A B21-N059 544 0-600 THERMOWELL TEMP DEO F U21-N057 SUPP/ ELEMENT DEO F DEO F W/SEL SWITCH A 4 000

' B21-NOG 4 AND INDIC D21-ROO8 D21-NOG 4 TEMP SELECTOR REFER TO N/A N/A N/A N/A 544 0-600 s/ SWITCH D21-NOGO DEO F DEO F W B21-ROO8 ETC '

Combined accuracy of temperature element and temperatur6 transmitter.

r TABLE 1 (Continued)

MPL NO TYPE FUNCTION HONINAL TECH. SPEC ACCURACY CAllBRATION, OPERATING SCALE LIMIT, MAX. DESIGN PolNT RANGE SET PolHT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-ROO8 TEMP IND MONITOR STEAM N/A N/A +/- G N/A 544 0-600 (TI) W/ TEMP SEL LINE DEG F DEO F DEG F SWITCH DRAIN TEMP B21-NOG 4 821-N041 TEMP ELEMENT MONITOR FEEDWATER REFER TO N/A +/- 1.5s N/A 420 300-450 A B CSD THERMOWELL TEMPERATURE B21-NGO2 DEG F DEO F DEG F SUPP W/ ELEMENT A B CSD 021-NGO2 TEMP XHTR MONITOR FEEDUATER N/A N/A +/- 1.5s N/A 420 A B CSD 300-450 TEMPERATURE IN DEG F DEO F DEG F CONTROL ROOM

' 21 -NG5 8 TEMPERATURE NONITOR FEEDWATER N/A N/A +/- 1.5m N/A A B CSD 420 300-450 XMTR TEMPERATURE DEO F DEG F DEO F IN CONTROL ROOM (NECLENET READ OUT)

B21-NO27 LEVEL XHTR PROVIDE SIGNAL N/A N/A +/- 6 N/A 34.9 IN 0-400 SHUTDOWN TO D21-RGOS IN _

LEVEL (NORMAL IN WATER LEVEL)

B21-NG05............................................................................................__.................._..

LEVEL IND PROVIDE REACT N/A N/A +/- G N/A 34.9 IN SHUTDOWN 0-400 WATER LEV AND IN (NORMAL IN LEVEL PRES INDICATLON WATER IN MAIN CONT RM t LEVEL)

  • Combined accuracy of temperature element and temperature transmitter.

h O m O .

O .

- . A .

g O A

  • TABLE 1 ontinued) ~'

MPL NO TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CALIBRATION, OPERATING SCALE LIMIT, MAX.DE510N PolNT RANGE SET PolNT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-NO44 LEVEL XMTR PROVIDES SIGNAL N/A N/A +/-6 N/A OFF CSD TO B21-RGl5 & -150 TO 50 IN SCALE IN WTR B21-RG10 (FULL ZONE 1 B21-RG10 LEVEL FROVIDES N/A N/A +/-2 N/A INDICATOR LEVEL IND OFF -150 TO So IN SCALE IN WTR (W/821-NO14D)

FUEL ZONE B21-RG15 LEVEL PROVIDES N/A N/A

+/-2 N/A OFF NETER LEVEL INO -150 TO 50 IN SCALE IN WTR (W/B28-NO44C)

FUEL ZONE B28-NO91 LEVEL XMTR PROVIDE SIGNAL REFER TO NOTE I A B ESF TO B21-NG01 34.9 -160 TO 60 D21-NG91 IN A B ESF B21-NG92 IN WATER A B EEF (NORMAL WATEft B21-NG93 LEVEL 3 AB 021-NG91 LEVEL ____...___. ___.............____............................................................._.......

LEV 1 INIT -140.8 -152.0 2.2 .44 A B E4F INDICATOR ADS RHR LPCS 34.9 -160 TO GO IN -154.2 IN 2.2 IN SWITCH IN WATER PROVIDES SIG INORMAL IN IN WATER TO B21-NG92 A B EaF LEVEL) 828-NG92 LEVEL LEV 2 INif -3G.5 A B ESF -38.7 2.2 .44 34.9 -160 TO 60 SWITCH RCIC IN -40.9

' IN 2.2 IN IN WATER PROVIDES Slo TO * (NORMAL IN IN WATER B21-NG93 ASB l LEVEL)

I.

TABLE I (Continued)

HPL NO TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CALIBRATION, OPERATINO SCALE LlHIT. HAX. DESIGN POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-NG93 LEVEL LEV 8 TRIP 53.2 55.4 2.2 .44 34.9 -160 TO 60 AaB SWITCH RCIC IN 57.G IN .2.2 IN IN WATER (NORMAL IN IN WATER LEVEL)

B21-NO73 LEVEL XMTR PROVIDE SIGNAL REFER TO NOTE 1 34.9 C G DSH -160 TO 60 TO B21-NG73 B21-NG73 IN IN WATER C O DSH C G DSH (NORMAL B21-NG74 WATER C&H LEVEL)

B21-NG73 LEVEL LEV 2 INIT -3G.5 -38.7 2.2 dl 34.9 C O D&H INDICATOR HPCS

-160 TO 60 IN -40.9 IN 2.2 IN IN WATER SWITCH (NORMAL IN IN WATER LEVEL) -

021-N674 LEVEL LEV 8 INIT HPCS 53.2 55.4 2.2 C&G SWlTCH

.44 34.9 -160 TO 60 IN 57.6 IN 2.2 IN IN WATER (NORMAL IN IN WATER LEVEL)

B28-NO99 LEVEL XMTR PROVIDE SIGNAL REFER NOTE 1 A E BSF 34.9 160 TO 60 TO B21-NG99 TO A B ESF IN IN MATER B28-NG99 (NORMAL A B ESF WATER LEVEL)

B21-NG99 LEVEL LEV 2 TRIP -36.5 N/A 4.4 A B EaF N/A 34.9 -160 TO 60 INDICATOR RECIRC IN IN IN WATER SWITCH '

IN (NORMAL WATER LEVEL)

I I

l O 1 0- ___Q

v.q, ^ O G

% ) f Q) (w TABLE (Continued)

MPL NO TYPE FUNCTlON NOMlNAL TECH. SPEC ACCURACY CALIBRATlON. OPERATlNG SCALE LIMIT, MAX.DESION POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-N095 LEVEL XHTR PROVIDE LEV IND REFER TO NOTE 1 34.9 AEB TO O TO 60 B21-NG95 IN IN WATER B21-NG95 ASB ASB (NORMAL WATER LEVEL)

B21-NG95 LEVEL LEV 3 l NIT ADS 11.4 10.8 .60 AEB .12 34.9 0 TO 60 INDICATOR IN 10.2 IN .G IN SWITCH IN WATER (NORMAL IN IN WATER LEVEL)

B21-P081 LEVEL XMTR PROVIDES LEV IND REFER TO NOTE 1 A B L40 34.9 IN -160 TO 60 TO B21-NG81 B21-NG81 (NORMAL IN WATER A B CSD B21-HG82 WATER A B CSD LEVEL)

B21-NG81 LEVEL LEV 1 INIT . -149.8 -152.0 2.2 A B CSD INDICATOR

.44 34.9 IN -160 TO 60 NS4(MSIV) IN -154.2 IN 2.2 (NORMAL IN WATER SWITCH

!!A TER IN IN LEVEL)

B21-NG82 LEVEL LEV 2 INIT -36.5 -38.7 A B CSD 2.2 .44 34.9 -160 TO 60 SWITCH NS4 IN -40.9 IN 2.2 IN IN WATER (NORMAL IN IN WATER LEVEL)

B21-RG04 LEVEL MONITORS REACT N/A N/A */- 2.2 N/A 34.9 IN -160 TO 60 INDICATOR WATER LEV IN (NORMAL (W/B21-NG01 C) IN MAIN CONT RM IN WATER

, WATER LEVEL)

I e

e

,. w - A  %

".s.

A*  %

TABLE (Continued)

MPL NO TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CALIBRATION, OPERATING SCALE LIMIT, HAX. DESIGN POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-RG23 LEVEL NONITORS REACT N/A N/A I E N/A 1025 PSIO O-1500 PSIG A&B & PRESSURE WATER LEVSPRES FS RECORDER 34.9 IN -160 TO 60 IN WATER 821-NO80 LEVEL PROVIDE SIGNAL REFER TO NOTE al 34.9 IN 0-60 A B CSD XMTR TO B21-NG80 (NORMAL IN WATER 821-N680 A B CSD WATER A B CSD B21-NG83 LEVEL)

A B CSD B21-NG80 LEVEL LEV 3 INIT RPS 11.4 10.8 .6 IN .42 34.9 IN 0-60 A B C&O INOICATOR RHR(ISO) IN 10.2 .G (NORMAL IN WATER SWITCH WATER (W/B21-NO80 IN IN LEVEL)

A B CSD) 821-NG83 LEVEL LEV 8 l NIT RPS 53.2 IN 53.8 .6 .12 34.9 IN A B CSD SWITCH O TO 60 54.4 IN .6 (NORMAL IN WATER WATER IN IN LEVEL)

B21-ROO9 DIFFERENTIAL RPV N/A N/A */- 6 N/A ASB 34.9 -160 TO 60 PRESSURE DIFFERENTIAL IN (NORMAL INDICATOR IN WATER PRESSURE WATER LEVEL)

.........................................___.............~_............................................__...........

B21-NOG 8 PRESSURE REACT PRES REFER TO NOTEa 1 A B ESF 1025 0-1200 XHTR S/RV SET PT

  • B21-NGG8 PSIO PSIO SIGNAL TO A B ESF B21-NGGO ETC

4 e

EE . . . . . .

LG . . . . .

AN . 0 . 0 . 0 . 0 0 . 0 CA . 0 . 0 . 0 . 0 . 0 . 0 SR . 2G . 2G . 2G . 2G 2G

. 1I . 1I . 1I . 1I . 1I

. 2G .

. . 1I S . S . S . S . S . S

. 0P . 0P _ 0P . 0P _ 0P . 0P GT . . . . . .

NN . . . . . . .

II . . . . . .

TO . . . . . .

AP . 5G . 5G . 5G . 5G . 5G . 5O .

R . 2I . 2I . 2I . 2I . 2I E . 0S . 0S . 2l

. 0S . 0S . 0S . 0S P . 1 P . 1 P . 1 P . 1 P . 1 P . 1 P O . . . . . _

) . . . .

.NTW0 . . . _

NGFO1 . . . . . .

OI I L . . . . . .

I SRLE . . . . . .

TEDAT . . G . G . G .

A D.

O . 0 . 0. I . 0. I . 0. I . 0. IG .

0.GI R N . 5SI . 0.5 S . 0.5 S . 0.5 S . 0.5 S

. 0

. 5S DX ( . 31 P . 31 P . 31P . 31P . 31 P . 31P I A . . . .

L t1 A . . . . .

C . . . . .

) . .

0 . . . . .

Y 1 . _ _ . .

C . .

A E _ 0.GI _

. 0.GI _

0.GI .

. 0.GI .

. 0.GI .

0.Gt R T _ 5S . 5S . 5S . 5S . 5S U O _ 1 P . 1 P . 5S

. 1 P . 1 P . 1 P . 1 P C N _ . . . . . .

C ( _ . . . . .

A _ . . . . .

. 1 6 . 1 6 . 1 6 .

_ . . . 4 5 . 6 7 _ 5 6 .

C .LNT _ . . . 9 9 . 9 9 _ 9 9 .

ETAGI _ . . . / / . / / . / / ,  ;

I' I CI M _ .83O . 83G . 83G . 8 3G . 8 3G . 8 3G _

1 0I . 24I S. IMI TEL SI . 81 S . 11 S

. 35I

. 19 S

. 4

. 0 0S 6I . 2

. 8 1 4I S

. 8

. 0 0I S

HLYD . 11 P . 11 P . 1 1 P . 1 1 P . 1 1 P . 1 1

P C L . . . . . .

1 E A . . . . . .

T N . . . . . .

A . . . . . .

L T . . .

A N . 3G . 1I3G . 3G . 3 G . 3 G

. N I

. 0I . . 2I . 36I . 1 6I

. 3 G O . 1 S . 7GI I

. 1 S . 9 S . 02S . 8 4S . 03S M P . 1 P . 1 P . 1 P . 1 9P . 1 0P . 1 9P O . . . . . .

N T . . . . . .

E . . . . . .

S . . .

. . . . ) . ) . )

. F . F . F . E . E .

. RE . RE E

. RE . R S . R S . R S*

. OI . OI . OI . O O . O O . O O .

. FL _ FL . FL . F L . F L . F L

. E E .

N . VR

. VR E . TC . TC . TC ._

_ VR . VEE . VEE . VEE O . R . R _ R . RSR . RSR . RSR I

. /E3 . /E) _ /E) . / / . / / . / / .

T . SR3 . SR3 _ SR3 C . U . U

. EWN . SWN . SWN N

_ U . OE . OE) . OE

. SSE SSE _ SSE . SLP) . SLPH . SLP)

U . PST . PST . PST . P OW . P OC F . I EO . I EO . IEO . I WEO

. P OD

. I WEI . I WEI

. RRN . RRN . RRN . RORL . RORH . RORN .

. TP( . TP( . TP( . TL( ( . TL( ( . TL( ( .

) E . R . . . . .

d PY . EO . E . E . E _ E . E e T

. RT . R . R . R _ R . R s u . UAH . UH . UH . UH . UH . UH n . SCC

. SIT

. SC

. ST

. SC . SC . SC . SC i . ST . ST . ST . ST .

t . EDI . EI . . EI . EI .

n . RNW PIS

. RW .EI

.RW . RW . RW

.EI

.RW .

o . PS PS . PS . PS .PS C . . .

( . . . .

1

. 8 . 9 . 0 . 6 . 8 7

. GF . GF . .

GS . GS _7F GS

.GN-1 1 F 1 E O L N l

NE

. NE

.NE

.GS NE

.GN l 8 D 5 B 8 B 1 F 1 B 1 F A L 2 2 2 2a 2 2 T F BA BA 8A 8E 8A B B".

N

,p ^

P a ['N TABL Continued) ) \U )

NPL No TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CALIBRATION, OPERATING SCALE LIMIT, NAX. DESIGN PolNT RANGE SET PolNT ANALYTICAL DRIFT DESIGN ALLOW LIMIT B21-NO78 PRESSURE NONITOR STEAN REFER To NOTE al A B CSD XNTR 1025 0-1500 DONE PRESSURE & B21-N678 PSIO PROVIDE SIGNAL TO PSIG B21-NG79 B21-NG78 A B CSD A B CSD (ETC) f ...................................................................................................................

821-NG78 PRESSURE NONITOR STEAM 1064.7 1079.7 15.0 3.0 1025 A B CSD INDICATOR DONE PRESSURE & PSIG 0-1500 1095 l'S I G 15 PSIG

, SWITCH TRIP RPS PSIO PSI PSIO B28-NG79 PRESSURE MONITOR STEAN 135 150 15.O 3.O 1025 A B CSD SWITCH DONE PRESSURE & PSIG 0-1500 IG5 f *S t 15 PSIO TRIP NS4 (RHR ISO) PSIO PSI PSIO B21-NG97 PRESSURE NONITOR STEAN 533 542 ESF SWITCH 16.8 .098 1025 0-1500 DONE PRESSURE & PSIO <550 PSI 8.4 TRIP LPCS RHR PSIO PSIO PSIG PSIG 821-NG98 PRESSURE NONITOR STEAN 533 542 16.8 ESF SWITCH DONE PRESSURE &

.098 1025 0-1500 PSIO <550 t*S t 8.4 TRIP LPCS RHR PSIO PSIO PSI PSIO 1

821-N058 PRESSURE NONITOR STEAM REFER TO NOTE al 1025 A B ESF XNTR DONE PRESSURE 74 021-N658 0-1200 PROVIDE SIGNAL A B ESF PSIO 10 B21-NG50 PSIO A B ESF '

. I.

I

TABLE I (Cont inu ed)

MPL No TYPE FUNCTION NONINAL TECH. SPEC ACCURACY' CALIDHATION, OPERATING SCALE LIMIT, MAX. DESIGN PolNT RANGE SET PolNT ANALYTICAL DRIFT DESIGN ALLOW LIMIT 1

B21-NG58 PRESSURE MONITOR STEAM 1925 N/A +/- IS N/A 1025 0-1200 l A B ESF INDICATOR DONE PRESSURE S PSIG PSI PSIO PSIO i

SWITCH TRIP RECIRC PUMP 821-N067 PRESSURE MONITOR DRYWELL REFER TO NOTE al C O D&H XMTR PRESSURE & B21-NG67 0-1 PSIO 0-)

PSJO PROVIDE SlONAL C O DSH TO B21-NGG7 C O DSH B21-N667 PRESSURE MONITOR DRYWELL 1.88 1.93 .06 .02 0-1 0-5 C O D5H INDICATOR PRESSURE AND PSIG 2.00 PSI .05 PSIG SWITCH PSIO TRIP HPCS PSIG PSI l

R21-NO94 PRESSURE MONITOR DRYWELL REFER TO NOTE #1 A B d&F XMTR 0-1 0-5 PRESSURE S B 21 -N694 PSIO PSIG PROVIDE SIGNAL A B EaF TO B21-N694 A B E4F B21-NG94 PRESSURE MGNITOR DRYWELL l.88 1.93 .06 A B ESF .02 0-1 0-5 INDICATOR PRESSURE AND PSIG 2.00 PSI .05 SWITCH PSIG PSIO PROVIDE SIGNAL TO PSIG PSI RHR LPCS ADS RCIC 821-N076 PRESSURE MONITOR MAIN REFER TO -NOTE #1 A B CSD XMTR 997 O-1200 STEAM LINE PRES S B21-N676 PSIG PROVIDE SIGNAL TO PSIG A B CSD B21-NG76 .

A B CSD ,

...........................................................~... ....................................................

E

I
@ . O J G -

m p

]

  • i

)

TABLE G

(Continued) o NPL NO TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CALIBRATION. OPERATING SCALE LIMIT, MAX. DESIGN POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-NG7G PRESSURE MONITOR MAIN 849 837 12.0 2.4 A B CSD INDICATOR 997 O-1200 STEAM LINC PRES & PSIO 825 PSIO 12 PSIO PSIO SWITCH TRIP NS4 PSIG PSI

. . . . . . . . PRESSURE B21-N075 ..........................................................................................................

MON CONDENSOR PRES REFER TO NOTE si >27 IN A B CSD XHTR (VACUUM) & 0-30 IN B21-NG75 HG HG PROVIDES SIO TO A B CSD B21-NG75 A B CSD B28-NG75 PRESSURE MON CONDENSOR PRES 9 IN 8.7/9.3 .6 IN HO A B CSD INDICATOR (VACUUM) &

.2 >27 IN 0-30 HO .3 HO IN HO SWITCH TRIPS NS4 8.1/lo.C IN HO IN HO 821-NO97 PRESSURE MONITORS STEAM REFER TO NOTE el A&B XMTR OFF 0-600 DONE PRESSURE & B21-NG97 SCALE

-l PROVIDES SIGNAL PSIO B21-NG98 TO B21-NG97 A&B A&B i ........ PRESSURE B21-NG97 ...........___....___.............__................___...............

