Semantic search
Jump to navigation
Jump to search
Issue date | Title | Topic | |
---|---|---|---|
ML19317G327 | 9 May 1977 | RO-77-37:on 770416,emergency Feedwater Pump Tripped on Overspeed When Using Main Steam Power.Caused by New Governor'S Overly Slow Response.Feedwater Pump Left Lined Up on Auxiliary Steam & Engineering Dept Evaluated Governor | Overspeed trip |
ML19317G337 | 9 May 1977 | RO-77-36:on 770415,chemical Addition Valve CAV-2 & Makeup Valve MUV-258 Failed to Close During Performance of SP-370. Caused by Weak Closure Spring & Corroded & Dirty Contacts. Contacts Cleaned & Spring to Be Renewed | |
ML19317G345 | 28 April 1977 | RO 77-35E:on 770405-06,fish Impingement on Intake Screens Exceeded Tech Specs Limits.Caused by Barge Traffic & Strong Northwest Winds | |
ML19319C988 | 26 July 1977 | RO 77-74E:on 770719,unmonitored Reactor Bldg Purge Caused Radioactive Release Exceeding ETS & STS Limits.Caused by Procedural Inadequacy.Operational Procedure OP-147 Revised, Ensuring Radiation Monitor Rm-A1 Operability | |
ML19319D008 | 25 July 1977 | RO 77-73E:on 770716,unplanned Radioactive Gas Released to Auxiliary Bldg During Makeup Tank Venting.Cause Undetermined & Being Investigated.Venting Ceased & Bldg Evacuated.Supply Air re-established & Ventilation Resumed When Alarm Cleared | |
ML19319D018 | 30 June 1977 | RO-77-72:on 770630,gas Chromatograph Found Calibr Using Wrong Calibr Gases.Caused by Calibr Technician Failure to Follow Surveillance Procedure for Hydrogen Gas Analyzer SP-730.Chromatograph Calibr & Restored to Svc | |
ML19319D151 | 24 January 1977 | RO 77-4:on 770101,during Cycling Demonstration of Normally Untestable valves,DHV-42 Control Switch Opened,Permitting Flow Path from RCS to Reactor Bldg Sump.Caused by Operator Negligence.Valve Closed & Caution Note Added to Procedure | |
ML19319D366 | 16 April 1977 | Confirms 770416 Notification Informing IE That Steam Driven Emergency Feedwater Pump Failed to Start on Main Feedwater Pump Loss.Primary Cooldown Rate Experienced in Excess of Tech Spec Requirements | |
ML19322A371 | 18 September 1979 | RO 79-097-01P:on 790918,reactor Power Exceeded Power Level Cutoff Limit of 92%.Nuclear Instrumentation Calibr & Reactor Power Reduced.Detailed Rept Will Follow within 14 Days | |
ML19322A518 | 19 October 1979 | Ro:On 790708,sodium Hydroxide Tank Levels Not Reported Due to Misinterpretation of Reporting Requirements.Detailed Rept Will Follow within 14 Days | |
ML19326A778 | 20 November 1975 | RO-75-01:on 751108,fuel Assembly 3A33 Fell 5 Ft During Transfer from Shipping Container to Insp Station.Caused by Sling Wire Pulling Out of Swaged Fitting.New Fuel Handling Tool W/O Slings Used Pending Completion of Sling Evaluation | |
ML19329D700 | 20 June 1977 | RO 77-52:on 770614,B&W Evaluation of RO 77-17 Indicated Possible Unreviewed Safety Question Re Moderator Dilution. Possibly Caused by Unterminated Injection of Sodium Hydroxide Tank Contents Into RCS Causing Core Criticality | |
ML19337B555 | 26 September 1980 | Special Rept 80-1:on 800915,during Mode 1 Power Operation, Meteorological Monitoring Instrumentation Channels Were Not Restored to Operability for More than 7 Days.Caused by Const Effort Which Required Relocation of Cables | |
