ML082682047

From kanterella
Revision as of 07:32, 17 April 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search

Request for Additional Information, License Amendment Request to Revise Technical Specifications in Accordance with TSTF-448, Control Room Envelope Habitability, Using Consolidated Line Item Improvement Process
ML082682047
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 09/29/2008
From: Singal B K
Plant Licensing Branch IV
To: Muench R A
Wolf Creek
Singal, Balwant, 415-3016, NRR/DORL/LPL4
References
TAC MD7791
Download: ML082682047 (5)


Text

September 29, 2008

Mr. Rick A. Muench President and Chief Executive Officer Wolf Creek Nuclear Operating Corporation Post Office Box 411 Burlington, KS 66839

SUBJECT:

WOLF CREEK GENERATING STATION - REQUEST FOR ADDITIONAL INFORMATION RELATED TO REVISION TO TECHNICAL SPECIFICATIONS REGARDING CONTROL ROOM ENVELOPE HABITABILITY IN ACCORDANCE WITH TECHNICAL SPECIFICATION TASK FORCE (TSTF) 448, REVISION 3 (TAC NO. MD7791)

Dear Mr. Muench:

By letter dated January 15, 2008 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML080240232), Wolf Creek Nuclear Operation Corporation requested an amendment to Technical Specifications (TSs) for the Wolf Creek Generating Station. The requested amendment is to revise TS requirements related to control room envelope habitability in accordance with TS Task Force TSTF-448, Revision 3, "Control Room Habitability."

The U.S. Nuclear Regulatory Commission staff has reviewed the information provided in the application and determined that additional information is needed in order to complete the evaluation. A draft copy of the request for additional information was forwarded to Ms. Diane Hooper on September 22, 2008. You are requested to provide a response within 30 days of the date of this letter.

If you have any questions, please contact me at 301-415-3016.

Sincerely,

/RA/

Balwant K. Singal, Senior Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Docket No. 50-482

Enclosure:

Request for Additional Information

cc w/encl: See next page

ML082682047

  • via e-mail dated 9/25/08 **Via e-mail dated 9/24/08 OFFICE NRR/LPL4/PM NRR/LPL4/LA NRR/SCVB/BC NRR/LPL4/BC NRR/LPL4/PM NAME BSingal JBurkhardt
  • RDennig** MMarkley BSingal DATE 9/21/08 9/25/08 9/24/08 9/29/08 9/29/08 Wolf Creek Generating Station (7/2/2008)

cc:

Jay Silberg, Esq.

Pillsbury Winthrop Shaw Pittman LLP 2300 N Street, NW Washington, DC 20037

Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125

Senior Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 311 Burlington, KS 66839

Chief Engineer, Utilities Division Kansas Corporation Commission 1500 SW Arrowhead Road Topeka, KS 66604-4027

Office of the Governor State of Kansas Topeka, KS 66612

Attorney General 120 SW 10th Avenue, 2nd Floor Topeka, KS 66612-1597

County Clerk Coffey County Courthouse 110 South 6th Street Burlington, KS 66839

Chief, Radiation and Asbestos Control Section Kansas Department of Health and Environment Bureau of Air and Radiation 1000 SW Jackson, Suite 310 Topeka, KS 66612-1366

Vice President Operations/Plant Manager Wolf Creek Nuclear Operating Corporation P.O. Box 411 Burlington, KS 66839

Supervisor, Licensing Wolf Creek Nuclear Operating Corporation P.O. Box 411 Burlington, KS 66839

U.S. Nuclear Regulatory Commission Resident Inspector's Office Callaway Plant

8201 NRC Road Steedman, MO 65077-1032

REQUEST FOR ADDITIONAL INFORMATION REVISION TO TECHNICAL SPECIFICATIONS CONTROL ROOM ENVELOPE HABITABILITY WOLF CREEK NUCLEAR OPERATING CORPORATION DOCKET NO. 50-482

By letter dated January 15, 2008 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML080240232), Wolf Creek Nuclear Operation Corporation (WCNOC) requested an amendment to the Technical Specifications (TSs) for the Wolf Creek Generating Station. The requested amendment is to revise TS requirements related to control room envelope habitability in accordance with Technical Specification Task Force (TSTF) TSTF-448, Revision 3, "Control Room Habitability." The Nuclear Regulatory Commission staff det ermined that additional information is needed in order to complete its review.

1. WCNOC letter dated January 15, 2008, Page 3 of 5 of Attachment I (the last paragraph of Section 2.2.1), states, in part, that "in TS 3.7.10, TS 5.5.18 and TS Bases 3.7.10 the phrase 'control room envelope (CRE)' is replaced with 'CRE and control building envelope (CBE) boundary' and CRE is replaced with CRE and CBE in several places."

However, in insert 5.0-21 (Page 8 of 9 of Attachment II), Sections 5.5.18.d and 5.5.18.f, "control room" is used instead of "control room envelope" or "CRE and CBE boundary".

The use of phrase "control room" is not consistent with the explanation on page 3 of 5 in Section 2.2.1 of Attachment I.

In addition, this appears inconsistent with the intent of TSTF-448, Revision 3, as indicated in the technical analysis Section on Page 9 of TSTF-448, where Bases Changes are discussed. On page 9, it is stated that "the Bases are revised to use the terms 'control room envelope (CRE)' and 'CRE boundary' instead of the ambiguous term

'control room.' The definition of 'control room' and 'control room envelope boundary' are added to the background section of the Bases."

Please clarify your intent with the use of "control room" in insert 5.0-21 on Page 8 of 9, Sections 5.5.18.d and 5.5.18.f of your submittal.

2. In accordance with TSTF-448, the title of the program represented by Section 5.5.18 should be "Control Room Envelope Habitability Program," instead of "Control Room Habitability Program," as stated by Insert for Page 5.0-21. The diffe rence is minor, however, the title in the TSTF places a more appropriate emphasis on the control room envelope. Please consider revising the title of the program to be consistent with the TSTF.
3. Section 5.5.17.e of your submittal is also inconsistent with TSTF-448, Revision 3, in that there is no discussion of CRE occupants' exposure to hazardous chemicals such as is reflected in the REQUIRED ACTION of TS 3.7.10.B.2, where there is assurance that the CRE occupants are protected from hazardous chemicals regardless of quantities stored on site-now or in the future. The NRC staff is aware of the discussion provided in Enclosure section 2.2.3 of Attachment I of the WCNOC submittal and believes that the discussion does not adequately address the intent of TSTF-448. Therefore, please consider updating Section 5.5.17.e of your submittal to address CRE occupants' exposure to hazardous chemicals consistent with the intent of TSTF-448, Revision 3, Section 5.5.18.e.