MONITORS STEAM 533 542 16.8 A&D INDICAYOR .098 OFF 0-600 DOME PRESSURE & PSIO (550 PSIO 8.4 OCALE SWITCH TRIPS RNR PSIG PSIO PSIO B21-NG98 PRESSURE MONITORS STEAN 533 542 16.8 .098 ASB SWITCH OFF 0-600 DONE PRESSURE & PSIG <550 PSIG 8.4 SCALE l TRIPS RHR PSIO PS I,0 PSIG I

1

TABLE I (Continued)

MPL No TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CALIBRATION, OPERATING SCALE LIMIT, NAX. DESIGN POINT RANGE SET POINT ANALYTICAL INCTE 101 DRIFT DESIGN ALLOW LIMIT (NOTE 10)

, B21-ROO4 PRESSURE MONITORS RES ACT N/A N/A O.5 1 N/A 1025 0-1500 ASB INDICATOR STEAM DOME PRES FS PSIO

. PSIG B21-NO32 DIFFERENTIAL MONITOR CORE N/A N/A O.5 % N/A 22 0-30 PRESSURE PLATE DEVELOPED FS PSID INDICATOR PSID HEAD B21-ROO5 DIFF PRES NON JET N/A N/A +/-25 N/A 26 0-30 INDICATOR PUMP FS PSID PSID DEVELOPED HEAD B21-NGOG TURBIDITY FEEDWATER 205 INC N/A +/-2X SWITCH N/A (18% O-1005 SAMPLE FS W/ ALARM -CORROSION PRODUCT 55 DEC NONITORING B21-RG22 TURBIDITY FEEDWATER N/A N/A +/-25 RECORDER N/A (18% O-1005 SAMPLE FS

-CORROSION PRODUCT NONITORINO 821-RG59 AC METER NSIV CONTROL N/A "N/A +/-2%

B21-RGGO N/A 130 NA O-250 NA

  • FS B21-RGG1 B21-RGG2
  • A B CSD
  • I a

G -

O -

O. .

n r R '

dh.

'? h-/ Q TABLE I (Crntinued)

NPL NO TYPE FUNCTION NOMINAL TECH. SPEC ACCURACY CAllBRATION, OPERATING SCALE LIMIT, MAX. DESIGN POINT RANGE SET POINT ANALYTICAL (NOTE 10) DRIFT DESIGN ALLOW LIMIT (NOTE 10)

B21-RGG3 AC METER FEEDWATER BY BY BY BY BY BY (A/B) INLET OTHERS OTHERS OTHERS OTHERS OTHERS OTHERS CHECK B28-RGG4 SOV (A/B)

B21-NOO5 FLOW STEAM LINE N/A N/A N/A N/A N/A N/A ELEMENT FLOW RESTRICTOR (REFER TO PARA 3.1.5)

B21-Z001 FEEDWATER FEEDWATER N/A N/A N/A N/A N/A N/A NONITOR CORROSION MONITOR 821-F022 POSITION MSIV CLOSURE 94 5 93 2 +/- 2X +/- 2X OPEN 0-100 2 D28-F020 SWITCH SCRAM OPEN 90 2 +/- 15 A B CSD , OPEN ADS TIMER TIMER ADS 116 117 +/- 2 +/. 1 N/A O-150 INITIATION SEC 120.0 SEC +/- 2 SEC -.

DELAY SEC SEC j

.................................................................................................__.............. l I

i t

I,

NUCLEAR ENER3Y BUSINESS CPERATl3N5 GENERAL h ELECTRIC 5

NOIES:

1. Refer to master trip unit for overall accuracy, drif t and catioration e tc requirements including transmitter.
2. Water level instrumentations are referenced to instrument zero waton is 529.75 inches aoove vossol zero. Fuel Zone Instrumentation are ref erenced a t 363.5 incnos (B21-N044, B21-2610, B21-R615) , wnica is at the top of tne active fuel.

I

3. Refer to Paragrapa 3.1.3.6 for reclosure pressure.
4. Instrument Accuracy. The quality of freedom from error of tne comple te tastrument cnannel from sne sensor input enrougn tne trip dey tco out put includind tno coariaed conformity, nysterosis and repeataa tlity errors.
5. Catteration Accuracy. Tne quality of freedom from error to wnica tne trip se tpoint is catiorated with respect to the desired so tting, including Octa calibration instrumentation accuracios and calibration proceduro allowancos. Wnon associated with tne calioration instruments; this term is some times referred to as ! Resolution;.
6. Instrument Drift. The chango in ene value of the process variaole, at vnica tne trip action will actually accur, .cotwoca tno time tne nominal ,q trip se tpoint is calibrated and a subsequent surveillance test,.due to all causes, .as measured in terms of the instrumentation indica tor scato.

The value of the process varisolo at wnica the trip action will ac tua11f accur at tuo calioration is caten to De tne intended nominal trip so tpoint value.

7. Analytic al Limit. Tae value of tne sensed process varisolo estaolisned as part of the saf ety analysis, . prior to wnica a desired action is to no initiated to prevent tne process variaolo from reacning tne associated design saf e ty limit.

1 l 8. Tocanical Specification Limit. The limit prescrioed as a license condition on an important proces s variable.

9. Nominal Trto Setsoint. Tne intended calibration point at enica a trip action is set to operato, commonly the conter of an acceptaole range of ,)

l trip operation.

l

10. Instrument accuracy, calioration and drift specifications are plus and minus ( +) the value specified.

meo sof a iserv saf es p l

l

1 421.19 Discuss your methodology and rationale for determining th'e setpoint '

(7.6) values associated with the various leak detection systems (LDS) discussed in Section 7.6 of your FSAR. Discuss details of the manual bypass switch which will be used during testing of the leak detection system for the RCIC, including its conformance with the guidance pro-vided in Regulatory Guide 1.47. Discuss the applicability of your

response on this specific leak detection system to other such systems described in Section 7.6 of your FSAR.

k*0fc*'e r f5 <pp:a~

&sd meerkddeyy- J u/n%4g &clb <=L m a & uspc,-re X . p ui k y2/ 9 Dg/cu~u &

Thi 9;v,cl,y n<,g )i 2L us aud 6e Jua.xJ ist # a cc z ~I: .

Rh ou,ua- ( /><yn sA4(ico,4ckJ)kpim' a pr Ap.: prX & Q .tbhk4h%

byk a d gn A'ctc ixp % Ee4 % - %W .na '

smu-w% gz4 &p,u A ri,x.pws/e ' spa Aa 6 ypsi "& "Qu 6 k G yp e s." .Zin bpe i od wm%,, opphu 4 % luk di& C pn % qf 2b Scic mk% hye & den et g4d- Acic c<pn 6 ta~ % r1 cpv% - ELi nz :e <f a-t ME $$r MN! k.o;e& N'y & & l 'l?-

RE;E E 421.20 Discuss in Chapt:r 7 of y:ur FSAR, the d:. sign crit;.ria you have l; , - [, p, established to prevent trapping of air or noncondensable gases in 5y g,

! the reactor pressure vessel instrument sensing lines. Discuss the applicability of these criteria to safety-related instrument sensing lines.

RESPONSE

The criteria to prevent trapping of non-condensible gases in the RPV

' sensing lines are as follows:

1) the instrument lines are required to be sloped downward from the vessel to the sensors whereever local instrument racks can be located such as to accornodate the slope. A slope of approximately 1" per foot is specified to assure that gas bubbles will migrate back into the RPV. Lesser slopes required engineering approval. The instrument line slope is required to be maintained through the drywell penetrations area except where structural interferences k

make it impractical to maintain the 1" per foot slope. In such cases a 1" per foot slope is allowed in this area.

2) Instrument lines for liquid service are required to be installed for self venting back into the process or be provided with high point vents to release trapped non condensibles after initial filling and thereafter if necessary.

Globe valves are required to be mounted with their stems horizontal to reduce the amount of gas that can be trapped in the valve body to a practical minimum.

Orifices in impulse lines are concentric to obtain optimum accommodation of venting and avoidance of plugging by foreign particles. The slight heel of non condensibles resulting from this practice does not introduce any instrument error.

( 21.20 3) Condensing chambers are connected to the RPV by 1" IPS minimum (cont'd) nozzles which are insulated to within 18 inches of the condensing chamber, thus making the condensing area and the amount of condensate draining back to the RPV more uniform and predictable. The evaluation of the condensing chamber above the vessel instrument tap is limited to provide favorable conditions for the non condensibles to diffuse back into the steam volume so that the accumulation of non condensibles will not become high enough to impair the condensing chambers function of maintaining the reference column level.

Conservative analysis has detemined that with a condensing chamber located 4 feet above the vessel nozzle the maximum non condensibles partial pressure is less than 300 psi which would not reduce the condensing rate unacceptable since it would not prevent sufficient steam from condensing to maintain the reference level.

The foregoing measures are consistent with the safety functions performed by the vessel sensing lines.

l

FEU;Vic l 1

i,Tn, ' 5 *' z 421.21 Provide impulse line routing criteria for safety-related y";

( pressure and flow instrumentation.

RESPONSE: l Safety related pressure and flow instruments sensing lines are required to be routed such that the single failure criterion is complied with and also such as to avoid unacceptable errors from trapped non condensibles. Instrument lines are assigned to mechanical separation divisions and the instruments served by them are assigned to electrical divisions of the same number. In some cases it is necessary to serve more than one division of instruments from a single flow element. These special cases are analyzed on a case by case basis for compliance with safety criteria and shown to be acceptable.

Redundant sets of instrument lines for flow sensing (e.g., Leak k Detection sensors) are required to be separated so that an event for which these lines provide sensory infomation necessary to initiate the mitigating action cannot cause disabling of the sensing lines unless there is provided additional backup by means of diverse sensing or additional redundancy not affected by the same event. (An example of diverse backup is ambient temperature backup for excess flow sensors).

Redundant sensing lines are required to be physically separated except where convergence is unavoidable such as at the flow element itself as in the case of the main steam flow sensors and the recirculation flow sensors. Each of these cases has been analysed to show that localized failure of redundant sensing lines tkt S* Gli kehen does not impair,as explained on the next page:

421.21 (cont'd) 1. Main Steam Flow Sensing for Main Steam Isolation Valve Closure:

j A main steam line break within the drywell does not have to be sensed by the steam line flow sensors because the MSIV closure cannot isolate such a break. The high flow sensing is to protect against a break outside the drywell/ containment. The sensing lines are widely separated outside the containment, they are outside the steam tunnel and on opposite sides of it so they are not vulnerable to damage from the event they protect against.

2. Recirculation Flow Sensors for Flow Reference Scram:

The instrument lines for Recirculation flow converge at a single ef.4% &

sensing pefft causing pipe whip or jets that could break or crimp an instrument line. It has been determined that a break of sufficient magnitude to be considered damaging to these

( lines would be sufficient to increase the drywell pressure to the scram point very quickly and thus obviate any need for the flow reference scram to be operative.

Pressure sensing lines for the reactor vessel are also designed and routed to serve as reference pressure lines for the reactor pressure i

I vessel level measurements. Therefore, they follow the same venting, draining, and azimuthal dispersion and limited vertical drip in the drywell as specified for the level reference lines. The routing criteria for these lines are as follows:

1. Redundant sets of instrument nozzles for reactor vessel level (pressure) are required to be widely dispersed around the periphery of the vessel. (Azimuthsare 15', 165 , 195* and 345 ).
2. Instrument lines are required to maintain divisional separation as they run radially from the vessel nozzles through the drywell 1

and thence to local instrument racks located in the corresponding four quadrants of the containment.

? -

421.21 3. Vertical elevation changes for the pairs of level sensing lines

'ont'd)

( are required to be equal within + or - 1 foot inside the drywell where ambient temperatures can vary over a wide range. (from nonnal to LOCA environment) This practice results in automatic correction for drywell temperature effects and thus keeps errors resulting from varying water density predictably low.

4. Slopes of the instrument lines are required to be adequate for effective venting of non condensibles and to permit effective flushing. This is obtained by a slope of approximately 1" per foot.
5. The vertical elevation difference from the condensing chambers to the drywell penetration is required to be not more than four feet to limit the potential error which might result from instrument line boiloff under condition in which the RPV is cooler than the drywell (in the event that the drywell is r.aintained above 212 F for a time sufficient to permit gross boiloff of the reference column.)

l l

{

a

. l QUESTION _

( in Section 7.2.1.1.F.2 ef our FSAR, you indicate that the reactor system mcde 421.22 switch is used for protective functions, restrictive interlocks and refueling equip-(7.2.1) ment movement. Discuss how this mode switch is incorporated into the overall design so that the single failure criterion and separation requirements are satis-fled. Use detailed drawings and schematics as appropriate.

RESPONSE

421.22 The Reactor Protection System (RPS) mode switch provides bypasses and iryter-locks associated with various plant operation modes; RUN, START / HOT STAND-BY, REFUEL, & SHUTDOWN.

The mode switch has four contact blocks, each physically separated within com-partmental barriers. These contacts (A, B. C & D BLOCKS) perform interlocking functions within their .issociated channels (RPS A1,81, A2 & B2 respectively).

The mode switch, as incorporated in the Reactor Protection System, meets system design requirements of separation and redundancy.The Reactor Protection System is a dual trip system with two channels per trip system. Trip of a single channel trips one trip system. Both trip systems must be tripped to initiate scram.

Failure of any one contact block will not prevent normal protective action of the safety system (scram), nor will it cause a scram.

i l

l l

l

,x,- --G-.k- .- np - .__ 1 -

--~, -

J l

42123. G&

.- . _ . . . I . DM Bs /JaccepC $ b 5; Q 4 e f Gj 0 c 4 Wf yu+~f W & aZa at + ~ cemr).

/?.ap,ae Qp $ gp;reL f m 7 LuTP?"-

1 w w 4-1 i

l I

i i

i

~

. veutsvtu

~

im 1219p y2/43 hap-</ 1 P.9 Sir /K The basic elements of the decision making logic of the NSPS are standard MIL grade CMOS logic elements, in dual in-line epoxy packages, mounted on multilayer printed circuit cards.

CMOS logic was chosen for the NSpS application because of its high noise imunity compared to other types of solid state devices. With the CMOS devices powered by 12 vde, it takes an input greater than approximately 4 volts to switch the output on a low to high transition, and less than approximately 8 volts to switch on a high to low transition. Thus, noise spikes of consider-able magnitude can be tolerated on the input lines without causing errot .ous logic states. As a comparison, TTL logic which must be operated at +5V has a low to high minimum threshold of approximately .7 volt.

Numerous design techniques have been utilized to reduce the possibility of any significant electrical noise being coupled into the logic circuitry.

All inputs and outputs that leave the NSPS cabinets are buffered and isolated, and internal wiring is routed to prevent " crosstalk" or radiated electromagnetic interference.

( Specifically, prevention of electromagnetic conducted interference is accomplished in the following ways.

Power Lines: Conduction of EMI via power lines to the logic elements is prevented by the use of switching power supplies which are speci-fied by the manufacturer to have a maximum noise spike of 62 mv.

In addition, each logic card has single pole filters on the power input to remove any remaining high frequency noise.

Input signal lines: Inputs from other separation divisions, and from nondivisional sources are processed through optical isolators

  • l which are also filtered on the input side. Inputs from same-division l sources such as the control room panels or field sources are processed through Digital Signal Conditioners (DSC's) which are filtered and optically coupled. Inputs to trip units are current loops and there-fore not vulnerable to EMI.

i i

l l

l l

l

, ....m._..~._.... . . , . . . . . . . . . . . . ..

,g Page two Output signal lines: Outputs to actuated devices pass through load drivers which have pulse transformer coupling between input and output stages. Outputs to other logic eierents in other divisions pars through optical isolators. ,

Internal wiring: Interconnections between logic cards is on a backplane of wire wrapped terminals. The connections are made point to point so that groups of wires do not run in parallel for long distances. Power wiring is routed as far from signal wiring as possible. The high current wiring of the drives to the pilot valve solenoids is run in conduit, as is the wiring for utility services (lighting).

Card layout: All signal inputs at the card level are buffered by a 100 K ohm resistor. The use of ground planes over large areas of the boards also insures electrically quiet circuitry.

All standards of good practice were applied during the design and con-struction of the solid state safety system to prevent any problem with EMI.

(

O t

421.24 QUESTION

(

In Sections 7.4.1.1.B and Section 7.4.1.2.B of your FSAR, you provide details of the design criteria and classification of the RCIC and the standby liquid control system (SLCS).

However, it is not clear if you have classified the RCIC as safety-related. Additionally, you indicate that you do not consider the SLCS as beingrequired to meet the safety design basis requirements of the plant safety system. In contrast, recent applications for operating licenses (e.g. , Shorham, Perry and Clinton) have classified all portions of the SLCS required for the injection of fluid, including the switch used to initiate the sy: tem, as safety-related while the heaters, indicator lights and alarms are classified as not safety-related. In these applications, all the equipment required for the RCIC system to perform its safety function of injecting water, is safety-related. Even though the RCIC is not part of the ECCS network, it is our position that the RCIC is a safety-related system similar to that of the auxiliary feedwater system in a PWR. In light of our position on this matter, discuss in detail your proposed design criteria and classification of the RCIC and SLC systems.

421.24 RESPONSE The C&I components required to perform their safety functions for both RCIC and SLCS are classified as safety-related. The

" safety-related" classification as well as the systems themselves are identical for all BWR 6 plants (See GESSAR II, table 7.1-2).

As indicated in the response to question 421.17, safety-related components are so indicated on the electrical drawings. Note the " NUCLEAR SAFETY RELATED" stamp on the front pages of RCIC and SLCS elemantaries (GESSAR II figures 7A.4-1 and 7A.4-2 respectively) . Textual statements attesting the safety-related status of RCIC and SLCS are found in Subsections 7.4.2.1.1.B.I.(d) and 7.4.2.2.B.3.(c),(e) respectively. The safety design bases for both systems are found in Subsections 7.1.2.4.1 and 7.1.2.4.2 respectively.

(

421.25 QUESTION

(.

In Section 7.7 of your FSAR, you indicate that the rod pattern control system (RPCS) is used to restrict rod worths and credit for this is taken in the design basis rod drop accident. You also indicate that the rod block monitor (RBM) is used to prevent erroneous withdrawal of control rods to prevent localized fuel damage. Discuss your rationale and basis for not designating these systems, or portions of these systems, as sa fety-rel a ted. Discuss their interfaces with safety-related portions of your design; e.g., the average power range monitor (APRM) and the refueling interlocks.

421.25 RESPONSE The Rod Pattern Control System (RPCS) has been classified as safety-related since the PSAR stage of the GESSAR standard.

(See Section 7.7 of GESSAR - 238 Safety Evaluation Report:

NUREG-0124 Supplement 1 to NUREG-75/110, September 1976; also Section 7.7 of GESSAR - 251 SER: NUREG-0151, March 1977.)

Statements attesting its essentuality are found in GESSAR II, Subsections 7.6.2.4.2.C and 7.7.1.2.B. Since the RPCS is safety-related, its textual discussions are found in Section 7.6, which is disassociated from the non-essential Rod control and Information System (RC&IS) discussion in Section 7.7.

The Rod Block Monitor (RBM) is not a part of the GESSAR II design and is not mentioned in the text. This function was associated with pre-BWR 6 designs as a subsystem within the Reactor Manual Control System.

6tt G .

II(J ,' ] I,1 421.26 In S::ction 7.2 of your FSAR, you indicats that int:rconn:ctions eu (7.1) between redundant safety divisions are allowable through isolation "' E. -

. (7.7) devices. These isolating devices are used to maintain independence

! between safety-related circuits and between safety-related and nonsafety circuits. Provide the following additional information:

a. Identify the types of isolation devices used.
b. Provide the details of the testing which has been performed, including the results, to ensure that the isolation devices provide adequate protection against EMI, microphonics, short-circuit failures, voltage faults and voltage surges.
c. Discuss the applicability of the tests performed in Item (b) above.

