TXX-4492, Deficiency Rept SDAR-179 Re Project Const & Insp Programs That Do Not Specify Criteria for Placement of Concrete Anchors in Proximity of Embedded Angles.Const Procedure CEI-20 Revised

From kanterella
Jump to navigation Jump to search
Deficiency Rept SDAR-179 Re Project Const & Insp Programs That Do Not Specify Criteria for Placement of Concrete Anchors in Proximity of Embedded Angles.Const Procedure CEI-20 Revised
ML20127D883
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 06/11/1985
From: Wells J
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To: Hunter D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
SDAR-179, TXX-4492, NUDOCS 8506240363
Download: ML20127D883 (2)


Text

r -- a e

TEMS UTILITIES GENERATING COMPANY m EY h 4T 1elWEN ' Gott helHill (BLIV E MTHE ET, L.H. hl

  • ID A LLAM. R E% AN T Statt

~

M S*

~ ~ ~

June 11, JSas TXX-4492 ) ]gQ gyg h JMi355 Mr. D.R. Hunter, Chief o "-- 3

, Reactor Project Branch 2 <

U.S. Nuclear Regulatory Commission Office of Inspection & Enforcement 611 Ryan Plaza Drive, Suite 1000 Docket Nos.: 50-445 Arlington, TX 76012 50 '.46 COMANCHEPEAKSTEkMELECTRICSTATION EMBEDDED ANGLES QA FILE: CP-85-18, SDAR-179 FILE Nd.: 10110

Dear Mr. Hunter:

i I In accordance with 10CFR50.55(e), we are submitting the erclosed written report of actions taken to correct a deficiency regardinc the project construction and inspection programs that do not specify criteria for the placement of concrete anchors in the proximity of embedded angles.

Supporting documentation is available at the CPSES site for your Inspector's ,

review.

i, +

} Very truly yours,

, / )

1 JRW:tig Attachment cc: NRC Region IV - (0 + 1 copy)

Director, Inspection & Enforcement (15, copies)

U.S. Nuclea'r Regula';ory Commission Washington,DC'205fS,,

) .

8506240363 Bbohti / '

$" ^*KO M 5 .

q{Alb + - - }4"-} ,

A ninnlON OF TEXAN E7illTERN Kl.ECTRIC COMPANY w . ., . . .

TXX-4492 6/11/85 Page 2 ATTACHMENT EMBEDDED ANGLES Description The construction procedure for the installation of concrete anchors provides specific criteria for the placement of the anchors in the proximity of embedded plates. Specifically, the anchor must be placed no closer to the edge of the plate than five (5) times the diameter of the anchor. The construction procedure is unclear, however, in the application of this criteria in the placement of concrete anchors in the proximity of embedded angles. The separation of concrete anchors is required to assure the structural integrity of adjacent shear cones. An engineering procedure to control evaluations of closer spacing is currently implemented at the jobsite.

D Evaluation by site engineering has concluded the spacing criteria is sig-nificant for embedded angles in two (2) applications. Embedded angles which frame openings for removable block walls and watertight doors induce loading into the welded studs (anchors) which must be considered for affect on adjacent concrete anchors. The lack of proper spacing between concrete anchors and embedded angles in these two (2) critical applications has resulted in indeterminate conditions. The concern is applicable to Units 1 and 2.

Safety Implications In the event the condition had remained undetected, failure of the concrete anchors or the embedded angles could result in impairment of an essential support system.

Corrective Action The construction procedure (CEI-20) which prescribes the installation process for concrete anchors will be revised to include the following:

Where embedded angles are used for framing watertight door or

-removable block wall openings, the minimum clearance from center line of Hilti anchor to the opening edge is 5" + 5 times the Hilti anchor diameter. A sketch will be included.

An inspection will be performed by site Quality Control to identify all existing applications in question. Separation violations identified in-this inspection will be documented by a nonconformance report and dispositioned after an engineering evaluation..