ML19326C513

From kanterella
Revision as of 23:22, 31 January 2020 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Submits Fire Protection Info as Followup to Util 780615 Ltr & in Response to Discussions W/Nrc
ML19326C513
Person / Time
Site: Arkansas Nuclear  Entergy icon.png
Issue date: 06/22/1978
From: David Williams
ARKANSAS POWER & LIGHT CO.
To: Stolz J
Office of Nuclear Reactor Regulation
References
1-068-15, 1-68-15, NUDOCS 8004230631
Download: ML19326C513 (7)


Text

[ #W '/ff REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS) ,

DISTRIBUTION FOR INCOMING MATERIAL a : -91

  • r 68 REC: STOLZ J F ORG: WILLIAMS D H DOCDATE: 06/29/78 j NRC AR PWR & LIGHT DATE RCVD: 07/10/7@

DOCTYPE: LETTER NOTARIZED: NO COPIES RECEIVED SUDJECT: LTR 3 ENCL 40 FURNISHING INFO AS FOLLOW UP TO APPLICANT"S LTR OF 06/15/73, AND IN RESPONSE

/ TO COMMITMENTS MADE IN SUBSEQUENT CONVERSATIONS WITH NRC STAFF RE SUBJECT FACILITY"S FIRE PROTECTION. W/ATT INITIAL & REQUALIFICATION FIRE TRAINING FOR FBST.

PLANT NAME: ARKANSAS - UNIT 1 REVIEWER INITIAL: XJM ARKANSAS 1 - UNIT ? DISTRIBUTER INITIAL: q 0000************* DISTRIBUTION OF THIS MATER: * :s AS ICLLOWS ******************

FIRE PROTECTION (PRIOR TO ISSUANCE OF OL).

(DISTRIEUTION CODE BOO 2)

FOR ACTION: BR CHIEF orbit 4 BC**W/ ENCL PROJ MGR VISSING**W/ ENCL LIC A9c7 N H4 LAu LTR ONLY INTERNAL: REG FILE **W/E NRC PDR*rW/ ENCL etu**Lau out.: I & E**W/3 ENCL DIRECTOR DPM**LTR ONLY DE YOUNG **LTR ONLY VASSALLO**LTR ONLY DIRECTOR D?S**W/ ENCL AD FOR PLANT SYSTEMS **W/ ENCL AUXILIARY SYS BR**W/2 ENCL I & C SYSTEMS BR**LTR ONLY AD FOR QA & O**LTR ONLY OAB**W/ ENCL R. MURANAKA**LTR ONLY ,

, HANAUER**W/ ENCL '

EXTERNAL: LPDR'S STC L L Wl6 #

RUSSELLVILLE, AR**W/ ENCL R @4Rrt AJ W/6 M TIC **W/ ENCL NSIC**W/ ENCL HVLrod W/G d C- L POWER SYS BR**W/ ENCL l PLANT SYSTEMS BR**W/2 ENCL l AD FOR SYS & PROJ**LTR ONLY DIRECTOR DOR **LTR ONLY OPERATOR LIC BR**W/ ENCL ACRS CAT B**W/16 ENCL I

l l

l DISTRIBUTION: LTR 46 ENCL 36 CONTROL NBR: Je l o 1 mO2'J SIZE: 4P+2P

/Nf coce******************************* THE END ********************************d 1

8oo4230 @ l u

, (

- a ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 LITTLE ROCK. ARKANSAS 72203 (501) 371-4000 June 29, 1978 e.-

. S,'

~

1-068-15 5.?

2-068-41 3 '? '

d Director of Nuclear Reactor Regulation .5 ATTN: Mr. J. F. Stolz, Chief '.y 2,8 3 ..

Light Water Reactor Branch #1 .sg.- 3 g

Mr. Robert W. Reid, v,; -e e Operating Reactors Branch #4 's, .'

U. S. Nuclear Regulatory Commission Yy#u

~

Washington, D.C. 20555

Subject:

Arkansas Nuclear One-Unit 16 2 b.k 1

Docket No. 50-368 50-313

Fire Protection (File: 1510 2040 2-1510 2-2040)

Gentlemen: /

As a follow up to our letter of June 15, 1978, and in response to commitments made in subsequent conversations with the Staff, the following infonnation is provided. Item numbers (where applicable) refer to the May 24, 1978, meeting agenda.