RESPONSE

a. Optical isolators are the principal devices used to provide physical and electrical isolation between safety-related circuits and between safety-related and non-safety circuits.
  • An isolator is an optical coupler with a high degree of electrical and physical separation. The working parts consist of a LED (light Emitting Diode) photo receiver (photoRthnsistor or photo diode) pair separated by an optical barrier that will permit light to travel from the LED to the phote receiver, but will provide the necessary physical separation to satisfy USNRC Regulatory Guide 1.75.

The LED's are mounted near the edge of an input circuit card that also containt the appropriate excitation and logic circuitry; the card is slid into one side of a specially designed double-sided printed circuit card file. The output

' circuit card containing photo receivers and appropriate output circuitry is located on the opposite side. A refractory material between the two sides contains holes filled with clear quartz rods which permit the light to pass while providing the necessary impervious physical barrier. The printed circuit card file is designed to be mounted in a control panel wall or other bulkhead between redundant divisions or between divisional and non-divisional bays or ducts to provide signal continuity while maintaining electrical and physical separation.

Several different input and output circuit boards will handle a variety of input and output signal levels and characteristics. Some can be intermixed for maximum flexibility i p a minimum number of different card types.

RUl@

k' i 5 "

421.26 RESPONS_E. (Cont'd)

TV V

(

b. Optical isolators are tested to conform to the following requirements:
1. Provide electrical isolation between the input and output sides so that any abnormal circuit condition which occurs on one side will not affect the functional capability of circuitry on the other side. Electrical isolation between the input and output is sufficient so that a voltage of 5 kV applied to the input or output will not impair the function of devices on the other side of the barrier. The applicable require-ments of USNRC Regulatory Guide 1.75 are also satisfied.
2. Provide physical isolation between the input side and the output side so that any environmental abNrmality (such as fire) that occurs on one side and affects circuit operation will be inhibited in affecting the functional capability of circuitry on the other side. The center barrier between the input and output sides of the isolator card file is designed using special materials as are required to allow light to pass with negligiblelosswhileprovidingaphysicalbarriercapableofpreventing fire or other severe environments from having easier access between control panel divisions than if there were no isolators.
3. Provide the means of coupling between the input and output sides to allow electrical stimuli on the input side to produce the desired electrical response at the output.
4. The isolators are capable of operation within specifications when exposed to the following environments:

I

a. Temperature, humidity, pressure, and radiation according to the requirements specified in FSAR 3.11.
b. Seismic vibration according to IEEE 344 and the requirements specified in FSAR 3.10 using standard plant response spectrum multi-frequency excita-tion while mounted in control panels in which used.
c. The isolators have wide application and therefore meet codes and standards as separate equipment as well as part of system control panels in which they are to be located.

1

l. Institute of Electrical and Electronics Engineers (IEEE)
a. IEEE 323- Qualifying Class lE Equipment for Nuclear .Nwer Generating Stations.

! b. IEEE 344- Seismic Qualification of Class lE Equipment for Nuclear Power Generating Stations

! c. IEEE 384- Criteria for Separation of Class lE Equipment and Circuits.

2. Nuclear Regulatory Commission (NRC) l a. USNRC Regulatory Guide 1.75 (Physical Independence of Electrical i

Systems) Rev. 1.

b. USNRC Regulatory Guide 1.89 (Qualification of Class lE Equipment for l Nuclear Power Plants) l c. USNRC Regulatory Guide 1.100 (Seismic Qualification of Electrical Equipment for Nuclear Power Plants) l

GESSAR

@SSTION h21.27

) our review of the Clinton application for an OL, we were concerned about the

( .aismic and environmental qualification of the analog trip modules (ATM) and the optical isolawrs (01). In response to that concern, the applicant stated that ,

o qualification test of these devices is underway. State whether the ATM's and the OI's proposed in your design are identical to those used in the Clinton facility. If not, discuss how they will be . qualified.

IESPONSE:

The seismic and enviromental qualifactions of the optical isolators are fully discussed in the response to Question h21.26. The A1M's A are identieel to those used in the Clinton facility.

luvd O I E

(

2 421.29 QUESTION

.- o I, In Table 7.1-2 of your FSAR, you state that .your design 'of!

the main steam positive leakage' control system (MS-PLCS) is identical to the River Bend design. The River Bend application in turn identifies this system as similar in design to the comparable system in the Hartsville facility. Since construction of the Hartsville plant has been delayed, modify Table 7.1-2 to either reference ancdher facility having the same MS-PLCS design as your proposed design or list this system as a new design.

421.29 RESPONSE Table 7.1-2 (in GESSAR II) correctly identifies Riverbend as having an identical MS-PLCS desion. This is in accordance with Subsection 7.1.1 of Regulatory Guide 1.70, Revision 3. However, the Riverbend reference to Hartsville predated tFat plant's cancellation. Riverbend is 'now committed .to revise its FSAR table in response to a similar NRC que'stion on their docket (See Riverbend questicn #421.25y. 4 .,. .

( i

~

~

,\

\

t

+

421.30 QUESTION i

, We discuss our requirements for anticipated transients without

+

scram ( ATWS) in Volume 4 of NUREG-0460. However, we note that no description of the instrumentation and controls to implement these requirements for your proposed design has been provided in

, Chapter 7 of your FSAR. Accordingly, discuss your design and its conformance with our requirements in NUREG-0460 for AiWS. Identi fy all non-safety related equipment relied upon in your design to satisfy our ATWS requirements.

421.30 RESPONSE The GESSAR II design incorporates the safety-related Recirculation Pump Trip (RPT) as required by the NRC for the BWR. Its safety design basis is stated in Subsection 7.1.2.6.6 and the system technical descriptions and analysis are found in Subsections 7.6.1.6 and 7.6.2.6 respectively.

Plant requirements for ATWS in addition to the RPT have been proposed and are currently being reviewed by the NRC. It is not clear what, if any, additional ATWS requirements will result from this review. It should be noted that the NRC has determined that the current risk from an ATWS event is acceptably small .

Therefore any additional plant modifications would only be required

(. for long-term resolution of the ATWS issue and such modifications need not satisfy the requirements for a design basis event.

Should the NRC mandate additional ATWS modifications, the GESSAR II design will be appropriately modified.

I l

8

- - - - - ~ - - - - - - - . . . - - , - ., ,,

Yb k 421.31 As a result of an event at the Brown's Ferry facility where a complete insertion of the control rods was not successful until after several attenpts were made, we required design modifications related to hydraulic coupling and level monitoring to resolve this problem. kJ indicate in Paragraph 7.2.1.1.D.2(g) of your FSAR that four nonindi-cating level sensors provide scram discharge volume high water level inputs to the RPS. We conclude from this that your proposed system for monitoring the level of the scram discharge volume lacks diversity.

Discuss what modifications are planned to meet the reconsnendations of the Office for Analysis and Evaluation of Operational Data (AE0D) presented in NUREG-0785. -

RESMNSE

}<w n 4 e & Arrd% (sAu) d Ar d m k u ds $pn+6 cou; a SD V m8D Adm (p flea foOz r/c c A s o#9H-/). Nw t

cl+yse f 6 C S SA A u k / M 7.2./.l.D 2 pu dezm s-n ZA 8Y N<

I

. . f(*~

' ;2.'o b

, j'y'8.' .

GESSAR II 236 NUCLEAR ISLAND 22A7007 Rev. 0

(

7.2.1.1.D.2.f System Description (Continued)

The arrangement of signals within the trip logic requires closing of at least one valve in two or more steamlines to cause a scram. In no case does closure of two valves in one steam-line cause a scram due to valve closure. The wiring for position-sensing channels feeding the different trip channels is separated.

, Main steamline isolation valve closure trip chan-nel operating bypasses are described in Subsection 7.2.1.1.D.4.(c).

(g) Scram Discharge Volume ,

^

lNSE6T-

~~

Four nonindicating level senso

/

provide scram I

discharge volume high water level inputs t e reactor protection system. Each sensor provides an i to one instrument -channel. ,

The sensors are arranged so no single event will prevent a reactor scram caused scram discharge volume high water level. ._

With the predetermined scram setting, a scram is initiated when sufficient capacity still remains in the tank to accommodate a scram.

Scram discharge volume water level trip channel operating bypasses are described in Subsection 7.2.1.1.D.4 (d) .

The environmental conditions for the RPS are described in Section 3.11. The piping arrangement of the scram dis-charge volume level sensors is shown in Section 4.6.

(h) Drywell Pressure Drywell pressure is monitored by four non-( indicati.ig pressure transmitters mounted on instrument racks 7.2-12

r S d- /%pe 7? 2 Fe1 mMae7 /ddX M saA6 C es m 4 c 4 p/

-A1 J~ c.sw)peJ A,oM A+nd,)$

a& A

& M M if>)Risb Ae/rm ~ Az/A

& Ef l5 ,-rz mA-A4 4:t ~

yAredcYan Y # m A T A n a +2 q ~ ,

n-4 L&An.

u a W a AadL A $zs ca L A m Aaw 8 4 Aw wOf a,=" si m ?'

d

.- A f;YY c+u y SD V2 Acv N a

GESSAR II QUESTION I 421.32 Based on our review, it appears the the proposed logic for manual initiation for several ESF systems is interlocked with permissive logic from various sensors.

In some cases, it appears that the permissive logic is dependent on the same sensors as those used for auto-matic initiation of the system. Our position on this matter is that the capability to manually initiate each safety system should be independent of the permissive logic, the sensors and the circuitry used for automatic initiation of that system. (Refer to Section 4.17 of IEEE Std. 279). Identify each safety system which is interlocked in a manner similar to that described above.

Provide proposed modifications or justification for the present design.

In this regard, manual contrcl of actuated devices at the motor control center (MCC) has been typically provided in previous designs. Our review of drawings I-960 A through M indicates that this feature has not been provided for your proposed design. Provide your rationale for not providing local control at'the MCC's.

i

RESPONSE

ESF Manual Initiation

( 421.32 I. ECCS The Emergency Core Cooling System (including the LPCS, LPCI, HPCS and ADS subsystems) as a whole meet IEEE 279 Paragraph 4.17 since each individual system has a provision for its own manual initiation. In addition no single

. failure in the manual initiation portion of the network of systems will prevent manual or automatic initiation of redundant portions of the network.

Individual Subsystem Level LPCS, LPCI (RHR), and HPCS The LPCS, LPCI and HPCS initiating logics can be activated manually by the operator. HPCS, LPCS each have a system manual initiation switch, LPCI is manually initiated by selecting loops B and C or loop A. The system operation after manual initiation is dependent on normal or auxiliary power being available at the pump bus and on normal valve and pump control lineup for " auto" operation.

Additionally the LPCS, LPCI and HPCS operation can be initiated manually by the manipulation of the in-dividual subsystem valve, pump and power systems control switches. In this mode the LPCS and LPCI injection valves cannot be opened manually unless a LOCA signal exists or until the reactor pressure is below t.

421.32 (Continued)

(.

~

the setpoint which inhibits manual operations of these valves. The HPCS flow to the vessel is inhibited in manual or automatic mode with a high vessel water level signal present.

ADS The ADS initiating logic can be activated manually by the operator. There are two manual switches per

division logic. The manual initiation action bypasses the ADS timer but is subject to interlock conditions

. which are the same as the automatic mode. The inter-lock ensures the LPCS or LPCI pump is running prior to depressurization of the reactor vessel by ADS.

Additionally, each ADS valve can be operated manually ,

without restriction from a control switch in the l

control room.

i l

l -

. - , - - . . , , - - - - - - , ~ , . . . , , - - - -- ..

421.32 (Continued)

[ II. CRVICS The CRVICS initiating logic can be activated manually by the operator. Initiation is accomplished by operating the two switches for inboard logic and the two switches for the outboard logic. There are no interlocks for manual operation.

III. MS-PLCS The MS-PLCS is remote manually actuated in the main control room. Both inboard and outboard divisions are activated to establish the necessary pressure barrier.

One switch is provided for each division (inboard and outboard). Both the inboard and outboard division systems are provided with plant air pressure and

! reactor pressure interlocks to prevent inadvertent system initiation during normal reactor power operation.

IV. Containment Spray Mode (RHR)

, The Containment Spray Mode initiating logic can be 1

activated manually by the operator. Separate manual initiation switches are provided for loops A and B.

The manual initiation is subject to interlocks which include High Drywell Pressure for both A and B sub-systems and a 90 second delay timer for the B subsystem.

These interlocks are considered necessary to protect containment integrity.

(

421.32 (Continued)

V. S1ppression Pool Cooling Mode (RHR)

[

The Suppression Pool Cooling mode of RHR is initiated only by manual action. Initiation is performed by manual switches for each valve and the two main RHR pumps. Manual initiation is governed by a 10 minute post-LOCA timer. The 10 minute timer prevents operator action which could divert LPCI flow away from the reactor core.

Containment Spray Mode also takes precedence over the Suppression Pool Cooling mode. Upon initiation of containment spray the RHR test return valve F024 and heat exchanger bypass valves will close if open or will be interlocked to prevent opening if they are

( closed.

l

421.32 ESF Manual Initiation

( ESF Systems with Manual ,

Initiation Permissives and/or Interlocks System Permissives/ Interlocks Basis Low Pressure Manual operation of Overpressuriz-Core Spray (LPCS) LPCS and LPCI Injection ing LPCS, Low Pressure Valves requires LOCA signal LPCI System Coolant Injection or reactor pressure below (LPCI) setpoint.

High Pressure Core High reactor water level Overfilling Spray (HPCS) shutdown reactor vessel Automatic LPCS or LPCI pump running Depressuriza-Depressurization tion without System (ADS) core flow Main Steam Positive Reactor pressure, Inadvertent Leakage Control Air system pressure initiation System (MS-PLCS) during reactor power operatior I. Containment Spray High drywell pressure Containment Mode (RHR) 90 second delay, loop integrity' B only Suppression Pool 10 min post LOCA timer, Operator Cooling Mode reactor vessel low level, directing LPCI (RHR) high drywell pressure flow away from reactor core f

421.33 In testing the operation of the scram pilot solenoid valve at the Grand Gulf facility, several valves were found stuck in the energized (7.2.1) position when the solenoids were de-energized. The licensee has determined that the valves were damaged when operated with insufficient voltage applied to the solenoid coils.. The basic cause of this problem was undersized cables leading from the power supply to the solenoid.

Discuss what steps are being taken, if any, in your proposed design to

(. prevent such an occurrence.

4 2 /. 23 GESSM? T V244 in 75 y== da y m w,,-a ASe sc<a m s/en04' 6<&

Ouv snaffsa asan'haks kel $4e veNye G4sf a n we a xs na , n./ n n,sp d ed' ys' Ale , 0cAnoiV c oiZr a; mncA /ny4ev A6%

a[. '/

jaywada--

recommen As' m,u/ma,,,

vie

( .

e. e-4 - - - -

w--

e b

  • 6- -%O e. e

, ( . . .

e 4 + w &

-a n 6

- - . -- - . - - - - + . - _ . , . -- . - -

/CP[

QosET706H 421.34 In Section 7.2.1.1.D.6 of your FSAR, you indicate that pilot solenoids for the scram valves "are not part of the RPS" and that the RPS inter-faces with the pilot solenoids. Discuss this interface using detailed schematics and drawings as appropriate, including a discussion of the backup scram valves, their classification and their interaction or interface with the RPS.

fES P6 M E

  • 42.l.39 7ecrWA) 7.2.l.I.b b DcG3 los sy(411;r y?fyt7 ; 8' 77hE /Natu/Dv47.

C o N r1L<>3-80 bS & W 6C W Vkt.ve-T, P/ Lor s'et &O'PS i+su b nte7a co serrx<a.s ,wte- Nd'r ?Mir o,c- rite - E PS

1~W M 7v k r'N < pe ,,ces ep. to as y aaeesas oug ,cs, p aa ug g TD Provibe on arrwuor 7tv o@wert TD nye cocmusso.r oF 'ritc'- 3' CAM 1 7 /Lo 7- V 4-L.y 65~ if72e- P M z r 0r1 riser ff.S~,

/-AM* vert, nre ne7v m o w nces ose ratr seseer pico.r vnt.as .7%wseic Ves, pa rrrers. .sste wows,- ps: xin 24127 o F- rht: sePS, Jor#4-17 tert A rz e c o n , cow o m rx o, - srsa Ccwnnua. J c'o Der u- (Cs26) Sam ,Sw /h'osemic < c Cownece

()N sT (//6 U) 0f TI/V [kb ~0'S'C1 /f*3 4 3AI6LE i %m ?>cs7 Ysts-VG~ N/?r:s'r' 4~UNT90L 5 77/c ?tr/Z suPr'4J' 7e 7?r e rav o st /zo*+ vsts-ves op- rinrr r/Ct.). ~71e- scsA-1es ,

ykz-v'E N/H. B&ccM 5&em str/t yt: .9twe. strie. po t .T//4VST r?tv ara 7D 7b'G Th' a & # m '1 ystr.yt 5 susje r1 Bo75 OF r!ff Th' d SEIL6*A'C OS OP /~'M SC24+f P/c07~ &stL &G fl/2 6~ bLL~~A'EF-6 / ?3@ ,

,5n- a rire-l

560fes 7A - 2.- l ) 7A Ie ons 7A / ssr jn7b7sriteers 6 t am) 7fM t'04O Dil a e- W esc - rs?tr

$t>S'dWD 7;Ve- Solenvoiks of ;35e s tszsi m picor vstr.vts op-rirr CAD svs7tm.

7n' - HCO'r ir,vo cournoi asos ne .meswsso -xi7o rcde St~AofM G400Ps . Isu e?>:sy scxse ss Group, 77 7 1 % crz 70 AtL 'A

  • sele;voibs on- 77tc or/Ar ts pit or s'stt.ibs /p pf,tr Sc/zw 6/20JP " G" d'A'71*u L C G~D B 9' //s'S M7 car op 779 0 SfS" L es +o e/ttu e72S', Stuf2LP , 77tL;'s sOObve7L.75 gt L- '8 " $~JLEA'd'D.s op- 77st' .5C#dM P/ Lor v'4-r.Vs5 s,u 71,vty-
Stse A r.1 tsseo u P Arze- ccisv72cLLGD BV 7 zoo siPcie scour

(

/ Oh'1D SA/We*M , k AfsTC OP Wfb~tf?U G / W p/t.s(< 6125 W U$c"D 17D C2JN YJEOL 7Wc'- Po A'W .7"O T H C* % " sdk/b v----- - - - - - - - =wv -- _,..r. _ - , _ - . , , , , , __, -_. _,.._.,y, , , , , - . , _ _ _ _ . _ _.,.-_-_,.._.____m_ _ , , _ ,y__,, _ - , . , _

2 Oc 3" (A/Q.1 b'l ksno9se cour.) .

(

"B %LWA.AiskS o p- 7b'ar scse&&T P'to r v ex. sr 65 e p- 77/g toag, sceA+1 49odPs.

