ACCELERATED DjRIBUTION DEMONSTRATION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9004060232 DOC.DATE: 90/03/14 NOTARIZED: NO DOCKET #

FACIL:50-269 Oconee Nuclear Station, Unit 1, Duke Power Co. 05000269 50-270 Oconee Nuclear Station, Unit 2, Duke Power Co. 05000270 50-287 Oconee Nuclear Station, Unit 3, Duke Power Co. 05000287 AUTH.NAME AUTHOR AFFILIATION TUCKER,H.B. Duke Power Co. R RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk) I

SUBJECT:

Forwards public version of Rev 90-01 (Vol A) to EP & Revs D 90-01 (Vol B) & 90-03 (Vol C) to EPIP manual.

DISTRIBUTION CODE: DF01D COPIES RECEIVED:LTR ENCL SIZE: ' O S TITLE: Direct Flow Distribution: 50 Docket (PDR Avail)

NOTES:

A RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL D INTERNAL: NUDOCS-ABSTRACT 1 1 E01 1 1 D EXTERNAL: LPDR 1 1 NRC PDR 1 .1 S NSIC 1 1 R

I D

S A

D D

NOTE TO ALL "RIDS" RECIPIENTS:

S PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED: LTTR 5 ENCL 5

DUKE POWER March 14, 1990 Document Control Desk U. S. Nuclear Regulatory Commission Washington, D. C. 20555

Subject:

Oconee Nuclear Station Docket Nos. 50-269, -270, -287 Emergency Plan Manual (Volume A), Rev. 90-01, Emergency Plan Implementing Procedures (Volume B), Rev. 90-01, and (Volume C), Rev. 90-03 Please find attached for your use and review a copy of Revision 90-01 (Volume A) to the Oconee Nuclear Station Emergency Plan Manual and Revision 90-01 (Volume B) and 90-03 (Volume C) to the Emergency Plan Implementing Procedure Manual. Insertion instructions are provided for each volume.

These revisions are being submitted in accordance with 10 CFR 50.54 (q) and do not decrease the effectiveness of the Emergency Plan or the Emergency Plan Implementing Procedures.

Please delete privacy material in the form of personal telephone numbers prior to placing in the Public Document Room.

By copy of this letter, two copies are being provided to NRC Region II, Atlanta, Georgia.

uly yours, Hal B. Tucker, Vice President Nuclear Production KLC:nfg Enclosures 90406C)

F:D-1R j,ui0 C-K O Fo0Ql/:

-F zi

tNR~ REG(

o UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 March 29, 1990 50-269/270/287 Oconee MEMORANDUM FOR: Chief, Document Management Branch, TIDC FROM: Director, Division of Rules and Records, ADM

SUBJECT:

REVIEW OF UTILITY EMERGENCY PLAN DOCUMENTATION The Division of Rules and Records has reviewed the attached document and has determined that it may now be made publicly available.

Donnie H. Grimsley, Director Division of Rules and Rec rds Office of Administration

Attachment:

As stated A

2.0 IMMEDIATE ACTIONS 2.1 Compare actual plant conditions to the Emergency Action Level(s) listed in Enclosure 4.1 then declare the appropriate Emergency Class as indicated.

2.2 Initiate the Emergency Response Procedure (RP) applicable to the Emergency Class as follows:

Notification of Unusual Event RP/O/B/1000/02 Alert RP/O/B/1000/03 Site Area Emergency RP/O/B/1000/04 General Emergency RP/O/B/1000/05 3.0 SUBSEQUENT ACTIONS 3.1 To escalate, de-escalate or close out the Emergency, consult the procedure indicated by the action level.

4.0 ENCLOSURES 4.1 Emergency Action Level(s) for Emergency Classes Event No. Page(s) 4.1.1 Primary Coolant Leak 1 &2 4.1.2 Fuel Integrity 3 4.1.3 Steam System Failure 4 4.1.4 High Radiation/Radiological Effluents 5 4.1.5 Loss of Shutdown Function 6 4.1.6 Loss of Power 7 4.1.7 Fires and Security Actions a 4.1.8 Spent Fuel Damage g 4.1.9 Natural Disasters and Other Hazards 10 4.1.10 Other Abnormal Plant Conditions 11 & 12 4.2 Area and Process Monitors

RP/O/B/1000/01 DUKE POWER COMPANY OCONEE NUCLEAR STATION EMERGENCY CLASSIFICATION 1.0 SYMPTOMS 1.1 NOTIFICATION OF UNUSUAL EVENT 1.1.1 Events are in process or have occurred which indicate a potential degradation of the level of safety of the plant.

1.1.2 No releases of radioactive material requiring offsite response or monitoring are expected unless further degradation of safety systems occur.

1.2 ALERT 1.2.1 Events are in process or have occurred which involve actual or potential substantial degradation of the level of safety of the plant.

1.2.2 Loss of either the pressure boundary or the cladding boundary.

1.2.3 Any releases are expected to be limited to small fractions of the EPA Protective Action Guideline exposure levels.

1.3 SITE AREA EMERGENCY 1.3.1 Events are in process or have occurred which involve actual or likely major failures of plant functions needed for protection of the public.

1.3.2 Loss of two fission product barriers.

1.3.3 Releases do not, nor are they expected to, exceed EPA Protective Action Guideline exposure levels outside the Site Boundary.

1.4 GENERAL EMERGENCY 1.4.1 Events are in process or have occurred which involve actual or imminent substantial core degradation or melting with potential for loss of containment integrity.

1.4.2 Loss of two fission product barriers and failure or imminent failure of the third barrier.

1.4.3 Releases, if made, could be expected to exceed EPA Protective Action Guideline exposure levels outside the Site Boundary.