Item 5b Manual Hose Rael in zone 2055JJ Response ANO-2 1

We will provide manual hose capability in zone 2055JJ. This modification '

will be completed by the end of the first refueling outage. We consider this item resolved. I Item 7b - Emergency Fire Team Training Response ANO-1 and 2 l 1

The Fire Protection Plan will be amended to state that the Eme gency Fire Team will receive the same training as the Fire Brigade. We consider this item resolved.

Item 7c - Fire Brigade Size. l 1

l Response (ANO-1 and 2) l l This item was previously addressed by our letter of June 13, 1978. As agreed in a subsequent conversation between Mr. William Cavanaugh and Mr. Victor 9-Stello, we amend that submittal in part as follows. l hD MEMDER MIDOLE SOUTH UTIUTIES SYSTEM 49' 17' I :,';y,g

(

. (

2-068-15 2-068-41 Mr. J. F. Stolz & June 29, 1978 Mr. Robert W. Reid

)

Item 12 - (Practice Fires) The Fire Brigade Support Team (FBST) will be initially trained the same as required of the Fire Brigade (FB) as indicated on Attachment I page 1~(which supersedes Attachment-TI to Vur --

June 13, 1978, letter). Requalification training will be as shown on Attachment I page 2. We understand this is acceptable to the Staff and consider this item resolved. (This comitment is made without prejudice to potential future rulemaking proceedings on this' topic).

Item 7d - Storage of combustibles in safety related zones.

Response (ANO-1 and 2)

As stated in the Fire Protection Plan, no combustibles will be stored in fire zones with redundant safe shutdown circuitry and/or equipment. In addition, no combustibles will be stored in safety related zones unless that zone is protected by a sprinkler system. We understand this is acceptable to the Staff and consider this item resolved.

Item 8a - Testing of ANO-1 fire stops.

Response (ANO-1)

Justification of the adequacy of the ANO-1 fire stops will be provided in accordance with our letter of June 15, 1978. In addition, if any of the fire stops fail to meet acceptable criteria, they will. be upgraded to that criteria. We understand this is acceptable to the Staff and consider this item resolved.

Item 8b - Associated Circuitry. l Response (ANO-1)

The results of our an'alysis of associated circuitry will be provided in accordance with our June 15, 1978, letter. Should that analysis reveal a problem with associated circuitry affecting safe shutdown equipment, adequate electrical separation will be provided. We understand this is acceptable to the Staff and consider this item resolved.

Item 8g - (PF.20) RCP oil collection systein i

Response (AN0-1 and 2)

As comitted in our June. 15, 1978, letter, we will provide details of our RCP oil collection system. If, at that time, it is determined that our oil collection system is inadequate to meet your position (PF.20) we will modify as practical the system (s) to comply. We understand this is accep-table to the Staff and consider this item resolved. ,

l l

l

(

5 2-068-15 2-068-41 Mr. J. F. Stolz & June 29, 1978 .

Mr. Robert W. Reid Item 8h - (PF.21) Smoke Detector _s,_in Safety Related Zones

. Response (ANO-1 and 2)

As agreed in a June 23, 1978, telecon between Mr. William Cavanaugh and Mr. Victor Stello, we will provide smoke detectors, which alarm in the Control Room, in the following safety related fires zones. With these modifications, all safety related fire zones will be protected with smoke detectors with the exception of zones 1-E, 95-0, and 2155-A. These three (3) zones contain no combustibles and only one (1) safety related division. Three additional zones which were mentioned in the June 23, 1978, Cavanaugh/Stello telecon are provided with detectors due to other commitments and are not included in the list below. These six added to the 43 below make up the 49 zones mentioned in the Cavanaugh/Stello telecon. We under-stand this to be acceptable to the Staff and consider this item resolved.

This modification will be complete by the end of the next refueling outages.