& o F- 77/E FveR- LuMD D/Ls t/GMs As6eerstrarD w#7H A 25'iNCLC 3C##s't 6#d dP #FCf7s/25 s73 773rP s>6/J4E nedH A h spt=z=7ts s !r E P S 3/W tr/ o Al . Tetr ,4/729Lt>fce 4E730&

g $5 4<>&b Ditstr69ES s# !b 77)L- .52)LeAJe/As JP Grta9' st##M JVier YstL ifL"5 AW 52)&# ' TMf7- 12t /;> co^.)D/7NDS 1

pu ;T2r fMr/> Lo ds65 e/~ E17Wb'72--dP 250 o NS DswDows tv/LL CM Se~ 77/tr sp7vic P77 o sal 4F- PetuGE '7t> sitt. of W % S d 2 t'A J U ' b 5 0F 4- Se*/Ek M 6/2uuP, Ar'b 76 sp CdA./bi 770f/S //) 77Y2~ MrP H)6 /C5 dF- 677??b'7L o>= /W yson SdNkrAJ'4'S SN J/W'J/04r w/t. c CA-rJs6. 77/t'-

/N72R uP/70sU d '~ Po'UE?t 7D & op 77/E~ '5' Edi cravotDS 0F M SA*'tC- Se/Lett 6#0 0P, 77/ar/N7bnP>tcG~ Ac=7txItta) 72)zr s*O u AL S N .DJ W Ss /A.2 3 Arvb 7?fv~ scad *1 P/Lb7 .

t, vnLi/B"' d2?L6tJ0)DS OP tmG*t .st;/tds*r 6 Att>P ss 7?fus ac A- o par -o v Y- Or -TkJo - 7/WerJ -7wsCo* DeGr ssot) c~onrv Gungfr.W, Tw nrippe<>vo Si<erw- A sirews 77Ar is'mnters o r=- 7rie-Sf5 4040 DAI V Uk' 'J ' 17+ 7Ve~ 6/8L s/G5 e p.- 77tE' (S0 aySrnrrs Pftu/E- 70 ffs /4 me"A"T7/cA) 0 /=- & 'r 8/D/08-l, de o s+No BooWH,pev.o , Armwez, seerea 5 sasws ranr +mernws wrr wuL ewirr smm. .tric

&[Ab drev /MPLws<a?v759 /94.- 6 MAS E. /k4 t*tikillcri JVSc o sssoA) 0 5-774=~ /A/7&127stct-S kJsL L A s'5uMG~ CovR6u/A7s.A.)

1 ss Pert 31 eriw E, MM h d/b N hk [ Md D ~

b pf2 s s/EF3-S oA46 / Add 75 Ffah1 d?3C//- c P- M f* F e //t- SAS

\

pitiSisp s ,

EddM Nmo /, .rns c m .s6Nkts comp 2n fv~ vP- 0 F 71/6 SVrt~wLJ Logo iWrverts ,dsrSocs47sD Ar/74' 77'tr t

i

\ sS2'/2AsL4 E/ LOT L/A1. bf6 [oLt*R,.Ad s OS , $ fddR $'he-Mt C st124~

l l lDvxtr7 Cort- IN $/6Hkt. coAsinuf, MD wsNNryvFL 77/w- 6/6A/ACS

/92G" s49- 406/C l.UveZ 2t.~7t D lo), ONr c/= 77ttr ss&A41cs w/LL

/

/N 7'L'$ uP T R n!&7L TD stt L "$'CdLeWesbs /AJ Sct2AM 6fot P/]

17/Er 3CCcNb WJLL sN7t'7E. up 7~ Pow e% 70 s97 L *B " sve rn.>osos

/A) 3C/Eksst 6 00 JP 1.- j l'!/2" 7777/eb dd/LL sN 7b-?2 v f7" Jtarse=pR.it.)

B e P.$

(42.l.34 Ateigouw cbAx, )

  • 'B % esso.es # scann eaoap 3 ms s r w sounsw J

so/LL /HTm=16.UPr 70*U672- TO ALL "4"sotewstas su ge m GGeUD $. 'LM Ll' 71fF*PtJUAL M tc 4avdi as4H4z.s OStG / sus +'17N4 hioM 10 Divsrsop 2. p a r a.) in w Ad6/c u _ co>s g ut -,AuPr n ,,- ~

8Lt 'A " s> Lax.svinf ix><enner esoups 2. eso i suo ro azc

  • B #coLerx^): b5 /H sc/stes e12o o Ps 3 ,e u b tyf, ,7] tar seu e. s St6Asd'LS ON ds /W+77N6 t%2e /1 APS DiversoA) .3 / Wht"AJ /A' yflY loc /C Lat/dL -Eg7LO (0) 57pt7gr pytt, pp7t9L<>Pr 77)'t7 PCoubrl.

ro irz.t. 'A"sounus>os su scfm saoops 3n,vo 2 , ova ro pz.c "B.saLewvM su scam naoaPs %vs /. Tw M*w%

pe)04 s>6 HRLS cst 6iM4f?h>6 Potos't St'S biession </, nuncim nu 77tw to6 tc LevEx. testo &) snwa=, A>rLL ssu7t9t uPT* Pd Wmt-7z> stz. t.

  • h " S3 L arm os DS sp SCP/tts 6AloJPS f'efsu b 3,ews p ,yst ",8 " fstaduob5 s4 SCAT *1 69<>U PS / Au b 2.,

bk)17 tr1hYr 72m ;nGrP S #6w<x S 70 77ter w pg:aggS coWTPvLt H4 7W~ 70*' *nt- 77' 7?/tr .52Ater P/ Lor W'tz v5-wzy ; tis 1/bS D:> /J e 7' W C T 1 2cW/Ld5W TP/PS d** sNDIVlU'iE-RP5 Div's'oP we '"6/C s . Yn Frivse ms omsm ypg4 y f)P.5 absusf/e N / A)/4 L ct+>tsd4 G' Prec H A- Lo 6 sc f,, cry'gz, CDbk/h, uAJ7P/PM M' Y2) 4 /-46sc L ib't*L &%D ,

72.-rpfGD ~W /F- /W D/ V/St)A / ffb P 2-o / 6'/c st'?hs" At'a=?u 7N t/fGD , 0 P- /P &>7H 17/E b/vst/oA) 2. ,9,< is Di ysssoio 3 j~r/t tf L o 6 / C.S &~f26 DMJL 7?tN6TJUSL}# jus.) st ne/ffgo ~G,vbj7tsg.)J Cf - /F BOThe 77tc~~ b/Vsf/d A) 7- eph LV v /ss6 a pt 772-/p ic.o g/c3 st12w S/ HOLT)tN6i)vs L.y /AJ A 7 M-is'P e-a co 's a /77.us , 7k" ff/Jk7.- 772 iP S/64)st LS Fie-c s'f ;77/c=' 77f/2CE7 C)7?ytst.'L A8 DIV*$0AJS Af26'~ Grs't/L sf17-LY COMP /6of k'O fu r'/l't t='

ps ff'L-1LC'?L'T WR- c=??c# N S~ D/Vs5su/). .7s'j'r fcs.*.e S/Sivsr:s f'f2s As f& D/V'ficP 2 &U/LL C/ft)**'A G" 77) ??fc= dodsc 1. e,ixttil 2-c"M.O {0) S7)trE /F L>s V/Stu A) 2. sit.oH'S sfits- ac2P') 7?t/PA b, y f /P Of V/S/0NS b es"b '/ /Mfk~ Ror?V /$Eli3) Der//t~'D, d!C

/P DIr V/ Pox's 3enio / sist1va- skar/ de ents ireiPtsz). life' FovP -

.3s frAlstT.S FYid M S?S b/ Lf aStCAJ 3 s/ <-L C d'fW6 6~ 70 7'%*'

LD6!C LGt/c=2 W {0) S7)fTai / F- b I V J S/ # A-} S tit UL'C If5

- Ge s 60 TW PPs D , o /2 /F DIV/S<dDS ft,q,vp / mgyu- Bc;7W RewA)

fdps

(,tl11.3t/ Aesm's-9"d

(

%PPWb , el IP b sueG s 09 Sl h entb 2 fttva Bow 66n) TRIPP6D.

TM R)UA- S/6//ALS PY4 H & D)vsSrs4 Y MLL C//hv6 G Tz 7?>5" to6/C 4.WVW2 St"M.O(0) _STR76 /F bs y/Csosu 4' s+s.c ate

//g$ /36*W 792///6D , e f- / C bt V/CsoA'S /sovvo 2. /Mvs-gu 7N /Jg-1N 772/P !t'O, 'E- l'= O/V/S*t o/US / prevb S / Art /G

&JTh'- dt=VA ' 7FL/ pfg,Q f)HY' UN/ 90E J'6 /dstT. con 7anV7" $P 7771r P/A JJr., 774P J-d 6 /C- Ss GA'stC-S fft-d A'T iPkA! $$ b/V/sso/ J C&ttesAse-D s o a;r W 7WG FrAJAt- 0//5'--od7~-r>/=--tze 0 - JFtz'eru/-7xJacs-C64/M 6uPkf3dN /A/72fA-/9t~C6 0 P /~~?tar ft9t//!'- J/ t////d"s id777f- efkc# OF- 77/57 FOL// -tS %d M 6 Rut /P.S~ Ac*!TUZZ3 j,) s4- b V5/ 6A) N#entaBP As Vs Sc/zAM P/cc7" Vitz Vc 5 dp ~

/tZ.4- EE"% 6AQUPS 60'L L Af A<TE/ A'fEs'D /F A9VY 750 g) D F 77f27* /%)U/2. $$ b/V/S/ c A) dd 6/C,5 443.G" re,piro . A>o ses c ,+-m ae-soc.7s is:- one.>- s- s ws ce-f5 Lod /l'- #4 7M/fi'E'D . $ sitTOt.a77A/6 Co/t6 talk 77pA) t

y/p<.-a</c seneew > mr .w oiviorse se es sivis sa, lF' tP3 t&;*' b ~

v'IYW~/SCYZ'NTIPAA Of" IN 6'dAA~l ?'#O 7" sfA1 vr5 ccro L b desr~ s95 Pe5cAnsev ns 0AJE'- o ur-poC -73J 0 7)d/ C E C OM 8/AA67D 54/ /77,t P)fR77kf 7sud - 0t/7-OF f*OUf.- 7N/ C 6' Cc,h8/A/sf?7cA) Z,dG /C . J'Aff"d) &&s'6AJ

/12. 4 d406 /W FUA/d770A/AE- .72;;n5~77AAG, C /-- 7 ?y s - /*7 A /A E-Ac 7vA:rvb &2.-crns nv73 ,M/2/s/4 /t'stxir est-vz-grrdAJ VJt7hto v7 s'u8nFt7?AJ6 7?fs ftd>vr 70 & PA) saktt.!ED S c fL Ar'1 iTN b J'67 / hts of /@ro /3%Ls77- of 312422WSPs'L Scfst+ t 7Wr 15 l$'re e")P7L%. 77/sta.) e777/t.st. ,e o p e ' - # v 7~-

c)F -Tk!0 - 730!C e~ D C=S'6/t) ost. A- 7to o- ou1 - of - /=ciuA-DE5/6 A' a T/h=~ /N7t"tFrtce of 7ec= Ei f3 ous77'- rec- A*xo P SCAk?'f V#2.4/25 /6 /9f 60 C/rveJAf d AJ SA:'c'/C// (3 a ~/Ivo DC LoAb bM V6xs c)f .nyt M WG/ c/s'c-b TD fro v/A.-

f%)>ot0t-- '70 77te:mLaR./d/bs o/=- 7s'S 730d dett'uP sc/2ifft

\

v'42. Vbs /N int =" t=~1c'A /I~"~ c)'= s+- FL/LL se e9h:~roit SW, fryg-sste-)vooO n

s /P dde'daP sctzs+y yi*t. ve- C// ,C /jfjjf su/g e, se ewern-siwo e s w w w 7si,, e ,s7s -a, ,ers

  • s'n-J'-

Q{2l.34 e<spopst cossr.)

(

y, yissor.> ; on bevison 2. p,vo Ar ras- sew DS gtp 9 7 7)y c-)C of'- Th4F 1hid A4ckup ~52'/ZA*f Vft ut5 y js c fig)cg' 7b*G" //S7&o/*GA/7 s97/2 SJ//'l t' 7D 70' C q;'c/tA-p.7 s+r/L //bJVD W /t/O N M~ WS 77M =~ &X/ 6 fat /ST 7// Z A -7 /E- sN T?tt=T~ Sk'/E-#'*7 A~lfl /t'tr M & /E. /1Y k'Ab bf Wh~bts' i4124r* Psfr*7' ssc fr/c=~ N $ AJ'9'6?*C M 77227 asi<ap s w z n r a z.v y s se rv o 7>ien /t sotea.isas /*re s cas M J@ N W N 15 dP 7W9- W 59'S m ,

Tor acx'up scun vez ea s no wr,e_ avieais,os m CLAs5'/ Pre'b ets Ald7~ sMi@'#TR3!!~ po .Sm Ag /j o C/29b/7 /S 7?YM&W /N AF/V Sofr=c'7V ogst fzysss i piest.177g

, C H:f'of770 D OF 77'tr B/)t'.'KstP S'atA*1 f & t V 2 5 , T/s b 7se ; ,v tJ*

Fsipcr70/> /s ro 62//ofs'C7 77/?rA72- scAs nVt; ScseM s+rst

/fi?rMP&12- f.7FM- A- AfhWK ScALHf Guly 7?fn-Q/tc' drely '

mp6LE scR,+tt P/ccr stz W ,mes ,9 7L.en 70 oh-n/rer 4-

./ pr SWo t)L P DP/M7?/c- De=a-NER6s7st7to AJ oF ii5

?wo cuiLealdips, 77/Er Arte SUP!steo .7p ~<t f 'pv o s cic h wr ystz vbr5 po,gygo ,

p>1Til r?/MT* o*> lot Vitt VE tu/Li S771L ef'n't>?v&t.t y /3 G' E X /t)+t/ 6 7 2 0 /9A'b Iht** #4f S& Cs A-7'br't) f.e 47f36 & Sei 13 oun r 9G /4SM 7D 7?/5 f2e=?!cro/2- cose e~. 71jt72.e ,.c sus

$4ft?7'r ccipSFSubHCG ASSocrifft.-D IJ174--777c- s e,.+7Lupp dF- A- S/N64 G" 60s 74b/2A*J'V CON 7&ol Ao b ro is.)SG7L7~ V/A

%~'\:'f.-J+Ft LU 6 /C . T/rbULb 77tt~ SCC'ft'1 R Le 7"V)f1 V5' f777L.

7L) oP&72.M 79suD 2 071/ 6/1CMuP St'/2stff Vif7 V65 /9d fo Ftt1L 7C) CP&7tst7E~ / 17& Cos/7Ro& Rob c A s / s' 7 7 L /J G 4

,61 Aftll.Js$7 L-Y / jus 5M 10V'//[ CY&$ /ffC'st. V /tY- /7/ G A/0/Z H#t- CA D SYSte^M Cbbrn:uLs.

Af19Ctf&~b : 1,t2.j, 3 y ske=7c%

et 2.1. 3 4 S*c7ut 8

.{,  :.

ya w

le >d v m.

+ g e m N -

t el-$dl cgu li'y d i

  • Il i,Y ki-1 g. h I'

g g ilNt f-g g-. g h .:.l l g _g <9 y g -

) g e

+ --(-H e . , r

., . . , .. . .4 .

i

- r '

t i

.j

, 3' < r

'Y

' ' '~~

N,. ' -

g ,

!EWA.'ld,i I  ;' t .u c 3 N. !

4 - -

jf 4 ' '

{>

[k ,

-[.lkt bi

.Q , ~

w r >

4 ., '

M

<q.k h, i g '+ g .o c4 g*U tt* ! t 7: 84 $I. M +

6:

21

.pc. .

g; +, , , .

., sy  :

t . .

g -

. _ .- v 3 s s

- \  ;

h.

} j 'I J '

14 el

.w

- , + = N.

+ d Dr

  • d t $% ag- b 4-f.3 .  :' g, e.g pg ,,

4 L u. J e o 4 [ ' f # l_X R8

$4 y .d d w . o.

<. 3 ,

s e, =s oa'.

g3 E% i g% E %

M**I ,

m ,

6, 2

-u ,,

t .

6

< ~ ,

c- .

.E -

7 +

x-1,;

/\

t a

'3d(Jh,'

l4 h.kdj , .

4}is" (-$ ,.

-i.f') n ?,. -( .5- .

l L '_~ _

^

13 30 --

Y9 4 - -

ve -

xs --

re -

xs , -

12 - -

re -

Y- T v Y2 E 7 E gx^l - ,{iT W . T'

, T T I 'jg .

                                                                                                                   !n v!T'                       i                      T                            .j                                                        T. }*-;-
                ,                       y                               q           N                                             ,               s                      M                    M                                           93 T                    T
                                                                                                                                                                                                                                          .:/v4A
                                                                                                                                                                                                                                                             '2 ::9c e.--==-e       - = w = - .e-
                  -w           ,      --           - , - -                                      -                 - - , . - ,             -                                                                                                                                     -

w y w e se e m,.>.

                     ,,.. .    ?,,,                      'y                                                                                            -,                                                                                                                     i
                     &      (Y                            f-...      ] -"                                     E              L      .~9e ]                                                                                                                                    l J-.

k g- m A n , 4 li I g-

                                                                                                                                                                                                                                ? m
                              ---                       -4           -C-                                      .g_                                      -                                                                                                                   at 9                                                       . =- < @$                        .hb
 .V.4 ,'i                          -                    iY 2                            3,                   .T. . Q ...                                 ~         _t .          - e N                                      ?                        -

y3 d e 6 35 f 34 {1 [~ 1. {,'  ! #I E 1- 8t; b n* u e.

      -I                                                                                               . x                                              .b                          .E R -.t:                A               2 E2 3 c l3 3
                                                                                                                               @-               ~

43 - 8 -M-eS -

            -i!J                                                                                                                                                                                                                                                       51 WS        --

XS -

                                                                                                             .ys     -                               -  t*    -

t ig - {" }*

                                                                                                                                                                                                                                                         . 7h l
            ~
                                                                                   '    -.             t                                                                                                                                  \W.$$
                                                        ;.y ~ -5i                                                      . . _ .
                                                                                                                                                       'y/ -l                                  ..- .
                                                                                                                                                                                                                                  '[                          b[k
                                                                                                                                                       ; ....      .o   g                      .- .                              -.

j it,sj,k  ! - d 5

                                               <- gf Pe"_it.yl,Iki,h.
                                                                                                -( -
                                                                                                                                                    $1ih[                        (-5E p

30 u did$ k<- .-

                                                                                                                                                                    }e                                                          idb(h .DQj
                                                                                                                               .fl!.

Q*S

                                         "              D
                                                                    .                 -4
                                                                                        ?-
                                                                                                     ~
                                                                                                                                . _.M b
                                                                                                                                                                      +

107 .k

         .O 5 ,                                                               . .I . %                    (5g - :-

g.

                                                                                                                                                                                                                                    ..ts                 '

M

                                                                 . g, .4                                       . .
g. 5; 80 '

(.; g

                                                                                                                                                                                                                   ~

h .s9 . . . b ' ., , fV U m i -

                                                                                                                                                                    ,               m.           ,-

1

                                                                                                                                            ~~
                                                                                                                                                                                                                                                    'i - ;.          ,

4 ,% 2 a e '+ . +- Et Oc

                                                                 $                                                                                                                                                                               g) g k                 i P)                             I                                            g% ? tL } '         .

a It' :

                                                                                       ~                                                        s w

4 7',1f.T _Y - Y0yaR $. S Y ., 1$ p 'R

                                                                                                                                                <    E., R cc,            4                ,

g < t.o-e - 7 g-

                                         #2Re                                                                                              E% Ew       og                                                                                    *2'
                                                                                                                                                                                                                                             =

s u hr. b O

                                                        !, g                          . . .

