x OFFICIAL COIT DUKE POWER COMPANY Powra Dunwswo 402 SocTu Cnuwen StazzT. CitAnwrTE N. C. 2aa4a w a LLI AM O. PA R M E R, J R.

Tgggn=ONt; Anta 704

/CF Pets orm?

sec.- P.oouce.o.

July 22, 1981 373 4o.3 Mr. James P. O'Reilly, Director

,f U. S. Nuclear Regulatory Commission

/ \\\\ '

e4 N(,(

l Region II h

U 101 Marietta Street, Suite 3100 2,7 '

Atlanta, Georgia 30303 NJ

'Q f > O

,po v

9 9.5 "$$'5

/

Re: Oconee Nuclear Station s

Docket No. 50-269 W-q nu \\

- 1 s

Dear Mr. O'Reilly:

t Please find attached Reportable Occurrence Report R0-269/81-9.

This report is submitted purauant to Oconee Nuclear Station Technical Specification 6.6.2.1.b(2). which concerns operation in a degraded mode permitted by a limiting condition for operation, and describes an incident which is considered to be of no significance with respect to its effect on the health and safety of the public.

I Ve truly yours,

( b.r <_. c t.0, /c

'k'illiam O. Parker, Jr.

Q JLJ:eck Attachment cc:

Director Mr. Bill Lavallee l

Office of Management & Prograut Analysis Nuclear Safety Analysis Center l

U. S. Nuclear Regulatory Commission P. O. Box 10412 Washington, D. C. 20555 Palo Alto, California 94303 i

r l

h S

I l

iI s

8108040288 810722 PDRADOCK05000g S

l 6

m.

DUKE POWER COMPANY OCONEE UNIT 1 Report Number:

R0-269/81-9 Report Date: July 22, 1981 Occurrence Date:

June 22, 1981 Facility: Oconee Unit 1, Seneca, South Carolina Identification of Occurrenca:

Startup Transformer CT-1 Locked Out Conditions Prior to Occurrence: 90% FP Description of Occurrence:

At 1322 hours0.0153 days <br />0.367 hours <br />0.00219 weeks <br />5.03021e-4 months <br /> on June 22, 1981, startup transformer CT-1 locked out for unknown reasons.

This constitutes operation in a degraded mode per Technical Specification 3.7.2(a) and is thus reportable pursuant to Technical Specification 6.6.2.1.b(2).

Apparent Cause of Occurrence: The reason for this incident is not exactly known.

There is speculation that a bird or some other object could have entered the broken inspection glass on the 6900 volt disconnect switch causing a V $ differential trip.

1 Analysis of Occurrence:

During the time period that CT-1 was locked out, back-4 1

up power was verified available from Keowee-l.

Thus, the health and safety of l

the public were not affected by this incident.

1

Corrective Action

The CT-1 transformer and buss work were checked for faults, and the protective relaying was checked for malfunction prior to returning control to Operations.

A more complete check will be performed on the CT-1 transformer and switchgear during the current Unit i refueling outage.