ANO-1 ANO-2 159-B 2156-4 167-B 2114-I 144-D 2115-I 2-E 2136-I 128-E 2107-N 68-P 2106-R 104-S 2109-U 73-W 2068-DD 76-W 2073-DD 20-Y 2084-DD 34-Y 2076-HH 40-Y 2081-HH 46-Y 2024-JJ 47-Y 2025-JJ 53-Y 2040-JJ 14-EE 2055-JJ 79-U 2223-KK 77-V 2006-LL AN0-1 Intake 2007-LL 2010-LL 2011-LL 2014-LL 2200-MM ANO-2 Intake

(

t 2-068-15 2-068-41 Mr. J. F. Stolz & June 29, 1978 .

Mr. Robert W. Reid Item 9.la - Smoke Dectectors in Control Room Cabinets

. Response (ANO-1 and 2)

Self contained UL or FM listed smoke detectors will be provided in each Control Room cabinet containing safe shutdown circuitry. This modifi-cation will be completed by the end of the next ' refueling outages. We understand this is acceptable to the Staff and consider this item re-solved.

Item 9.2b - ANO-2 Cable Spreading Room Sprinkler System Response (ANO-2)

We will further attempt to evaluate the existicq sprinkler system to NFPA-15 1977. If our evaluation reveals we do not meet the new standard, we will upgrade the sprinkler system as practical to meet the standard.

We understat d this is acceptable to the Staff and consider this item resolved. Tuis modification (if required) will be completed by the end of the first refueling outage.

We wish to reiterate our concern that the Staff has not fully reviewed our Fire Hazard Analysis nor utilized it as a basis for approval of fire protection provisions at ANO-1 or ANO-2. As a result, we feel we have had to make several commitments beyond those we feel necessary based on our Fire Hazard Analysis.

Mr. Reid has verbally requested a clarification of our statement of in-tentions regarding the maintaining of the Fire Hazards Analysis validity and consideration of it as a basis for comitments. This statement was made in our June 13, 1978, letter. Any portions of the Fire Hazard Analysis which is utilized as a basis for approval of fire protection pro-visions at ANO-1 and/or AN0-2 will be maintained valid and considered a basis for comitments. Currently no portions of the Fire Hazards Analysis fall within that category. If that situation changes we will take -action in accordance with the above commitments.

It is our understanding that these commitments are sufficient to resolve all remaining open items on Fire Protection and will provide you with adequate infonnation to support your SER for ANO-2.

Very ruly yours, l { W1 A Daniel H. Williams Manager, Licensing DHW/JTE/ew Attachments

(

4 ATTACHMENT I Initial Fire Training for FBST .

Item Degree of Training

1. Hose Reels
  • Same as required for FB
2. Portable Extinguishers
  • Same as required for FB
3. Air Masks ** Same as required for FB
4. Communication *** Same as required for FB
5. Lights None
6. Other Equipment *

(Clothing,etc.) Same as required for FB

7. Portable Smoke Removal Equipment ** Less than required for FB
8. Installed Plant Fire Protection Systems ** Less than required for FB
9. Fire Fighting Strategies
  • Less than required for FB
10. Electrical and other hazards * - Same as required for FB
11. Rescue ** Same as required for FB
12. Practice Fires Same as required for FB
13. Team Drills Same as required for FB

(*) Covered by Videotape Fire Protection Training Program

(**) Covered by supplemental classroom training

(***) Covered by general plant indoctrination.

Page I i

(

(

ATTACHMENT I Requalification Fire Training for FBST Item Degree of Training

1. ' Hose Reels
  • Same as required for FB
2. Portable Extinguishers
  • Same as required for FB
3. Air Masks ** Same as required for FB
4. Connunica ti on*** Same as required for FB
5. Lights None
6. Other Equipment *

(Clothing,etc.) Same as required for FB

7. Portable Smoke Removal Equipment ** Less than required for FB
8. Installed Plant Fire Protection Systems ** Less than required for FB
9. Fire Fighting Strategies
  • Less than required for FB
10. Electrical and other hazards
  • Same as required for FB
11. Rescue ** Same as required for FB
12. Practice Fires None
13. Team Drills Same as required for FB

(*) Covered by Videotape Fire Protection Training Program

(**) Covered by supplemental classroom training

(***) Covered by general plant indoctrination.

1 i

i l

Page II e L