4 -

                                                                                                                                                           ,ge4         ,.                                                                             ,s
                                                                                        + +                                                                               ++

A a l5i (4 2 Jf H" .f 4 . JdG#I . g 1- . . u C - C -- d 4* ve 4 WS - C - - d - 0 -p

                                                                                                                                                                                                            '( _-

go < ga4 L T " Ji .a f rt T .il ui 1, f E2 Y

                                                                                                                                                          't          -

4.7 8 as .

                                    +
                                                             *       . ,5                                           ?

o c 1-

                                                                                                                                                           .s.

kk no o- h T - + 4 2 e

                                                                                                                                                           ,5 4

6

                                                                                                                                                                        ,e

FJCWEL j L . fi ' 421.35 In Figure 5.1-3C of your FSAR. you indicate that the RPV pressure and

      '7.7)                                                                                '

N ( water level instruments use the same instrument lines. Identify all other instances where instrument sensors or transmitters supplying infonnation to more than one protection channel, are located in a common

                                               ~

instrument line or connected to a common instrument tap. Verify that a single failure in a common instrument line or tap (such as a break or a blockage) cannot defeat the required protection system redundancy. Identify where instrument sensors or transmitters supplying information to both a protection channel and one or more control channels are located in a comon instrument line or connected to a common instrument tap. Verify that a single failure in a comon instrument line or tap cannot cause an initiating event and also defeat protection channels or functions. Provide a list of the shared equipment identified in response to these questions. Include the turbine stop valve / control valves as well as the ( RPV instrumentation in your analysis.

RESPONSE

The figure cited (5.1-3C) shows a part of the nuclear boiler system and its safety related level and pressure instrumentation and illustrates , schematically the grouping of instruments on the four sets of instrument taps at the four different azumuths. The vessel level and pressure instruments of each single division are connected to the same tap. This is consistent with the single failure criterion which assumes failure of an entire division of equipment as a Single Failure. There are instances where a single instrument line or tap serves l instruments in more than one division of the protection system. These cases are: 1

1. Main Steam Line high flow sensor for isolation of large main steam line breaks outside containment.

l

i

2. Reactor Recirculation flow sensors for flow reference scram inputs. I k
3. RPV level sensors for RPS division 4 and HPCS division 3 level inputs.
4. The Main Turbine First Stage pressure taps providing power level information to the RPS to pemit scram on turbine trip above a specific power level.

Each of these four cases has been analyzed for single line break or blockage consequences and found to be acceptable as follows:

1. The main steam flow sensing element has two sets of A P taps which run in divergent directions to two local instrument racks -

located outside the drywell on opposite sides the containment outside the steam '.unnel. Each local rack has two steam flow transmitters, which are assigned to different electrical divisions located on different separated sections of the same rack. Postulated instrument ( line failure could cause two high flow signals to be disabid. Such a failure could not be the result of a main steam line break outside the containment because of the location of the instrument racks. Therefore, the failure can be considered a random failure. The remaining two channels of flow information emanating from the second instrument rack provides the signals to the 2/4 logic which will initiate isolation as required by a large main steam line break. These main steam flow taps serve no control functions.

2. The Reactor Recirculation Line flow element is an elbow tap which has two sets of instrument lines which run in divergent directions to local instrument racks outside the drywell and in different quadrants of the containment. Each set of instrument lines serve twoAP transmitters which are assigned to different electrical divisions and so are located on separate sections of the sub divided local instrument rack. A postulated instrument line f ailure could affect two of the four channels of flow information to the flow reference scram circuit but the remaining two operative channels would

l provide the necessary 2/4 inputs to obtain a scram on the 2/4 logic IF ( low recirc flow were to occur. Instrument line damage in the vicinity of the elbow taps as a result of a LOCA induced pipe whip or jet could not result from a leak so small that it could not quickly raise the drywell pressure to the scram set point. Therefore, failure of these lines as consequences of a LOCA is not a safety concern. These recirculation flow taps serve a rod block function but do not cause any active control action that would initiate a transient.

3. The division 4 RPV level sensors includes level transmitters for the HPCS system which is a Division 3 system. Therefore these transmitters have 24 VDC circuits from division f coming into a Division 4 (441MF 7 p55 popstoA 3 oses Avr n

_i " at^ circuits are required to be repmt-d from the Division 4 c j g y 9 i E t $n 49 t>* s (N T14 C DInstw y CA psy.g 3 I circuits by 4cpr;te enc':=::gand routed in a Division 3 raceway, or Cond ann + :f t% * %no aspa & ain hu- um ca u w we Aid 2%4=$A% %%ir-ebke*44ti+4%p-~C;Ta4Mt % 4 k :i%id W ' N II,a os c m 6 h i i un 7. 7;;c ;f ;^., P eu >2nnnt_E05e a threat to cA4wf7 fo ti,e Division 3 e4+ee ts. It is also noted that the HPCS has a separate set of sensors located ca the other side of the vessel / l containment. The division 4 RPV level taps do not serve any control l l function.

4. The main turbine first stage pressure connections are not always separable into four separate taps because of physical constraints.

Where only two taps are available each tap serves two sensors one in each of two divisions. The breaking of an instrument \ ' line can thus disable two sensors. However in the 2/4 logic the S E Y:' e 5 ! two remaining operable (+ps would give the required two inputs to permit the turbine stop-valve-closure scram on pressure above their set point.

The first stage pressure taps provide input to transmitters used in the rod block circuits. Each tap serves one of the rod clock circuits so failure of a tap could disable one of two rod block circuits leaving the other active. This failure would not initiate any transient that could cause a need for the first stage pressure safety signals.

5. The Turbine Control Valve fast closure signals are taken from four separate taps. The only other instrument taps that serve both safety and control functions are the RPV level taps on divisions 1 and 2. The transient analysis covering a failure of one of these taps as an initiating event is covered in detail elsewhere but in summary a single failure that could initiate a RPV level transient that exceeded normal operating limits would cause either a high or

[ low level scram which would not be disabled by an additional single failure. 3'QLa y- 15 -rc & L I ( l l

421.36 Provide an evaluation of the effects of high temperatures on the (7.1) ( (7.7) reference legs of the water level measuring instruments resulting from exposure to high-energy line breaks.

RESPONSE

Exposure of the RPV level reference columns to the high ambient temperature associated with a High Energy line break will heat the column at a rate corresponding to a thermal time constant of approximately 10 minutes. Therefore, the water in the reference column will approach the temperature of the drywell environment in about 30 minutes. This temperature will depend upon the nature of the break. A large break will give a relatively low temperature (approx. 280*F) whereas a Small break will superheat the drywell to approximately 340*F. This is the condition which is of k greatest concern because in the small break case, it is expected that the vessel will be depressurized after a short time and vessel water temperature will then be lower than the reference column water so that the reference column will boil. The boiling will be rapid if the vessel depressurization is rapid and it has been determined that approximately 20% of the reference column exposed to the high drywell temperature could flash quickly. This is based on a vertical column and will be less for a sloping reference line such as exists in the drywell because the volume of i wate per unit of vertical drop will depend on the slope which will typically be i inch per foot compared with 12 inches per foot l for a vertical pipe. After the initial rapid flashing there would be a gradual boiling over a period of hours if the drywell ambient was maintained above the vessel temperature. Thus the reference column could be gradually depleted. The effect of this

depletion will be limited by the vertical height differential between the reference level and the instrument line penetratier. ( through the drywell wall. This distance is limited by design reconnendation to 4 feet so as to limit the boil off potential error to not more than that equivalent to four feet of reference column. The error would be in the direction to make the indicated level higher than the actual level. This error will not exist prior to the depressurization of the vessel because there will be no boiloff and the reference and variable legs will heat up at very nearly the same rate and thus compensate each other. It has been determined that an error of the magnitude cited will not result in incorrect operator action or unsafe reactor conditions during recovery from LOCA. I 1 l l l l l l l s

I I I 421.37 QUESTION ( V'trify that there is sufficient redundancy in the water level ' instrumentation to prevent a sensing line failure (i.e., break, blockage or leak), concurrent with a random single electrical failure, defeating an automatic reactor protection or an ESF actuation. 421.37 RESPONSE A complete analysis of this event scenerio was performed and submitted to J.E. Knight (NRC-ICSB) for the Grand Gulf docket. This was in response to Grand Gulf Question "J" (LRG II Item 1-ICSB), " Failure in Vessel Level Sensing Lines Common to Control and Protective Systems." In July,1982, Rick Kendall and Jerry Mauck (NRC-ICSB) did an independent matrix study of systems / divisional failure combi-nationsand confirmed GE's identification of the worst-case scenerio. Furthermore, they indicated they were satisfied with GE's analysis of BWR 6 plants, and of the results which assured adequate core coverage throughout the postulated event. GE made a comparison study of the Grand Gulf analysis relative to solid-state (GESSAR II & Cliatoa) designs, and assured

    ,            the results were conservative. This is because RPS scram logic is any 2-out-of-4 for sc, lid-state plants compared with 1-out-of-2 twice for Grand Gulf. Tne results of this comparison study is described as follows:

In BWR/6 solid-state plants, the RPS logic is any 2-out-of-4 channels to scram. Therefore, if one RPS channel reads errone-ously high due to the instrument line failure and any additional RPS channel is assumed to fail-short, there are still 2 remain-ing channels lef t to accomplish norma' scram. Assuring an instrument line break in Division 1 (worst-case in the Grand Gulf analysis), it is possible to fail either RCIC o_r HPCS by postulating the additional failure in ECCS busses 2 or 3 respectively. However, both systems cannot fail due to a single electrical failure and there will always be a normal Level 3 scram prior to automatic initiation of either (or both) high-pressure system. The worst-case scenerio is postulated to be the reference line break coupled with HPCS failure. Normally, the operator would switch feedwater control from the bad instrument line to the good one as soon as the level mis-match is detected by the annunciator alarm. This would immediately restore normal water level. Should he neglect to do this, the water level would continue to drop until it reaches Level 2. This level would normally initiate both HPCS and RCIC and trip the recirc pumps.

   '            Assuming the additional electric failure of HPCS, only RCIC will start.      Since a successful scram occurred at Level 3, RCIC is sufficient to cause water level to turn around between Level 2 and Level 1 and rise; slowly filling the vessel as power decays. If still unattended, the vessel level will gradually increase until it reaches Level 8 which trips the RCIC turbine and assures closure

421.37 RESPONSE - continued ( of the main turbine stop valves. Thus, level will drop back toward Level 2 and the cycle will continue to repeat itself even slower due to residual heat decay occuring in the vessel. This will limit vessel level between Level 2 and Level 8 indefinitely until the operator takes the remaining shutdown action. The postulated scenerio therefore has no adverse safety consequences for BWR/6 solid-state plants. 6

421.39 In Section 7.3.1.1.2.K of ytur FSAR, you indicated that thm (7.3.1) containment and reactor vessel isolatior control system (CRVICS) ( is capable of operation during any unfavorable ambient conditions anticipated during normal operation. Discuss the capability of the CRVICS to function during abnonnal and accident conditions

               ,such high-energy line breaks.

RESPONSE

The CRVICS is made up of two separate divisions of equipment controlling two sets of valves; one set outside the containment and the other set on the inside of the containment with certain lines having their inboard valves within the drywell. All of the CRVICS valves close on low reactor vessel level and all except the PSIVs and those valves associated therewith (MS drain valves and Reactor Water sample) close on Drywell High Pressure. Isolation valves within the drywell are required to withstand the temperature and pressure and radiat'on conditions of all normal, abnormal and LOCA with a time limit on the duration of the LOCA environment because of their short function time for closurc on a LOCA signal. Since all the valves that close on drywell hign perssure start to close when the drywell pressure exceeds two psig they do not have time to reach LOCA ambient steady state conditions before they are l closed and their isolation mission is completed. Consideration of localized damage to equipment as a result of a LOCA focuses attention on the inboh isolation valves and their ability to withstand jet forces and missiles associated with a LOCA. l While it is true that an inboard valve may be affected by such forces, it is beyond the design basis to impose a LOCA pipe break and

more than one single failure beyond those which can be postulated as consequential. With this groundrule it is evident that the inboard l

i  ; 421.39 isolation valve failure as a result of consequential damages would (7.3.1) 1 ( (cont'd) not open a release path for radioactivity if the line involved were part of a closed system and had another isolation valve on the l outside of the containment. The following considers postulated damage to various inboard isolation valves and cites mechanisms of potential failures together with the isolation condition resulting. ' MSIVS Normally Open- Fail Closed Electrical or air service interruption may be impaired by LOCA. The valves are calable of closure on loss of air or electric power or both. Additionalh a third manually operated Motor Operated valve is provided. , MAIN STEAM DRAIN VALVES - Motor Operated Valves. These valves are normally closed buring power operation but opei. ( during low power operation. Therefore, failures (electrical cable damage or mechanical damage to the operator) could open a release path to the main condenser if the outboard drain valve failure was - the SAF. Because of this possibility, the MS'd, rain valves inside the drywell are located in a pg)tected area within the guard piped area of the main steam lines and considered to be out of t.hd LOCA' consequential damage zone. The AE and constructor are responsible ' for the design and installation adequacy with re' gard to explicit . protection methods. (CF Braun is to verify the foregoing statement). SHUTDOWN COOLING Suction Velves, Normally Closed MOV's. Since the inboard valve is nonnally closed and no electrical failure as a consequence of a LOCA can conmand the valve to open there is , no release path established through this valve. i I f

421.39 Reactor Water Cleanup Inboard Isolation Valve - Motor Operated. Fail-as-Is.

       '7 .3. 1)

( :ont'd) Damage mechanisms include cable damage or mechanical damage to the operator rendering the valve incapable of closure. In view of the fact that the portion of the RWCU system outside containment is closed system and also protected by a second isolation valve; no radiation release path will result from inboard valve failure and a single active failure. (or single passive failure provided the outboard valve operates.) OTHER Inboard Containment Isolation Valves. moi ~or Operated, Normally Open. Closed cooling water, chilled water and air systems are examples of systems that could communicate with the drywell atmsophere in the event of a LOCA and consequential breakage of one of these pipes. 1 The damage could also be postulated to damage the inboard valve but

                                                                                 . w in each case the outboard valve and the closed system piping outside        -

5 the containment would accommodate a single active failure or single passive failure without opening a release path to the environs. i e O

421.40 QUESTION ( Provide a discussion on high pressure / low pressure interfaces and the associated interlocks in Section 7.6 of your FSAR. Discuss how each of the high pressure / low pressure interfaces in your design conforms to our positions in Branch Technical Position ICSB 3. Discuss how the associated interlock circuitry conforms to the requirements of IEEE Std. 279. Your discussion should include illustrations from applicable drawings; e.g., the reactor heat removal (RHR) system. 421.40 RESPONSE The High Pressure / Low Pressure (HP/LP) System Interlocks are described in GESSAR II, Section 7.6.1.5. The table under subsection C lists each of the isolation valves and their interlocked process line, etc. As indicated in Subsection D, all lines have at least two series valves except the steam condensing mode line. These valves can be identified on the Process and Instrumentation Diagrams (P&ID's) for each system. For example, see Figure 6.3-7 for LPCS and Figure 5.4-12 for RHR. Interlocks prevent each valve from being opened until the primary system pressure is below the subsystem design pressure.

 ,        In most cases, they also provide signals to automatically I        reclose the valves when primary pressure exceeds the subsystem design pressure. Exceptions are the emergency injection valves used for ECCS which must open reliably and rapidly upon receipt of an accident signal. HP/LP interlocks are controlled by transmitters which sense vessel pressure directly from the instrument lines. These transmitters are connected to trip units arranged in complimentary logic channels to prevent inadvertant operation of the valves should single failures occur.

For example, the 1-out-of-2-twice logic to open LPCS injection l valve F005 is shown on the LPCS Functional Control Diagram, 1 Figure 7.3-2 of GESSAR II. With the allowable exception for ECCS valves (i .e. , they do not automatically reclose), the HP/LP interlocks described in GESSAR II meet the positions outlined in BTP ICSB-3. Also, the instrumentation and controls for the HP/LP interlocks are qualified as class IE equipment. They are designed in accordance with the single failure criterion, redundancy requirements and testability criterion of IEEE 279. 1 I l t 1 [ l t I

421.41 QUESTION ( In your discussion of the high pressure core spray (HPCS) system in Section 7.3.1.1.1.1.C of your FSAR, you state that the HPCS system provides water to the reactor as long as a high drywell pressure signal is present, regardless of the water level in the vessel. The control logic has been modified in the HPCS designs of other BWR's (e.g., Grand Gulf and Clinton) to stop the HPCS when the water level reaches the high level trip. This modification was implemented to prevent possible flooding of the steam lines and subsequent damage to safety / relief valves and the primary system piping. Discuss your proposed HPCS control and its " termination" logic. 421.41 RESPONSE The GESSAR II design is to be modified just like the other BWR's mentioned. Engineering Change Authorization (ECA) number 801203-1 is already in place to facilitate the change in the GESSAR II documenta tion. Attached is a mark-up showing how the text will be modified to delete the high drywell signal which inhibits the level 8 trip of HPCS. The HPCS Elementary and FCD will also be revised in accordance with this change. (

GESSAR II 22A7007 238 NUCLEAR ISLAND Rev. 0 7.3.1.1.1.1.C High Pressure Core Spray System Instrumentation ( and Controls (Continued) transmitter provides an input to an analog trip module (ATM). The output trip signals from the analog trip modules feed into one- ' out-of-two twice logic. The initiation logic for HPCS sensors is shown in Figure 7.3-1. Drywell pressure is monitored by four pressure transmitters (two in Division 3 and two in~ Division 4). Instru-ment sensing lines that terminate outside the drywell allow the transmitter to communicate with the drywell interior. Each dry-well high-pressure trip channel provides an input into the trip logic shown in Figure 7.3-1. The trip logic inputs are electri-cally connected to a one-out-of-two twice circuit. The HPCS system is initiated on receipt of a reac-tor vessel low water level signal or drywell high-pressure signal I from the trip logic. The HPCS system reaches its design flow rate within 27 seconds of receipt of initiation signal. Makeup water is discharged to the reactor vessel until the reactor high water level is reached. The HPCS then automatically stops flow by closing the injection valve if the high water level signal is available,and dryucil preccure is below thc trip sctting O-The system is arranged to allow automatic or manual operation. The HPCS initiation signal also initiates the HPCS Division 3 diesel generator. i Two ac motor operated valves are provided in the HPCS pump suction. One valve lines up pump suction from the condensate storage tank, the other from the suppression pool. The control arrangement is shown in Figure 7.3-1. Reactor grade water in the condensate storage tank is the preferred source. On receipt of an HPCS initiation signal, the condensate storage tank suction valve is automatically signaled to open (it is normally in the , open position) unless the pump suction from the suppression pool 7.3-4

GESSAR II 22A7007 238 NUCLEAR ISLAND Rev. 0 7.3.1.1.1.1.C High Pressure Core Spray System Instrumentation and Controls (Continued) 4; The valves in the test line to the condensate storage tank are interlocked closed, if the suppression pool suction valve is not fully closed, to maintain the quantity of water in the suppres-sion pool.

4. Redundancy and Diversity The HPCS is actuated by reactor vessel low water level or drywell high pressure. Both of these conditions may ,

result from a design basis loss-of-coolant accident. The HPCS system logic requires two independent reactor vessel water level measurements to concurrently indicate the high water level condition. When the high water level con-dition is reached following HPCS operation j and-Jzyucil prcccurc A y ic belcw the trip cettir.9, these two signals are used to stop HPCS flow to the reactor vessel by closing the injection valve until such time as the low water level initiation setpoint again is reached. Should this latter condition recur, HPCS will be ini-tiated to restore water level within the reactor.