ML19338G059 | 16 October 1980 | Special Rept 80-2:on 800923,discovered That Fire Protection, Deluge & Sprinkler Sys Test Was Not Completed in Required Surveillance Interval.Caused by Misinterpretation.Employee Appointed to Track & Schedule Required Surveillances | |
ML19340A354 | 13 July 1977 | RO-77-70E:on 770331 & 0429,monthly Seawater Samples Not Collected as Required by ETS 3.2.2.Caused by Univ of Fl Failure to Collect All Samples.Complete Sample Collection Importance Stressed to Univ | |
ML19340A404 | 18 August 1977 | RO 77-95E:on 770728-29,impingement Sampling of Fish Discontinued Due to Excessive Seagrass Load.Caused by Large Influx of Seagrass & Algae That Clogged Intake Screens & Resulted in Removal of Collection Baskets | |
ML19340A406 | 7 June 1977 | Ro:On 770606,unplanned Radioactive Gas Release Occurred, Venting Makeup Tank to Low Pressure Header in Progress.Max Instantaneous Release Rate at Profile Discharge peak6.4% of Most Restrictive Tech Spec Limit.Cause Under Investigation | |
ML19340A408 | 27 June 1977 | Ro:On 770626,unplanned Radioactive Gas Release Occurred, Venting Makeup Tank to Low Pressure Header in Progress.Max Instantaneous Release Rate at Profile Discharge Peak 8% of St Restrictive Tech Spec Limit.Cause Under Investigation | |
ML19340A412 | 18 July 1977 | Ro:On 770716,unplanned Radioactive Gas Release Occurred, Venting Makeup Tank to Low Pressure Header in Progress.Max Instantaneous Release Rate at Profile Discharge Peak 0.0063% of Most Restrictive Tech Spec.Cause Under Investigation | |
ML19340A415 | 20 July 1977 | Ro:On 770719,unmonitored Radioactive Release of 0.739 Ci Noble Gas Occurred at Rate of 559.5 Uci/Second for 22 Minutes.Reactor Bldg Pugge Discontinued Upon Discovery of Inoperative Radiation Monitor RMA1.Detailed Rept to Follow | |
ML19340A422 | 23 September 1977 | RO 77-117E:on 770909-10,fish Impingement on Intake Screens Exceeded Tech Specs Limit.Possibly Caused by Oil Barge Leaving Intake Canal During Survey | |
ML19340A429 | 21 September 1977 | RO 77-110E:from Jan-May 1977,milk Samples Not Collected or Analyzed from Sample Station C-47.Caused by Assumption That Milk Need Not Be Collected from C-47 Because Milk Was Unavailable at Critical Sample Station C-49 for Comparison | |
ML19340A436 | 21 September 1977 | RO 77-111E:on 770101-0731,environ Samples Not Analyzed Using Procedures That Provided LLDs Equal to or Less than Tech Specs Criteria.Caused by Inadequate Techniques,Procedures & Equipment to Achieve Required LLDs | |
ML19340A445 | 15 September 1977 | RO 77-108E:on 770830-31,fish Impingement on Intake Screens Exceeded Tech Specs Limit.No Cause Given | |
ML19340A446 | 26 September 1977 | RO 77-116E:on 770918,unmonitored Radioactive Release to Atmosphere Occurred.Caused by Reactor Bldg Purge Monitor RM-A1 Vacuum Pump & Monitor Alarm Indicator in Control Center Being Inoperable During 2-h & 51 Minute Purge | |
ML19340A452 | 15 September 1977 | RO 77-107E:on 770907,unplanned Radioactive Gas Release to Turbine Bldg Occurred for 12-h & 40 Minutes.Caused by Gas from Makeup Tank Leaking by Valves MUV-142 & MUV-143 to Bldg Via Vent Valve HYV-25 During Maint on Hydrogen Supply Sys | |
ML19340A459 | 9 September 1977 | RO 77-103E:on 770903,unplanned Radioactive Gas Release to Auxiliary Bldg Occurred.Caused by Concentrated Waste Storage Tanks Loop Seals Being Blown.Loop Seals re-established & Sys Mods Initiated to Prevent Future Occurrences | Loop seal |
