ML24239A397

From kanterella
Jump to navigation Jump to search
Rssc Wire & Cable LLC Dba Marmon - Part 21 Final Notification - 57243-EN 57243
ML24239A397
Person / Time
Site: Dresden, Davis Besse, Peach Bottom, Wolf Creek, Sequoyah, Arkansas Nuclear, Limerick, Waterford, LaSalle  Constellation icon.png
Issue date: 08/23/2024
From: Sargenski P
Marmon Industrial Energy & Infrastructure, RSCC Wire & Cable
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML24239A397 (1)


Text

Fax Address: (301) 816-5151 8/23/2024 Document Size: Including Cover Sheet - 5 Pages From: RSCC Wire & Cable, LLC (d.b.a. MarmonlEI)

Contact:

Phillip Sargenski Direct Line: 860-653-8376 08/23/2024 13:53

  1. 178 P_001/005

Fr-om:

1-1! Marmon Industrial 1111111. Energy & Infrastructure August 23, 2024 Attn: Document Control Desk U.S. Nuclear Regulatory Commission (NRC)

Washington, D.C. 2055S-0001 Fax: (301) 816-5151

Subject:

RSCC Wire & Cable LLC - Part 21 Final Notification

Dear Sir or Madam,

08/23/2024 13:54

  1. 178 P.002/005 Mal"l'YIOn hidl.lStrial hef1Y & 1rm.utructwr-e, 10 Bt,JtflE"V Par.. ltQ;:,n;t,

[;Bl,Gr;trit,p,, CT0602li F'~*~; 860-653-8300

~.a).:$b0*65-3-iUO ~

This letter to the Nuclear Regulatory Commission (NRC) is a written notification of shipments of a non-compliant material in accordance with 10 CFR 21.21(d)(4).

On July 23, 2024, RSCC Wire and Cable LLC (RSCC) discovered a reel of insulated conductor which had been segregated due to an off standard report (OSR) had shipped to customers noted in Attachment 1 to this memorandum. The reel was determined to be non-compliant due to failure of insulation tensile and elongation at break (EAB) test following air oven aging. The extent of condition is limited to a single production work order and a single part number. All non-compliant insulated conductor has been accounted for.

RSCC notified all customers that received non-compliant material, and RSCC requested return of the non-compliant material.

Root cause(s) and corrective action(s) have been identified, taken, and being implemented at this time.

If you have any questions related to this issue, the evaluation, and/or corrective action(s), please contact me at the number listed below my name.

Sincerely, Cc:

Aaron Folkening-President RSCC Wire and Cable LLC (d.b.a MarmonlEI) 11.ll Marmon Electrical IT'i A Berkshire HaH,11way Comp.i,ny

Fr-om:

08/23/2024 13:55

  1. 178 P.003/005 LU Marmon Industrial 11111. Energy & Infrastructure : Customer Exhibit RSCC (Manufacture) Part Number FS01014-002 {A82Dl46}

==

Description:==

lC 14 AWG 7/.0242" TC XLPE Firewall SIS Grey 600V Work Order: 727472 RSCC Customer Plant Customer PO Number Sales Order Number 139572 Wolf Creek Wolf Creek WCNOC-8000002251 139531 Constellation Dresden 1451762 139530 Constellation LaSalle 1451264 136622 Constellation Limerick 1405573 136475 Constellation Peach Bottom 1404513 138627 Entergy Arkansas Nuclear One 61231961 136393 Entergy Waterford 3 61094275 136346 Talen Susquehanna 708635 135564 Entergy Harbor Davis Besse 45686968 "Ill Marmon Electrical ffi A 8erki.t,,lre 1-fathl!lway Compan~

Mil"tl1Gf'I tndLJSlri.lil frtef:gy & tnftawvaw~

ro Bradl~ Pa~ Road,

[,nr Gntnby, CT060:Ui Pholtle': 860-653-8300 F>n.:860*65-3-830!

Part Number Shipment Date WSR81301304 3/19/2024 00000013741 3/18/2024 00000013741 3/18/2024 0012509502 1 9/28/2023 0012509502 1 9/25/2023 991790024 1/31/2024 143-B846163 9/28/2023 91210017 9/29/2023 0000112273006 9/28/2023 Quantity (FT) 1178 2200 2750 2000 1100 550 700 6000 3000

Fr-om:

ll! Marmon Industrial 111111. Energy & Infrastructure : Transfer of information per 10 CFR 21.21(dl(4}

08/23/2024 13:55

  1. 178 P.004/005 Man'IM)n lfidUWUI [ne..., ii infr-llnrut'IW~

1-0 Bfi'dley P;;-'i\\, ftoild.

£a,;!,G-r;Jnby, Cf06026 PtiODe-; 800*65-3-BJOO f-a:r.:860-6S3-$30!

i) Name and address of the individual or individuals informing the Commission.

Phillip Sargenski, Quality Assurance Manager RSCC Wire & Cable LLC, 20 Bradley Park Rd, East Granby, CT 06026 ii) Identification of the facility, the activity, or the basic component supplied for such facility or such activity within the United States which fails to comply or contains a defect.

RSCC Wire & Cable LLC shipped safety-related product to customers listed in Attachment 1.

(iii) Identification of the firm constructing the facility or supplying the basic component which fails to comply or contains a defect.

RSCC Wire & Cable LLC manufactured the insulated conductor.

(iv) Nature of the defect or failure to comply and the safety hazard which is created or could be created by such defect or failure to comply.

Insulated conductor is non-compliant due to failure of insulation tensile and elongation at break (EAB) test following air oven aging.

(v) The date on which the information of such defect or failure to comply was obtained.

Discovery occurred on July 23, 2024.

(vi) In the case of a basic component which contains a defect or fails to comply, the number and location of these components in use at, supplied for, being supplied for, or may be supplied for, manufactured, or being manufactured for one or more facilities or activities subject to the regulations in this part.

Customers that received non-compliant safety-related products from RSCC Wire and Cable are identified in.

"'-'Ea Marmon Electrical ii'i'i. A 8erk-sheln, M'athf!IW-lly COmpijony

Fr-om:

ll! Marmon Industrial 1111 a. Energy & Infrastructure 08/23/2024 13:56

  1. 178 P_00S/005 ftltl'l'nOrt lnduita1il fiteri-, & drifta~wr*

10 Srasdley Pa..tt ltoi!d.

[a$f G,r;i_nby, CTQ6026 Pl'.ol'le; 860 6!il*S300

~a:,,,:$00-6S!-IU0]

(vii) The corrective action which has been, is being, or will be taken; the name of the individual or organization responsible for the action; and the length of time that has been or will be taken to complete the action.

1-Implement electronic HOLD process in ERP system for work orders with applied nonconformance(s) until completion of disposition, released by Quality Engineer. Quality Engineer, ECD 8/31/2024 2-Add confirmation process at final QC Inspection/ Test that all applicable nonconformance(s) have been resolved with verification of conforming data associated with inspection and testing. QC Manager, ECD 8/31/2024 3-Add independent verification at final document review that all applicable nonconformance(s) have been resolved. QA Manager, ECD 8/31/2024 (viii) Any advice related to the defect or failure to comply about the facility, activity, or basic component that has been, is being, or will be given to purchasers or licensees.

The non-compliant insulated conductor may not be relied upon to perform its safety-function.

'J.J.'.I! Marmon Electrical ii"i. A Ehl!rksF'"lte Hathaway Comf)<}ny