Forwards LER 81-009/03L-0.Detailed Analysis Encl
ML20009G464
Person / Time
Site: Oconee Duke Energy icon.png
Issue date: 07/22/1981
From: Parker W
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20009G465 List:
References
NUDOCS 8108040288
Download: ML20009G464 (2)


Text

. . - _ _ _ _ _ _ _ _ - . . . - - - - - - _ _ _ _ _ _ _ . _. . . _ . - ..

x OFFICIAL COIT DUKE POWER COMPANY Powra Dunwswo 402 SocTu Cnuwen StazzT. CitAnwrTE N. C. 2aa4a w a LLI AM O. PA R M E R, J R.

Tgggn=ONt; Anta 704

/CF Pets orm?

July 22, 1981 373 4o.3 sec.- P.oouce.o.

Mr. James P. O'Reilly, Director ,f U. S. Nuclear Regulatory Commission / \\ ' e4 '

Region II 101 Marietta Street, Suite 3100 N(,( l h

U Atlanta, Georgia 30303 2,7 ' ,

NJ,pov

'Q f > O ,

Re: Oconee Nuclear Station 9 9.5 "$$'5 s

/

Docket No. 50-269 W-q -1 s nu \

Dear Mr. O'Reilly:

t Please find attached Reportable Occurrence Report R0-269/81-9 . This report is submitted purauant to Oconee Nuclear Station Technical Specification 6.6.2.1.b(2) . which concerns operation in a degraded mode permitted by a limiting condition for operation, and describes an incident which is considered to be of no significance with respect to its effect on the health and safety of the public.

I Ve truly yours,

( b .r <_. c t.0, /c '

'k'illiam O. Parker, Jr. Q JLJ:eck Attachment cc: Director Mr. Bill Lavallee l Office of Management & Prograut Analysis Nuclear Safety Analysis Center l

U. S. Nuclear Regulatory Commission P. O. Box 10412 Washington, D. C. 20555 Palo Alto, California 94303 i

r l

h S

I l

iI s

8108040288 810722 PDRADOCK05000g S

l 6

-._ - _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ . _ _ . . m. , , _ , _ _ _ _ , , _ . , _ _ _ _ __ _ _

DUKE POWER COMPANY OCONEE UNIT 1 Report Number: R0-269/81- 9 Report Date: July 22, 1981 Occurrence Date: June 22, 1981 Facility: Oconee Unit 1, Seneca, South Carolina Identification of Occurrenca: Startup Transformer CT-1 Locked Out Conditions Prior to Occurrence: 90% FP Description of Occurrence: At 1322 hours0.0153 days <br />0.367 hours <br />0.00219 weeks <br />5.03021e-4 months <br /> on June 22, 1981, startup transformer CT-1 locked out for unknown reasons. This constitutes operation in a degraded mode per Technical Specification 3.7.2(a) and is thus reportable pursuant to Technical Specification 6.6.2.1.b(2).

Apparent Cause of Occurrence: The reason for this incident is not exactly known. There is speculation that a bird or some other object could have entered the broken inspection glass on the 6900 volt disconnect switch causing a V $ differential trip.

1 4

Analysis of Occurrence: During the time period that CT-1 was locked out, back-1 up power was verified available from Keowee-l. Thus, the health and safety of l the public were not affected by this incident.

1 Corrective Action: The CT-1 transformer and buss work were checked for faults, and the protective relaying was checked for malfunction prior to returning control to Operations. A more complete check will be performed on the CT-1 transformer and switchgear during the current Unit i refueling outage.

4 i

l

. - _.. - .. , , - - - - _ - _ _ , ~ . . - - - . . - , , . - . . . . . _ . _ _ . . . , . - . . . . - _ . . - . . - -