5. Actuated Devices All motor-operated valves in the HPCS system are equipped with remote-manual functional test feature. The entire system can be manually operated from the main control room.

Motor-operator valves are provided with limit switches to turn off the motor when the full open or closed positions are reached. Torque switches also control valve motor forces while the valves are seating. The HPCS valves must be opened sufficiently to pro-

   -vide design flow rate within 27 seconds from receipt of th2 initia-      f tion signal.

7.3-6

GESSAR II 22A7007 238 NUCLEAR ISLAND Rev. 0 7.3.1.1.1.1.C High Pressure Core Spray System Instrumentation l and Controls (Continued) The HPCS pump discharge line is provided with an ac motor operated injection valve. The control scheme for this valve is shown in Figure 7.3-1. The valve opens on receipt of the HPCS initiation signal. The pump injection valve closes automatically on receipt of a reactor high water level signal. aedr t-uhon_ drywall- prcssure is below the trip m e t t-i n e

6. Separation Separation within the Emergency Core Cooling System is in accordance with criteria given in Subsection 8.3.1.4.2. It is such that no single design basis event can prevent core cooling when required. Control and electrically driven equipment wiring is segregated into three separate electrical divisions, designa-( ()

t ted 1, 2, and 3 (Figure 8.3-1). HPCS is a Division 3 system augmented by redunda t Division 4 instrument channels (Figure 8.3-1). In order to main-tain the required separation, HPCS control logic, cabling, manual controls and instrumentation are counted so that divisional sepa-ration is maintained. System separation is as shown in Table 8.3-1. I

7. Testability i The high pressure core spray instrumentation and control system is capable of being tested during normal unit oper-ation to verify the operability of each system component. Testing of the initiation transmitters which are located outside the dry-I well is accomplished by valving out each transmitter, one at a time, and applying a test pressure source. This verifies the 1

7.3-7 L

i GCSSAR l , QUESTION ( 421.42 In Section 7.3.1.1.1.1 of your FSAR, you indicate that (7. 3) the HPCS system will automatically initiate, if required, l during testing with specific exceptions. Parts of the ( system which are bypassed or rendered inoperable are indicated in the control room at the system level. In your response to Question 421.04, provide details relating to the HPCS system. Specifically, discuss the interlock which prevents HPCS injection into the reactor when test plugs are inserted during logic testing. Resolve the discrepancy between your statements in Sections 7.3.1.1.1.1.C.7 and 7.3.2.1.C.l.j.

RESPONSE

( 421.42 The High Pressure Core Spray (HPCS) system is capable of being completely tested during normal plant operation. Motor-operated valves can be exercised by the appropriate control relays and starters. Should HPCS be initiated during testing, valves will re-align, allowing high pressure core spray into reactor vessel. A motor-operated valve

                                                                                               =:

l (MOV) test switch in control room removes the over-torque interlock bypass associated with MOV's for testing. This is considered less reliable mode of operation, but does not prevent HPCS initiation (HPCS OUT OF SERVICE light illuminates in control room) . During plant normal operation HPCS system can be flow f tested by discharging into condensate storage tank. (

421.42 (Continued) HPCS logic is tested by applying a test signal to each l i e' analog trip module (ATM) in turn and observing that channel trip device changes state. To verify that both elements in one out of two twice logic are functional a plug in test box is used to operate the logic as one out of one for verification of single element function. If desired, the variable associated with the ATM can be varied and, in conjunction with the ATM output indicator light and appropriate instruments, both the transmitter and ATM outputs can be verified. In those cases where the sensor is disconnected from the process variable to allow testing, an out-of-service alarm will be indicated in control room by administrative action or automatically when analog comparator trip unit is in calibration. Test specification allows this system (division 3 power augmented by division 4 channels) to be down for testing during plant normal operation. The HPCS OUT OF SERVICE light in control room will indicate HPCS is at degraded performance or inoperable during these conditions. Though not implemented to meet the requirements of testability, the Automatic Pulse Test (APT) continuously and automatically performs end to end testing of all active circuitry. The APT improves availability of HPCS system by minimizing time to detect and loc a t.o failures. (

GESSAR II 22A7007

       .                                        238 NUCLEAR ISLAND                           Rev. 0
7. 3. 2.1. 2. C. l . i) Specific Regulatory Requirements Conformance k (Con tinued)

The sensors can be calibrated by application of pressure from a

               ' low pressure source (instrument air or inert gas bottle) after closing the instrument valve and opening the calibration valve.

However, transmitter output is continually monitorable from the control room by observing meters on master trip units. Accuracy checks can be made by cross comparison of each of the four channels (A, E, B and F). For this reason, trans-mitters need not be valved out of service more than once per cpera-ting fuel cycle. The trip units mounted in the control room are calibrated separately by introducing a calibration nource and varifying the setpoint through the use of a digital readout en the trip calibration module. { j) Capability for Test and Calibration (IEEE-279-1971, Paragraph 4.10)

1) HFCS HPCS control system is capable of being completely tested during normal plant operation to verify that each element of the system, active or passive, is capable of performing its intended function. Sensors can be e.xerc_ised by applying test-
                                                                         --s,   _ _ . . , ._          ,

p.ressures. / Logic can be exercised by means of plug-in tes,t_swi_tches I (usedalone.orinconjunctionwithsinglesensortests.'Pumpscan

                                                                                                    \

be started by the appropriate breakers, to pump against system _.gy. \

           /    injection valves and/or return to the Qujprbssion_ pool [thrN b est
              - valves while the reactor is at pressure./ Motor-operated valves can be exercised by the appropriate control relays and starters, and all indications and annunciations can be observed as the system is tested. Check valvas are testable by a remotely operable pneumatic piston. HPCS water will not actually be introduced ir.to the vessel except initially before fuel loading.

7.3-197

A f A

                                                            / Jacr4i/              A         exatf/      / /        is lTu rceca      / I         /      /
                                                                                               / I//            ///
     .  %.,nrus /           /   /      /       / / / / d dez-f {// Teu                              "       V V L/         (   / //               If        i /

cart / BY v p)I v y QuGST/0N 42/.4] Indicate why drawing I-170 A. Rev. 4.. lists check valve F 019 . as a control valve. RESPONSC 42/.43 aor< bo/ va />< i,, rXe

                                                                          ..r s Dra.wi y Z ~ /70 A , Ac v. 4 , fi.r f.r <*/ve F0/1 ira t a.s e. .Je a.k va/vs        in 14fe f/2 (Ant) sy.1 fen.

ES/(ac/c} Sy.rrsn, O e e

                                                                                       .p e

e O 9

y 421.44 In Section 7.4.1.1 of your FSAR, you identify conditions which are ( (7.3) monitored and which can trip the RCIC turbine stop valve and isolate the system ~if their set points are exceeded. Discuss the details of this design. 421.44 RESPONSE: Table 1 lists the conditions which initiate an RCIC turbine trip by rapidly closing the RCIC turbine steam supply stop valve. Table 2 lists the conditions which initiate RCIC system isolation and shutdown. Instrumentation incorporated in both the RCIC and steam leak detection systems are designed to continually monitor the conditions listed in Tables 1 and 2, and initiate an RCIC system turbine trip or turbine trip and isolation, as illustrated in Figure 1&2 logic diagrams. GESSAR II, sections 7.4.1.1.2,3,6 and 7.6.1.3.2 describe the details of the logic shown in Figures 1&2. While environmental and equipment ( protection is the primary purpose for isolating and shutting down the RCIC system during abnormal operations, the design incorporates

   .-        precautions to preclude spurious or premature corrective actions.

Table 3 lists some of these precautions. i l l

                                                                               ^

t

      /'
 /                                 -TABLE 1

( RCIC TURBINE TRIP SIGNALS HIGH TURBINE EXHAUST PRESSURE LOW RCIC PUMP SUCTION PRESSURE TURBINE OVERSPEED MECHANICAL TURBINE OVERSPEED ELECTRICAL RCIC ISOLATION LOGIC "A" RCIC ISOLATION LOGIC "B" TURBINE TRIP MANUAL TABLE 2 RCIC SYSTEM ISOLATION SIGNALS HIGH TURBINE EXHAUST DIAPHRAGM PRESSURE I HIGH RHR EQUIPMENT AREA AMBIENT TEMP. HIGH RCIC EQUIPMENT AREA AMBIENT TEMP. HIGH RHR EQUIPMENT AREA VENTILATION INLET AND OUTLET DIFFERENTIAL TEMP. HIGH RCIC EQUIPMENT AREA VENTILATION INLET AND OUTLET DIFFERENTIAL TEMP. HIGH RCIC PIPE IN STEAM TUNNEL AREA TEMPERATURE. HIGH RCIC STEAM LINE DIFFERENTIAL PRESSURE OR INSTRUMENT LINE BREAK. LOW RCIC STEAM SUPPLY PRESSURE i

jE ) TABLE 3 l

1. ESTABLISHING TRIP SET-POINT VALVES FAR EN0 UGH AWAY FROM NORMAL OP VALVES, YET SUFFICIENTLY CLOSE TO PROTECT THE ENVIRONS AND EQUIPMENT.
2. INCORPORATING TIME-DELAY TRIP LOGIC CIRCUITS
3. REQUIRING COINCIDENT TRIPS TO INITIATE CORRECTIVE ACTION
4. USING TURBINE SPEED RUN-BACK, RATHER THAN COMPLETE SHUTDOWN, TO CORRECT ABNORMALITIES WHERE ENVIRONMENTAL OR EQUIPMENT DAMAGE IS NOT IMMINE
5. SELECTING RELIABLE, SAFETY-QUALIFIED INSTRUMENTATION AND CONTROL EQUIPMENT.

t 4 t

ees F l^vn E- 1. - . T G t 17. L O G- I d c t R (L U \ T GCtC T U fe 'B i r4 G rr i G H Tu il (b i tss i EA Itnv5 T PflG*.Surt6 i o n c,- 6-r T 0 0 ca n n E Ex Hnus T i'R EM O R E . l Pct caudE uou R e t c Por t P S ucrtoa b -

                                                                                 \        ra se      vnv e tug b i N 5              o u c"t't & PE6 O E LECTRid sL             -

nl saue no s o

                                                               "    ~

TSotATtQN v. o c- 1 e A-Retc Ete s c E 5 0 G4 Ts' d N L o cr e c "B " TRtP M an v4 L.- FU tt O L a d.

                                                                                         ~
                                               .-           F t G u ti' G - \'.        -
                                                                                                               ~

ft C i t 5 Y S T E fvt T c o L. A , , o rst LOGIC ctGet T 'k ' h-t G H T O R ib s N E E A H rt V S T D l tt P h il A GM P ctE%uME 's" a- t G t-r T u (t(bn H & Ef.HhvLT D I & Prt fl AG M P(tEssullE

  • E M \G H RHR E Q u s t' rs is < T rVit En Mt-t o t EHT TEnnPalMTUM i A l sr\ G n1 R t, R EQ os P M c~bt T r+R ER t+\*i () I CN T TElFift A10stE. 2 A t,tG H 62 010 E Q 01 P Pi CN.T if11 Ed Al i se E8T TENrErmTdtE 'A" stcER DiFFEstEKTlal TsMVataTOf6 I A cc L G H (<n R Gqut9 M DLT y m
   \- k & H     Ct r1 G c'Q,ost M eat tr Gin O t FFEnENTltf L TEMf GiuiTvrtC 2.h-
                                ~                                                                      6162 Y       '

H t cr t c R c I c. EQ os Pn des T n (sTA O l F F E REN TI H L TEMVaknTut Eot. Arc s t6 na S TGn M Tv kn E L (+ tt En PI P E Tas-irifts tv{tE " A" "A " 14 s G rr d w .1 C

    ;4 tG- W    l}cIC. STEAM Lt M G DI F F eill ENTtif L TEt*PcitgluRE ' A "
    'rri G rr R O t C- 6 Tert M Lt M E Di F F EREt4TI AL TEr49sIMTult6
  • E' Low R0 C 6TErrM svPPtY fl? 6 6 5 ut? E' "A"

A 421.45 In Section 7.2.2.1.I of your FSAR, you indicated that the ( (7.2.2) condensing chambers and all essential components of the control and electrical equipment are either similar to those which have been qualified by tests for other facilities or additional qualification tests have been conducted. You also indicate special precautions are taken to ensure the operability of the condensing chambers and the inboard main steam isolation valve (MSIV) psotion switches for a reactor coolant pressure boundary (RCPB) break inside the drywell. Confinn that the condensing chambers and MSIV psotion switches are included in the environmental qualification program. Discuss the differences between the qualified control and electrical equipment which are similar to those used in your design and the additional tests j which have been conducted. In addition, provide the details for the " precautions" you have taken to ensure the operability of condensing chambers and the MSIV postion switches.

RESPONSE

The MSIV position switches have been included in the environmental test program applied to other safety related instrumentation and control devices located in the drywell in accordance with IEEE 323 1974 and RG 1.89 as stated in Section 1.8 Condensing chambers are code vessels controlled by ASME code rather than being subjected to qualification tests which are applied to electrical equipment therefore they are not included in the i same qualification program, as the position switches. l f

r 421.45

   ,   (cont'd) However, the ability of the condensing chambers to perfonn their

(' safety function as components of the instrumentation and control system as predicted by analysis has been confinned by actual operation in reactor plants under the extreme environmental conditions associated with a LOCA. All essential equipment used in existing plants has been (or is being) required to be environmentally qualified and from that qualification is developed a list of instrumentation and , electrical equipment types and models acceptable for applications in GE standard plants. Such equipment models are considered type qualified for use within their qualified applications and ranges, and environments. In the event that other equipment types or models not previously qualified are considered as alternatives for these qualified devices they shall be subjected to the same qualification as those already typed qualified. The precautions taken to ensure operability of condensing chambers during a LOCA event are as follows: The condensing chambers on the reactor vessel are physically separated by dispersing them around the periphery of the vessel at four different azimuths at least 30 apart. The routing of the lines from the condensing chambers is such as to avoid convergence where there would be a potential for comen damage as a result of a LOCA. The slopes of the instrument lines from the condensing chambers to the drywell t penetrations are kept to a minimum consistent with adequate

                                                                                    ~
 ;              venting of non condensibles and air back into the chamber so that the vertical elevation difference within the drywell is kept to 3 l

i

421.45 practical minimum eith a recomended maximum of fcur fe:t. (c:nt'd) This serves to limit the maximum boil off that might occur during a postulated condition of drywell temperature being [ maintained in excess of reactor temperature of time sufficient to pennit boiloff. In addition, the condensing chambers are connected to the vessel with a pipe sized to allow ample cross section for condensate drainback and free exchange of steam

        , and non condensibles between the vessel and the condensing cha.mber, to prevent any possibility of condensate binding or excessive non condensibles buildup that could prevent adequate condensing of steam to keep the reference leg filled.

The MSIV position switches are not required to initiate a scram on the RCPB leak within the drywell. Therefore, they are not required to be protected from damages that might result therefrom. Drywell high pressure avoides the scram signal for this condition. ( obviating the need for MSIV " closure scram" for this condition. Therefore, no special precautions are required to ensure operability of the MSIV position switches during a RCPB inside the drywell. However the following features give a high degree of assurance that they could give a valid signal during a RCPB if desired. 1) distribution of the position switches rmong the four valves (one on each inboard valve and one on each of the outboard valves), 2) housing each of the switches in a separate cast steel condulet switchbox, 3) qualifying them for the LOCA environment (pressure and temperature and radiation) and 4) use of fail safe logic. 1 The MSIV closure scram logic is three out of four inboard or 1 three out of four outboard valves closed 10% or more to cause j scram. The valve position switch circuit is fail safe in that a broken wire will give a channel trip signal.

421.45 Furth;rmore, the MSIV closure scram is not a safety function (cont'd) that is required for a RCPB condition within the drywell (' becasue MISV closure is not initiated by a high drywell pressure condition. f ( i a s - _ - . _- - - _ . _ _ _ . _ _ - _ . - _ . _ _ _ ._ _ . _ _ _ . _ _

e m =emennesamme e:= r: . & :- m o n A A A 0 5: '"' ' 'e; ,

       'cubrwen /    /    / /      /      I    /      /     /nctb I /             I      Arce l     /I      /

m, s / / / / // / / sceleso & \

                                                                                  '/           ///        /

are // ( y' (/ // l/ areL/ // 9)) v v v - v - v puESTION 421.+6 In Sections 7.6.1.8 and 7.6.2.8 of your FSAR, you describe the containment vacuum relief (CVR) system. Confirm that the CVR is , powered from class IE power sources. RESPCAfsa 421.46 7%e Cau'At,.me.f Vse m fe/ref (cvk) sp;% is powere/ k-C/asa .iE pawer .sa w ee ry /2 S VDc Bu DC-E for Divisina 1. d /23 V M E u.s DC-F Ar DIvTJio 2, a.c . s 7kfed in 3*.<.Yio n 7.d'./. 6.2.2. tac re. Cla.u 2 power .so vces ers .sdowse /** A)=re d.3-/a O . e og l i 4 9

7 421.47 In Section 7.3.1.1.1.2.C of your FSAR, you briefly mention testing of the automatic depressurization system (ADS) solenoid valves. These valves cannot be fully tested with the plant at power. Provide a discussion of your proposed method for integrated testing of these valves and circuits, including the frequency of testing. Identify other ESF systems where either a portion of the actuation circuitry or the actuated device is not routinely tested with the actuation circuits. Discuss your proposed method for integrated testing of the circuits and components, including the test frequency.

RESPONSE

Integrated testing of the ADS solenoid valves and circuitry is not. performed with the plant operating at power which is consistent for safety systems where the final actuating device (s) would cause temporary modification of plant processes such as fluid injection or discharges. The BWR-6 standard technical specifications provides for a functional partially integrated test without valve actuation, TWs is supplemented by a manual one-at-a-time valve test using Massociated actuation circuitry from the transmitter trip units with the reactor shutdown but with steam dome pressure equal or greater than 100 psig. This test interval is 18 months. Additionally, the transmitter / trip units that provide sensory inputs to the ADS are checked by control room personnel and the logic chain up to the solenoid is tested by the automatic pulse test performed by the self test sub-system and described as the sixth test in the discussion in 7.1.2.1.6 Other safety systemssuch as RPS, portions of CRVICS, MS-PLCS, HPCS, LPCS, RHR/LPCI, , RHR/ containment spray mode, RHR/suspression pool cooling mode, safety relief i valves, and water positive seal system likewise have components which are not activated or tested with a complete integrated testing procedure. Each of these systems has a modified test procedure that utilizes a manual test which allows for independently checking of individual components. The frequency of these tests, parameters verified, and procedures are included as part of the technical specification. The automatic pulse test described in 7.1.2.1.6 is utilized for these systems where appropriate,and also is included as part of the technical specifications.