ML19340A464 | 18 August 1977 | RO 77-96E:on 770801-02,fish Impingement on Intake Screens Exceeded Tech Specs Limit.Probably Caused by Coal & Oil Barges & Maint Dredge Entering & Exiting Intake Canal During Sampling Period | |
ML19340C134 | 30 October 1980 | RO 80-057-01P:on 801029 Reactor Bldg Exhaust Monitor RM-A1 Discovered Operating in Degraded Mode Due to Improper Detector Installation & Valve Lineup.Detailed Rept Follows within 14 Days | |
ML19340E980 | 12 January 1981 | Special Rept 80-03:on 801016,during Mode 1 Power Operation, Fuse in Channel RB2 Blew,Actuating Eecs Subsystem.Caused by Failed Relay in Engineering Safeguards Cabinet 5B.Relay Was Replaced & Functionally Tested | |
ML19350E200 | 11 June 1981 | to Special Rept 80-3:on 801016,during Normal Operation,Fuse in Channel RB2 Failed,Giving 2 Out of 3 Condition Required for Actuation of Es Channel B.Caused by Failed Relay in Safeguards Cabinet 5B.Relay Replaced | |
ML20004G105 | 12 May 1981 | Ro:On 810508,while Performing Surveillance Procedure SP-187, Auxiliary Bldg Exhaust Ventilation Sys Testing,Discovered That Three Filter Banks Had Been Inoperable Since 810505, Exceeding Tech Spec 3.7.8.1.Plant Shut Down to Hot Standby | |
ML20006D672 | 5 February 1990 | Special Rept 90-01:891228,waste Gas Decay Tank H & Oxygen Monitoring Channels Removed from Svc & Not Returned to Operational Status within 14 Days.Caused by Leakage from Fittings in Tubing.Mod Procedure Developed | |
ML20006G009 | 21 February 1990 | Special Rept 90-02:on 900122,plant Shutdown Initiated Due to Unidentified Leakage in Rcs.Dose Equivalent Iodine Exceeded Tech Spec Limit.Sampling & Analysis of RCS Continued at 4 H Intervals Until Iodine Decreased to Below Tech Spec Levels | Unidentified leakage |
ML20009F974 | 23 July 1981 | Ro:On 810722,during Power Escalation Following end-of-cycle Control Rod Withdrawal,Heat Balance Calculations Indicated That All Nuclear Instrumentations 5,6,7 & 8 Were Less Conservative by Amount Exceeding 0.8% | |
ML20011A906 | 27 October 1981 | Telecopy Message of Ro:On 811027,notification Was Received That Potential High Energy Pipe Whip &/Or Jet Impingement Could Cause Possible Loss of safety-related Sys &/Or Components.Detailed Rept Will Follow within 14 Days | |
ML20038B505 | 1 December 1981 | Ro:On 811106,during Switch from Decay Heat Removal on B Train to a Train,Approx 800 Gallons of Water from Borated Water Storage Tank Overfilled RCS & Spilled Water on Reactor Bldg Floor.Event Not Reportable Per 10CFR20.403(b)(4) | |
ML20040F836 | 2 February 1982 | Ro:On 820102,while Performing Surveillance on Power Operated Relief Valve Block Valve (RCV-11),discovered Valve Would Not Cycle to Full Closed Position.Cause Not Determined.Valve Closed Manually.Repairs Effected 820128 | |
ML20049A330 | 21 August 1980 | Ro:On 800821,during Surveillance of Circulating Water Discharge Temp,Temp at Point of Discharge Exceeded 103 F, Contrary to EIS 2.1.2.Cause Not Stated.Detailed Rept to Follow | |
ML20049A332 | 30 October 1980 | Ro:On 801023,reactor Bldg Exhaust Monitor RM-A1 Was Discovered Operating in Degraded Mode.Caused by Maint Action.Reactor Bldg Purge Terminated at Time of Discovery. Detailed Rept Will Follow within 14 Days | Time of Discovery |