ML19350E200
| ML19350E200 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 06/11/1981 |
| From: | Baynard P FLORIDA POWER CORP. |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| 3-061-03, 3-61-3, CS-81-129, RO-80-3, NUDOCS 8106170137 | |
| Download: ML19350E200 (2) | |
Text
I m ~:,.
,g[IT'N54%
- J S
Ecfk' /; Of410
$QG{
- e.ie o;3 M
June 11,1981 b
I 3-0-3-a-1 JUN 1 G 193g,,,
e.....,,o.
E s. % *j p %
/
CS-81-129 d
- 3-061 -03 h.W/Ty
/
Mr. J. P. O'Reilly, Director Docket No. 50-302 U.S. Nuclear Regulatory Commission Licensee No. DPR-72 Office of Inspection & Enforcement Special Report 80-3, Rev. 1 101 Marietta St., Suite 3100 Crystal River Unit #3 Atlanta, GA 30303 Occurrence Date:
October 16, 1980
Dear Mr. O'Reilly:
Enclosed please find Revision 1 to Special Report 80-3 which is submitted in accordance with Technical Specification 6.9.2.
Should there be any questions, please contact us.
Very truly yours, FLORIDA POWER CORPORATION (i
G Nuclear Plant Manager atsy Y. Baynard anager VAH/rc clear Support Services Attachment 5
General Office 3201 Tnirty-fourtn sneet soutn. P O Box 14042. st Petersburg. Florida 33733 813 - 866-5151 8106170 l~3]
SPECIAL REPORT Special Report No.:
80-3, Revision 1 Facility:
Crystal River Unit 3 Report Date:
June 11,1981 Occurrence Date:
October 16, 1980 Identification cf Occurrence:
Actuation of an ECCS subsystem requiring action in accordance with the action statement of Technical Specification 3 5.2.
Conditions Prior to Occurrence:
Mode 1 W wer operation (97%).
Description of Occurrence:
At 0947 during normal operation, channel 1 pres-sure module was in " test", giving a 1 of 3 condi-tion for a routine surveillance test. A fuse in channel RB2 failed, giving the 2 out of 3 condi-tion required for actuation of ES channel "B".
Makeup 1B operated for less than one minute with suction valves closed before it was shut down.
Other automatic actions were manually overridden until the ES "B" actuation condition could be cleared by taking channel 1 pressure module out of the " test" mode. The transient caused approxi-mately 250 gallons of water from the borated water storage tank to be injected into the Reactor Cool-ant System with an attendant pressure increase from 2145 to 2185 psig. The flowpath was through MUV-25 and MUV-26.
Designation of Apparent Cause:
The cause of this event is attributed to a failed relay (6373D/2) in engineering safegauards cabinet 5B. The relay was a Clarke SUK8-33-76 relay.
Analysis of Occurrence:
There was no effect upon the health or safety of the general public.
Corrective Action:
The relay was replaced and functionally tested.
s.
All nuclear operators hav9 5 +n advised of the incident, the potential for oemae to the Makeup Pump, and the required operator action. The revision to this Special Report is to provide relay model number only.
Failure Data:
The total accumulated actuation cycles on MUV-25 is nineteen (19), and on MUV-26 it is twenty (20).
. _