42I.49 QUESTION I Demonstrate that the safety / relief valve (SRV) low-low set point function is adequate assuming a sin'gle failure which could cause an additional SRV to open duriag the time when only one valve is permitted to be open (i.e., on second and subsequent valve pops). 42I.49 RESPONSE This concern was already analyzed and the Low-Low Setpoint logic was subsequently approved by the NRC. See NUREG-0802 written by T.M. Su, USNRC, Division of Safety Technology. The instrumentation and control logic is specifically addressed in Section 3.4.2 of that report which is titled " Safety /Felief Valve-Quencher Loads Evaluation Reports - BWR Mark II and III Containments." ( i

                 -                   [$3 k                    tinyi9 y
                                                                              % ~1    _
e. / RI. TiKL
         ,50         In Section 7.4.1.4 of your FSAR, you provide information on the remote ~-          )
   ,7.4 M            shutdown system (RSS). Attachment 2 provides the Instrumentation and Control Systems Branch guidance for remote shutdown capability (i.e.,

guidance for meeting the requirements of GDC 19). Indicate the extent to which your proposed design of the RSS .qonforms to the guidance provided in Attachment 2. Provide the following additional information in your discussion using drawings as appropriate:

a. Design criteria for the remote control station equipment including the transfer switches and separation requirements for redundant functions.
         /
b. Discuss the separation arrangement between safety-related and non-safety-related instrumentation and controls on the auxiliary shut-f down panel.

N -

c. The location of the transfer switches and the remote control stations.

N I d. A description of your isolation, separation and transfer override provisions. This should include the provisions for preventing electrical interaction between the control room and the remote shut-down equipment.

e. A description of the administrative and procedural control features .-

to. restrict and to assure access, when necessary, to the displays and controls located outside the control room.

f. A description of any comunication systems required to co-ordinate operator actions, including redundancy and separation.
g. The means for ensuring that cold shutdown can be accomplished.
h. A description of the control room annunciation of the status of 'l "

remote control or override status of devices under local control.

1. Discuss your proposed startup test program to demonstrate remote shutdown capability in accordance with the guidance provided in Regulatory Guide 1.68 Revision 2.

J. Discuss the testing to be performed during plant operation to verify the capability of maintaining the plant in a safe shutdown condition from outside the control room. l l l l

f ATTACFMENT 1: ASSESSMEfiT OF (f32sv $ se RSS COMPLTANCE The NRC's Instrumentation and Control Systems Branch (ICSS) has issued a 1 position on remote shutdown capability. An assessment of the compliance of the -Mw - RSS with the ICSB position is outlined below. MSS ICSB POSITION M 'D RSS DESIGN

         -     10CFR50 Appendix K, ECCS Requirements                                    g Tld MJL.

o Only LPCI in one RHR loopf& o Transfer of control to RSS disabled in transfer to RSS panel, should not disable any automatic actuation of ESF functions. All other automatic actuations of ESF functions operate normally. Therefore, the RSS o Specifically allows bypass gg of automatic LPCI actuation. design satisfies Appendix K.

                                                          -l{MW '.                             % 6e qq            -

M&&

          -    10CFR50 Appendix R. Fire Protection Requir rents o Provide separation and fire SW       o-      .

control room design protection in control room includes necessary separation and fire proection. design, o Or, provide non-redundant o RSS is not a safety system and s afety grade systems for fire damage is not within the re..ote shutdown assuming existing RSS design bases. RSS a fire in any fire area. Mhih pA2A h % pM.Q* ce3 M

  • f^o p% p k h dLMw
   '                                                     ( A(E. Mi% += hed4. phi 4 PM.                  ,
            -   10CFR50 Appendix A, GCC 19 ( As interpreted in Standard Review Plan 7.4) fful.PA8 o Provide redundant sa fety grade          o RSS is not a safety system and capability for remote :nutdown therefore m'c.d=; i: ut M' assuming no fire da.93;e or      d A:;d r:d. Ad4A^dAni cowi%R                M AOL., wrt acci dent has occurred.

Q@%At RdM

                                                              .-                   A R.M PM.

o Some redundancy is provided through operator actions at local panels.

                                              '
  • TLR kS$ 'd- M A 99 addc% aa.
                     'os Aiu i f f. f 2A                          ju%

L YL. CdA.R , 4Tcb Q M.w&% 3y w bz- u% & . -

6

                                               . - . _ . . .               .      -.m...              .-.. ._.                                           ..                              ...e.                          .- e . . . . . . . . .                       . .                                        .          . . , , , , .

4._ -dsa -_..Rn.w2.a . .skutM 3f.au~p &

                                                   ===_m                                              a&*                                              ek *                                                       .ie                                                                                       w, 2 J :^: G & u b 6..L: %                                                                                                                            ~ ~ : mal. nua_-

L

                                                                                                                                                                                                    ..a

(_g . .. 4 . . _ stW_ _ .&- ae

                                                                                                                                                                                                                                                                                                                                            ~
._                                                               .a. _                                                                                                                                                              9 mme                                                                                         .            ..                                      _                                                e. eams     c.        e-
        . e .ee.m    maempsm e    em                                         w e.                          ==

_TT::

          ^
 . _                  .               :~ ~ ~ V^~ ~ ~ L- . __ _ .. __ _. . __                                                                                                                                                                     _                          _
                              .._                                   .___                                  __           .-...._..+--__._._....._._._..g.._._                                                                                                                                                                          .
                                                                                                                                                -                -                                                              -__                                              h.                                      . LM_
} ___ _. _

lt dou_. skqa ~Q Z{4p__ _M1L. - w&i. .2h cu. -._R_S SL. -.. O__ _. _ __ . _ _ _ __ _ . pou. . _ . . .. .. .. . . .. ... _ _ _ . __ , -._.A.dk h [ dhuA.A_.__.md$_E E. b . T _... _. _4 ._ . _ _ . .. _ _ _ _ . _ . . . . _ . . _ _ _ _ _ _ _ __ _1d.a. 6.k. _ctwl ____. h C ..re. p hew _ _ .--. h53Mi _... . . l.i . ..M

                                                                                                                                . r...                                                                                                             .. . .                        . - . . . . _ . _                                  .--
 .             -                   _ .. . . _ . _ _ __                                                            . AGL                             ocvd                   .. d _ _.. _.                        ._-                                            _ .                   . . . . _ .
                                                                                                                        .M'         -m     .
  • 8' ** 'O MM**@ m **'*.he -.W .e e. g & _ _= as
                          .,e       e    3e,              . ee-e.e..                  e ...e.-               .Ie
                                                                       , .     .o                                                                           *                                               -          o.                       ep                            g.     ..                         . .
              .. .. . -- . ... .                                                                                                                       .       . . =.                         - .- - - . .                                                    .                      . ..                      . .. ..                         .            .               .. . .... . . .-. .
                                                                                  . _. ,.. .. .                         ~
                                                                                                                                                                       ... -IO4_._004                                                                       .. _ .. _                                                                                                       _k.__ _ _ _ _
         ._ . . .... ._. . h . _ .T. iqN                                                                                                                                                                                                                                                                                             _.

d m _ _ .y ... . . . _ .

                                                       .-                 .                             - -.                       - . , - . - . .. - .. .. __ . .- . . . - - . . - . . . -                                                                                                                                      [                              h                                                _ . . .
                                                ... ... . . l                                                              tcaS                                       .b O ..-..kzkto2% ydis M ,_
          .- .                     .                  . - - . . .. ,                                                                    e-mi. .                                                              ..-.m.--0                   .                                      e                                                                                    .mm . e w                             .-                                       .
       ... -- .. .. .. . . .                                                        - .                - - -                                                   ..-                   . .               . . ~-                                                                      .-                                                                     -. . - . - -.-..                                                        .

bg _ . m .h- ____ . __- _._- 0 i _-.7 m e d .._._. 4.-...-p _ -- __ Q. . z ' .

                                                                                                                                                                                                                                                                                                                                                                                                           .. .cA; .
          . _                                                                   _                                                    ,w                                  __                                                            -
                                                                                                                                                                                                                                                                                . _ _ _ _ _ _C.A. S- ___                                                                               ._. ._.                         . __ _

Mi w

                        .e                                                                e                                                                                                                                                                                                                                                                                                           - w h-M-..W.*                                                                                                               .        egeu.mmmu. -                                    em w                                                                                                                                                               semese                                           m ,
     *   .W**-..N                                            -GNde                  bm>e.-.6         eW.mW.                             a. m e e                            mw                                                   e                                                               ..6mm.m.                         mm..h.                       g .m              gm m e q                        w. mmh h        au   MeNe+6                         ... -    hmegm.m                          .mmp.% gs             e,w,                          w yeepw og                                                    gg                                          m -wwwg..                                                               mwe e.w                                                              ..ge.ew                         .gw "h.* * .*.                                            eM.&_                                             .-                         e                         -

eWMm 6

                                                                                                                                                                                                                                                                                                                     %4..                ..*.hau.-a@&6W                                                        h...m.'m
 .'.ah6                   -e                                      .e w              e           e     s mu.am               - . wee m -                                                                           .emp                                ww..% m .e                                                                   .ge m e w -                                   ..ma ush m.            O .          e.au. map a.e. e .

N 6 s. h .m .Wh meg em m W h ei. M .N gm m ge. w e .g M W 6 e.M6M6 .m

  • M 6*N . e.g-. uM- N 6w .e.h N*h eeBG um -w.em...6.
   . .**             6.N#               +6-e*                                            m.6e                                  .ghqeW                                                            g66.h-.                                                                                  M.+66.^66                                     -M*"                     66                                       .. b em           M.
                                                                                                                                                                                                                                                                ..N-6.                                                                               .h..                                 .M.                                                 46
 "                 .-8         h.               mw           eg      ,e               , ,            p,,,,                             ,,,,,,                      ,,                              p           g          ,           p        ,, , ,                                  ,             ag         a        , . ,                     ,, , ,                                     ,  a,,,,,,        , , , , g                      ,
                           ' *                *            *W"-
  • 8*-*--N 64...NM . m e e6m . .O e- wewhe -gm ee ..'e e .. Me .. 6 6*m.-gh se eenn . .6 6Mee- * . .
                                                                                    "     W         * . . . he..                     . gee.g--im         N**             ' . * .         4.        I. h..=        6  *h       .&         WM           .P"'        * " **
  • N"'- 8 WW' * - ^.' . N N*"4'. &
                                                                         # -*
  • 4 = *8'M' ' N * .e e> 4me. -s eu. e e. m- - -,amm . --_ h . ** 6
                                                                                                                                                                                                                                         .**e..                  ..*          e....        e    e                  . e.                                ..
                                                  . .. - .sw                       -.             == ..                                  .-==.....o..                                                       .e.           ..
                                                                                                                                                                                                                                                                                                                                        +.g6._h M                                                  . .                                       h                                   ..M
p. *h .m .h- _M_

m . . . y.

    .._ _.. .. .                         . - . . -.._A..mtus_Ao_                                                                                                                                                      ___. a.o. w .                                                    to. a _____.
                       ._. ._ _ _ . . _ _ _ _                                  %d                                     _ .. y^ _ . A _ _. p u u A . _ u A L L _ t w i _._ . k _

___ . _ . . . . . _.. . _ ,.J t . . _. . W _ ._ _ - A.eemN J2h 9 . d. - - . ~ - _ [LA _ .' " M. __ bL._ .[),,atp,,,{-d_'hA..___.[g cdl,__RLQ.,M b_.._. f%.O_. _. q _ 6 - 4D N h _44.m l yp g _. _ .

L j-- E44;%GGKM&K - _ . .._. _ _ . _ _. - _ ._ =

__. p . _.

                                                                                                                                            .Mp                                                                                                       _                          .                                     _         - _                . .
                                                    . .. . ce4w%x                                                                     m6euut M +                                                                                                                                                    M % . A.:

M .j _. . .. .. . . ... .. . ... . . . . . _ .. E'*'*** "..e ag . . m e .e . , . . .

                                                                                                                                    *- * * * *               ""**         *6         * * * '        * * * * * * * **   *#"*M'               O
  • D
                        ..h.&                                            .              ..           6       _*.*.4
                                                                                                                                                                                                             .                                                                                                             e
g. - .. .. . - e
                                                                                                                                                                  -,-,-------,,.m                                                   , . , -                               y-.      --
                                                                                                                                                                                                               \

w 0 e

                                                                                                          -go . .                       .......i-..===...ee.e,.e-                                                            .        .- .=           .e.         . .                -- - -                 '.- .
                                                                                                                                                                                                                                                                                                            *                        ..4     - -- .                      6
      ,,,              .                . . --.         ,. .         ..===.=ame
                                                 ).           .,                                    .I--.                                                         . .-. -.                             .                  .-                                                   -                           e                              .                                       _.

_ ._. - -..- _ _ - ~ .. ... . ~... - . _ . . M

                                                                                                                                 **-.                                                                M
  ..e.-                           .WM                            ..
    ~ l . LT . ..~. ~

3 5;T ME lAcadrK.Lif~.~.M._~2%OtC

  ~^ ~~ ~ ~- ~ ~

____ __ . _ . _. w.9, a _,. m u  %... _ G. a. H E

 ._                                                                         W~~4a- _ r.m s h 4 L _t e a                                                                                                                                                                                    w ouB- da_

Q ______catups__.%. sh __undib _., W _ w t&. -. _ . _7 Z_ _~~ Mhd a dra t i g _ L .~ + Q u. A 5 3 u.

--e==
                                                                                                                                                                                                                                                  +h_.adia_ m _

~~ ~ _ . _ _ %m uh te

                                                                                                                                                                                                                    .-.- == --.. . . . - . _ . . ..-                                                                        , ..                                           .
                                                                                                                                                                                                                                                                                                   --                     e.g.                               6.w                M6e w e y mwomgm                                                                                                                    m-

.ep-

                                                                                                                                                                                                                                                                  .m-ph_.                                                                                         N 6 -_ --

6M ,q _. .- _ _ . _ _ - - - - _._ _L .- ._~

                                                                                                                                                                                                                                                            . *.-                 . . e                  eme             ..e      e--e-w*              w.                  a...

w- a.= ee m- e e. e g.m . -- _ .. p em. .e We-e h-e w ep.yeq e e em e e. - N 6e

e. e --6-.u w eme - .N am es....e e .ee - et e. >.wh
                                                                                                                                 --e6N            a   mae ee                                    a  p-           .ee....e.         -h g             eee.                           ece       - h m e g. em              ..64       -   e. .e e m m.e_e.e.y                    . p.            ew ,. e                ye e m , ,                       ,,p      4
                               .e     ,       ww        - m           m    e.WW*                  .                  h"             *W84'-*M*N"'6                        h*.e     ww.e                    es.    .                  .De
                                                                                                                                                                                                                                        .. m
  • M**4PG * . e..e-..-e e .y . ee gy,. ,

p - m-m ee 6 e -me.e a. m @. e&=-M.m

         "*                                        e .                               e                w4 ee                      . . -

e- - n -

O g, , y -g-we e. .- - e e e e ee e aem e w eeaim e e e e se ei- .e em e apse. mpg . um -amee e e. ewee +oedemmeee ,eme- meeenemumum e. -.e . ,--p ,, - e umm e me -e 6 equum-em

                                                                                            /

_ .._ . _ _ - __... .e _ h.. -e _. . @_ . A-((.E.d.A. e- 6 .e. . ..__ _

                                  ..                        .              ._. -..                                                  . . . ....                                         - ..                                                      ...                ---e-...                              -- .                  4         -. . .- . . .-                                                              .... .                    e     . - ...                              e                      ....

_ m . _____ _ _... . . ._ ._e. ___

      .-.                       e       .- .. - . .. ....._.. ...                                                                                          ..e_                       - - -- -. . .-                                                         ...e             . - - - - . . . - .___ .-. _                                                                                               . _ _ - . _._ ...._ -.--_

ame s p .emi-Ma- musea- e 6 -Ae emumie m @ e gumu-. 6m6 --e .hh peew em & em e , w w w. Omam epme +eee eM= e 4 hege eWhmeo ee m.e em ehM eemuse yin - e emm . -- -

                                                                                                                                                                           -                                    4                                                                                                                                                                                                                                         -
   .$     hg                                          .m we                       e eewM                  W                                                                                                            men N+                   egudemD e       e-6 eN N m Mgm                                                             .ma+              w4m                                                    e e em em                           p       -ma                 e
        .. .                            ..           _e                 -                            .-                 m.                   .-- .              .e                     e          -.-- - - - --. . - -                                                                                                                         e..-.                                                                                      .

ee emes em m pes awe am- emweeese eWMN W N hpeuum m e_ ml.P . N m um enim .mm em

 .gepg w NM ee .                                                                                                                                                                                                                                                                           M em Wem emiMe W 66e                                 @ w w amem                                                                                                                                  N                                                                                                      h                                m @ m m h em ew ,m                                                                                                                                                                 -

O 9

m. h e .em -
      --em                                                                    -                                                                               -                                                                                                                                                                                                                                                                                                            m-.

e p h am .. 6 h eh e Nem W

         =@ pub'      we        A     e        Nh                              - em           e     hee 6 hee                                       e4pm agppe $w e6e 66 a-@heh
                                                                                                                                                                                                                                                                                                         ^

p wheh w s- W6 W emmune -.m. en MWNe..e - h

 -W.4                  hrep.e                                                                                                       W ee             --en             *mem.-hSee6wNN                                                                                                               N                                                                                                  e he6                                           Ne mh e e.w e                             ge==p      e 6esemeP e
    +.MNm                                                       e                                nem g                 .            h66 eme e 4 M.e*.66                                                                                                                                                                                              --M                                                                                    --Nm 6.e em h eww 6-                                                                                                                                                                                                                                                                                                                  .

tre-4 m4n m m , ep w aem 6. e=+e W 6-*=W66**een N W e4 6aut-66-e>h e.-wm--e e w , .._m ~- ese eensM emme 6 e4* _ m ey - eh N6 eee he -m e .weee me W eep'g om es e 4 em e h & ammen-- ~ -e.==me.es, ex--mm- m - --ma- ===ep -m -.me===

  • ei e n am e ese , em - emmm e=mp m e- D,.Ms6e p. e e Ma 4D Ger eme=m W 68'e* Nm6 eue e 6 . M6 m ew 4 me> + mg+ e 6 me e au@eeee- h
m. _e e . - . .. . .e . . . e-e--e.. a. ee--== eeeee- =.4 -- --e.-... - .---- e-- - . .e. . - . -- .- ._. .
           .                                                     .                    . . . .- - ._... ..                                                                                - . . ..                                               - - . ..                            ...e                    ..-- . . - . - ...... -                                                           - -.                                  -- .                -e.._                   ._ _ _
                                                                                                                  . m                m          gis   e .                                e       in&        we--            -er ee        m.**eeme                                =       ese ses'we6e                        wwh.@ ee-                              N-      'mmNm,-es-ammw.-w.                                                        hhmumpumm.             ee           ee        aneae ex--4 e -             e               D*e.h              e shWd c'4e6                                          6      eh    *Wh.                  ='6                       W * .          ^61'en=m6m.le                         ee eD              e -       an-      e     ., ehe                 een w4 e                 ey          - w m    -g                                         m        ,           .em          .we
                                                                                                 ,e                         p                                -e,                 ,_g.w                em           a     6*.h--e-h6                                             *ee'e            e   -*Ne.y               . M.We.-M-                                   6         e.m4mmmme                 -   gum _,s.g..ammye                                             e..,,e,,                ,,           e,
h. ,
e. ,

e 4 e e eme e.en e em ..e _ em e

                                         ,,,,                 e

i

                                                                                                                                    .                             _=

9lDe .'=6 m mw.ee

                                                                                              .                                   W e                   ..elum*       88.'  M      '*&.
                ~ ~i.
                                    .i_J~_l_~ M o d i { w .ii lfi %._ X M s~_li _
                                                                                                                                                                          . _ . . .                                     me
  • 66 .

g _ eue.she_ e6 h w .Wme. m

      ~

11 ._ 0i_ A _id fl$~3_1.audco_e A 'u.i

      ~T1                                                     TGiF5L,A L paiaas                                                                                                         _A
                                    .                             muauaA . Caw 2t_.un                                                                                % cuAa I                       .ies  mi.
                       *_ . - =

6 N* i "' a an-G

a. ns ~

_ ~2AL M 5 % ._.iE_. h _.w..._. e2Zi~_ _

      .._ _ _ .____ h e w p s. m _ a ta __. e A
                                                                                                                                        ~~

ZI.~~ i.._ .I. M _ ce i T . g ._ M~._.lwdt if

          .                                 _          .      .................q_                             .___.. . . _ . _ _ _ _ . . _ _ _ . . . _ . . . . _ . . -
                                                       . . b n.A_v & 2A.._.to._. A ._ g p M cw._ p l.                                                                                                                           .
                              ~                               ~

i .-i . .- p9A d t { M 11 Q ii h l % % Il.~ll 13 g s ::- u r u e c t e u ; 4

4 *

                                                   * .                                  m                                     -                                                               4-=             e                   e e                                                                                                    ,         o

_ (c g q - __..- . . _ _ . -_ _ ___ _ - . -

          .._ . _ . _.. _..._C u .ppe. .._ pea,_mx ch- . __.                                                                                                                                                                                                   ... . _ - _

g - .a e, ,,gm, e n. m ra-ee M. -O+e

    ~ I.. ~_ ..l ._lA~ Elf ~AEkguvUim.. TIKE ' ~'~~

a sneaut_wo _aA_E _.Z Z_ 6 - 1.____. uuh_a__au_.A. f _d m 1~.T Z 1-_T_.em hrdmC-~dh _ rk st _..f h __.. p 1Tu d _ W~ hA_T__

           -~ - - -
. ._ ~~~ h ~Ts ._ .. Eh u e *N GD em ee-
                          ~

W.WTOhv ~~r. +Pa _ _ & _ _5 C i~d a r~ _

          . .. _ ..- -- cx4k Em_..                                                                                                                                                                                                                          -. ._. _. -_ .

M 4eeW __

                                                                                                               .=

6* N =***me**=l>***N--No ee_M weme e m.m. e. *-Mum' e w.m e _

                                                                                                                                                                                                                                                                   . He                            ewN*e N

_gwm .pg m e h O 6-em We hw W W.h m m--ew.mv- W w meh h w. em e 6mW -e p+ e 4O estee -eNq*w w eemmee

                                                                                                                                                                                  .ma_
                          .. .-- - _.                   e    ._ .        . . _ - . - - . - . . . . - - - . . .                                                             .-._           _-----._.._...-_...--..e.                                                                                                 . . -

N O

                                                                                                                                              "* ***                         **** ** Nh"                      * * * * . " *
  • e e---m e e--empamu **====*. - _ * =
  • 4m.
                                                .._,.-e             e    e    . <-     m-M                =.4 em_ _         _w.me--m                     W     -ewes            --em.-extin          -m.      O     ww                     ,  .mm-             e=womm      .e-e          .. *             *.e                 e-gmww wes
g. , eg wp.

op.-M. *GN*.h 6 e. MW.4=- *N'hh*ehd.N 4 ==.m== e . -e m *. 6- --e

                                                          ,,ee      ,una                           ,ame.-        elmmmhe m

h

T

  %-We                 _ m e @ .it_                      .                  *' _ . *               '

i D-

                                                                                                                                                                             "*- Y N6"                                           b h*6             -               8'D
  • __

_ .. - . . . 01 kA10M . . . . _ _ _ . ___MO - T __. 1_~_. X . % ARedfU-Efq._j._Ma._i d l56_1 ZET.~1%.QZZ.JElf~~~~u.eetz_4F6i_@~.dLK "6 _ MW w

 & .6 6
                                                                                                                                                                                                                    .                                                      -                              m w*.*-     6                                                                                         h" p        .mumum  6W          .Me6 ma
                                                                                                                     .                                     +.e   se                                             _+                  e8                    __

ee-m. m.m.4.m N,mm.e .%

                                                                                                                                                                                                                                                                                       . e umi n               -.

h

                                                                                 .              m                .6m                                           N v-       h6 eW                 4 hm                                                   ehe   MN                  8'.                                                    6      g                             n ee. e .

m -. _a_ . DEES .M w N l - . . . - - . . _ . - - . - . M

                           --.e             -hWh                                                                               .6*
  - _ Z.T. __EE c Ah_(we                                                                                                                                                                  . d h .. A . A _ w i l -~
                                                                                                                                          . r _. ..                                          . . . . . _ - . . _ _ . . . . _ _ _                                                          . .
         .. _                                                             _A.ctA . . .. .                                          . _.               _._.._._m_                                   . . . _ _ _ _ . . _ . . _ _ . . . . . _ . _ . . . . . . .
                                                                                                                                                                                                                                            .                I                    -             .

A

                            '                                                                                         bA               A u)         (,
           +                                   xsr w cac                                                            a                  m td v& M                                            51  M kk h jp a                      JL92&c.           5o     hh.                                                  '

w%vL sevakz'n 9 L 4%g. rQ udte Aypuwa.- pA . o

  • A _. .
a. p2_ n a e .... p p .

4 [ed d. M IiddL..La_a U tud il

                                                                                                         ~
                  ~
                                                             % . mt u x. X st a e,e , d a A 4
    . L~i_T
                                 ~
                                ..i              'ridL i_..TcAb K k K .ad Q E ET ~~~~E~:,C,C:s E E .gu;E C ~M d TRT1X E4 K l

t E15w:^eE.WisGnC4CWuXKLh I .

                                                  $2               \ .W          %.                   . . .         . . . . . ~

e e e .m-s e w 6e w A Z .LaK11 4 1~cW 4 1E C

               ~ ~ ~
                              ~

i Wn ~~~ @ ak~~q L ikE~4

                                                            &          %&.s                ca u     p r % ; n                          cQ sq dm m.~ 75 x .A                                             =+ 1 L       mta ba re4 edgwa Jtc+m,           A      cwta L----_--                               . _ _ _ _ _ _ _

4 g .

1. ) k iS4 /y d M 1. 4 t C. M
                                                                                                                                                                                                                                                                               ..                                                                                           k yr4                                                         . -. . .. .

AstulD. g .o&k..t1#w..p.E 9/4twk .

                                                                                                                                                                                                                                                                                                                                                                                         .W. m     . .                 .
   <                        L
                                            ^~ q~: L}^.}. % g : Q9.gcas n                                                                              gna,e

_.e. _.p ot(W% . . . _. e .._ . . ... . _ e._ 4 .e . ._ . . 4

                                                                                                                                                                           .                                         . _ . ._._ _.__ _.__                                                 . . __ _ _ _            _e.                     .                          _ _ . . . . __                               _ _ _ _

ewe em se umanm enee e ee esea we m - e _p em.-ep ,geo g e e.m p4 e e q me m eeeg 4-m= mw a + - -

                                                                                                                                ....*,-e
m. e we w a - .
                                                        .. ..                                                         .e,                                                            , .                                  .. ..                                    .             - - .                    . . 4                               . ...                                          .           ..

eee-- @ _ m- egy- e m 9 .-re e aus6 6- em -e em e == w e hee e e h.e - =6 6 4 h--

                                                                                    . .. ....                                        .                .                               ...                                          ....                        ...                             - .-.                               -e                              . .                            -                             e e.a        -.m    .e   ,m.                          w e4                                                          e e,e         ,                                      ,,
        . ghe    e                    a       ei                                       m   me.      -e    e 9 e              e                      e                                      en              a          m             9         . W       6*                    e        -    em             --N                     e     ee                    e
                                             -ew $           . e                     mh m           e.e-ewee                                            6
                                                                                                                                             .a                       -.mD                                   @m-      --e        e     e        e . We                                     # 6       8m                   *
  • h up= eme e. e e6 4 .-see.i .ee +=8 Ge me .gume ogs hM e6me e *e emi eam p a een m -m e . e =g =g em e e O' e e ee M . .e e. eme .m .M ma e em-mw- e-ame i@ e4 -

man mmes e = 4e 4 - p6eeup e $a agae a as,e m=*=.e se < m w e e ,eh ump e-+ Wew m 4e mee D&& -=me e- *** e e- S6-e O+ =6 . > m e ee m e e e e m- . .==m m

m. mm. p l . _. . . .e . - _. . .
      .                                                       _e               .._                                 .

eum e e e

                                                              ,,,                           . p                                  .e          e i

e- + =. +w=% we . m me. g. eg- me m - ems * - . - - . m+*=en-e- m ====m.e.--.- e,,

                          -.em-                 ee-      = e me e                   e.e-=            a    se - -                       ee m *
  • ume*mhe mo m
                                                        . .                                                                                                                        6                                               . _ . _ -. _ _ _                                                                                                        6-                                                  e      . . .. ._._.
 ,,4mwa,,--MM                                           W      --
                                                                                          *M&
                                                                                                                                                          -.g                                                       -
                                                                                                                                                                                                                                                                                                                                                                                                           -q ehe6                                         em m.em4 memaem q w eg                                 eoe         eeg,            o     w            .e. ee                   esem        we = w                e ee          eee         e    eem e                 .m e a       y.m e. e ,e 66      -We              *6                 6*                em@ m wa                            ee-eh-e
                    .       e_....*                          e.        ._e_           ...e_             l.h                                                                                    .                    e                                                                                                                                                    $
                                                                                                                                                             . mee - --                                                                                                                           _. _                                               _ _ .                                                          ___m.e                  -                    ._e__
     .._ .             .e._         _e_                     _e.__                          . -.-

G g  %

         ._ _ ___ e                                   _e___                               ._[                                   9                   L                                LA -                                                                                         ..                                                                    _                                              __                                                  .___._

e_ _- __ me_._. _._. _. ____

     . _            ____.__e.__.                                              ____e_

em W6 Me. emD e ehe em me-NM 9e-6ew eem e .m ap eepi mega m we e h h &= 66**. --N4M6 N e6 M uno NM

       -sM e e Og e *                     =6m e.._                                                                                 me                                                                                                                      m
 .-w           %-a                 m m eeaum e                                                             e-4 e.ew..em_eae. e                                                                                 oee eme e 6e-me                    *                                *'m    6*e ee                     e      W         ge --                                  6 6 de @

OOM M M e mww* MO

          ._.,._e._.                         ..       e__.                                                -.e._                     .
                                                                                                                                                                                                                                                                                                                                                                                                ====                                                   , -
  - -          .-e      e.-.           ..=.-                          +.eme            N.         e-a.

__ e =>

       ==.e.emmem+e.-

_W mgg.g.ye+@e d*N

                                                                                                                                                                                                                                                                                                                                                                                   +N--                                                6*
                                                           @      mens.6 se                e se46                                M        MM                                                     M                          h*6
                                                                                                                                                                                                                                                                                                                                                          - 6                   m    N6w New                                                            eM_==um e-               e en a                        == 6 se e               de> enm -- awe m                                        @m    e*6*e             epusm . 96 @h4 N We                          e.pa' e eme                      --

OheNe em-=e6NN6M6

                  +ew         =e66ew
  • ep6 a eMhe64m e e*hea.

em.6 e @wM e Osw m-6 -@ mamO m h w-ee we 6 mmm66 _w ee@ N6NSN0N N M6* *O

  • em.me .egh.e Me **

M+ N _

       **'-         me-etNeNe S S'868'*M*               **h        *
     -e6.ph m                                                                          e
  * *                      =m       a       e e                                       ee        me*                                                    mmM-                                       mmea M6 es-                             N               mm                                 a. Op6              ae4     em.m m . m hh                                      we $ -emmewwe MMM "G#&mW6
                                                               .                      . -         .e-           .-__.                                                         _ _. . --.. . . _ .                                                                       .. e    ..                .            e         ._. ... ..                               ...e-                . _._._ -.                                                                .
                                                                                                                                                                                                                                                                                                                                                                                                                                                                         *O amme, eme e          p-se     -                   em--eh$6                       mye 6-                 h       e     =N-w                       eum                e     e ..       .e         ,eo m                  _,        emym.mgegn                        mm e                        m gagee e                  eeensem                      - *             *'*E*
                                           -am,       w .           e
                                                                                                                                                                                                                                                                                                                                                             -m.eog6-                                       Ne              m et     D'*         N
  • _ =e e ,we e O , w+- e e @ 6 w-w v. e- me - .+eeme emew 66 h
  • ewNe-m.-. m e w=-*m- e6e w agmy e -- ,e g., e w me ,e . em +--
                                                      -             e                                                 ,p,                                                         e.m*r              weemn.**                                t- he     *   @

e

           ~

QUESTION 421.51 You describe the performance monitoring system in Section 7.7.1.5 of your FSAR. { Provide the following additional information in this section: (7.7.1) a) Identify all safety-related parameters which will be monitored with the per-formance monitoring system during initial operation. b) For each safety parameter identified above, provide a concise description of how its associated circuitry connects (either directly or indirectly by means of isolation devices) with the performance monitoring system circuitry. Where appropriate, supplement this description with detailed electrical schematics. c) Describe your proposed design provisions to prevent failures of the perform-ance monitoring system degrading safety related systems. d) Provide the above information for the startup " transient monitoring system," if provided and distinct from the performance monitoring system.

RESPONSE

421.51 a) The following parameters in safety-related systems will be monitored during ( initial operation:

     ,                      SYSTEM                                            PARAMETERS Nuclear Boiler / Nuclear Steam        Vessel Wide Range Level Supply Shutoff System (NBS)            ADS /SRV Position ADS /SRV Initiation Signal MSIV's Position MSIV's isolation Trip Signal

, Vessel High/ Low Level Alarm RHR/ ADS /LPCS/HPCS Low Water Level Initiation Signals RHR/ ADS /LPCS/HPCS High Drywell Pressure initiation Signals Neutrnn Monitoring System APRM Output (NMS) APRM Heat Flux LPRM Output Recire. System Flow

421.51 (Ccntinued) SYSTEM PARAMETERS f Reactor Protection System (RPS) Reactor Manual Scram Reactor Scram Trip System Residual Heat Removal System RHR System Flow (A,B,C) (RHR) RHR Heat Exchanger Inlet Temp (A,B) l RHR Heat Exchanger Outlet Temp (A,B) RHR System Pressure Low Pressure Core Spray LPCS System Pressure System (LPCS) LPCS System Flow High Pressure Core Spray HPCS System Pressure System (HPCS) HPCS System Flow b) Isolation will be accomplished by means of optical isolators.The isolation.will be accomplished downstream of signal conditioning and analog-to-digital conversion. Figure 1 demonstrates a typical signal flow from a safety-system parameter to the non. safety PMS. The optical isolators shall be qualified in accordance with Regulatory Guides 1.75 and 1.89. The isolators provide a means for preventing a fault in the non-divisional wiring from affecting the safety-system circuitry. Figure 2 exhibits the power and signal connnections to the isolators. (-

              .                c). To maintain the PMS as a highly reliable system, I s normal power will be supplied from an uninterruptible power source (UPS). In addition, interfaces to safety system will be by means of isolation devices. Failures in the PMS will not affect safety system operation other than possible erroneous operator information.

d) Based upon current transient monitoring requirements, the following nSty systems will have interface with the safety transient monitoring system: e Neutron Monitoring System Reactor Protection System Nuclear Boiler System Nuclear Steam Supply Shutoff System Diesel Generator System 4.16 kV Power Distribution System l High Pressure Core Spray System { Residual Heat Removal System L

  • i - _ - . .-. - _ - _ _ -

1 421.51 (Cantinu:d) A concise description of how the associated circuitry merges or connects with ( the start-up transient monitoring system is inappropriate at this time because system design is not yet specified. Response at a later date, after system design, will be necessary to properly respond to this question. C. F. Braun and Company will provide the system design. ( e

1, - E X T R G E U D O UN E L T S S AI B G T AUP ER I A N N C CE A F L l OT C E R Y

                                             @             AI                                          RUM PPE MT T L                             O            9                              OS E A                                                 "                       CYS N

A O S I S R I A VI L D - C N U O N N ,

                             ~         =

2 l F LO

                                             @                                         AT CA I

T L O P OI S

                                                                                         !ll g i l ll l l l     l 1 l                i l
                                                                                                        )

L R A E N T N E O MI T lV E O I S I V A C RC I R E OA D GT F - AT OAR N O P O LR ET N YR AA N / TP NP I L AM T A

    .                 E F N                                                                     OI         N AI O                                                                      CN U

O I S T SI L A V AL I D C OS I ( P I L E Y R T N T OI A GTN P OAU LR P AAI NPR AMT O l nl r _ l nl , N O

                                                                    ~         b                                 T N I                                                                                N E

O T ' T I A ~ MT I _ NA I R T AT

                                                                                                       ~         TE NI         _

Y NN l

                                                                    ]

I [ l OE S CP C P T - LE N _ H LR R eC EK HEU

T
                                                                            )

MC

    -                          E               GWSS I

M m (- UA L HY R E X RR P R T M DP S N A I X E ll ,lI

4 FIGudE 2 , COMPUTER OPTICAL ISOLATOR Vj (+12v) COMPUTER POWER SUPPLY (+28v) I LOGIC LEVEL OUTPUT SIGNAL INPUT (+28v) V jRETURN V I

                                                            ~

421.53 In Section 11.5.2.1.2 of your FSAR, you indicate that if one channel in both the A and 8 trip logic is downscale in the reactor containment heating, ventilation and air-conditioning (HVAC) radiation monitoring system, system isolation is not possible. Your design is such that any one downscale trip sounds an alarm in the control room. Discuss i the details of your design which are provided to preclude downscale trips in one channel in each logic from occurring simultaneously. Discuss the required actions, either automatic or by the operator, including the procedures to be followed by the operator if a channel in one or both logics is downscale. Indicate whether the details ~ provided in this discussion are applicable to the other radiation monitoring systems identified in Section 11.5.2.1 of your FSAR. The logic embodied in the reactor. containment heating, ventilation and air conditioning (HVAC) radiation monitoring system (see figure 7A.6-4K) is such that either a downscale trip or an upscale per channel will be sufficient to provide one half of the required signal for the interlock. Figure 7.6-10C Note 7 also indicates that two-out-of-two high high/inop or downscale trips (in either A and D or B and C) will provide an interlock signal. The procedure to be followed in case of a downscale trip will be provided in the technical specifications chapter of the Safety Analysis Report. Although the exact .- l l procedure will need to be reviewed by the applicant, in general, the following is typical: With the requirements l for the minimum number of Operable channels not satisfied l for one trip system, place the inoperable channel.in the , tripped condition within one hour or establish Secondary l Containment Integrity with the standby gas treatment system operating within one hour. With the requirements for the minimum number of Operable channels not satisfied for both trip systems, establish Secondary Containment Integrity with the standby gas treatment system operating j within one hour.

  • i The details provided above are not directly applicable to the other radiation monitirong systems (i.e., containment space - refueling mode, fuel building ventilation exhaust, auxiliary building exhaust, standby gas treatment, shield
!           annulus HVAC, and control building HVAC) in Section 11.5.2.1 l            because these systems are configured with a one-out-of-two
                                                          ~

l trip logic. l l

s 421.54 QUESTION ( Provide a discussion of the process computer system in Chapter 7 of your FSAR. 421.54 RESPONSE The Performance Monitoring System (formally called the Process Computer System) is discussed in Subsection 7.7.1.5 and 7.7.2.5. As indicated in 7.7.2.5. A, the PMS is not required to initiate or control any engineered safeguard or safety-related system. ( l

 !}}