PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-III-85-89 Date October 18, 1985 4

This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or '$

public interest significance. The information is as initially received without veri-fication or evaluation, and is basical.y all that is known by the staff on this date.

c r6

}/A Facility: Consumers Power Co. Licensee Emergency Classification:

Palisades Nuclear Power Plant XX Notification of an Unusual Event Covert, MI 49043 Alert Site Area Emergency Docket No: 50-255 General Emergency Not Applicable

Subject:

SHUTDOWN FOR RHR VALVE REPAIR The unit was shut down on October 16, 1985, to repair a leaking Residual Heat Removal System (RHR) shutdown cooling suction isolation valve. The valve is located inside the reactor containment.

The licensee declared an Unusual Event under its emergency plan at 12:29 p.m. on 4 October 15, 1985, because unidentified leakage in the containment exceeded the Technical Sp:cification limit of 1 gallon per minute. During a containment entry, licensee personnel identified the leakage as being from the RHR isolation valve, and terminated the Unusual Event classification at 10 p.m.

The Unusual Event was subsequently reinstated at 5 a.m., October.16, 1985, as the leakage from the RHR isolation valve continued to increase, reaching a rate of about 3.6 gallons per minute. A plant shutdown was initiated at that time to repair the valve. The valve packing was replaced, but during post-maintenance testing, the motor operator for the valve failed.

The licensee is replacing the motor and expects to return the unit to service on October-19.

The Resident Inspector is monitoring the licensee's repair activities.

The State of Michigan will be notified.

Region III (Chicago) was notified of this event by the Headquarters Duty Officer on October 15, 1985. Additional information was subsequently obtained by the Resident Inspector.

This information is current as of 2 p.m., October 18, 1985.

U healv CONTACT: W. Hehl "N. Chrissotimos FTS 388-5552 FTS 388-5716 DISTRIB TION:

H. St.

  • 7 MNBB4 % Phillips9'.ll E/WS*.Q$ Willstethl6 Chairman alladino E00 NRR IE _ NMSS Comm. Roberts PA OIA RES Comm. Asselstine MPA AEOD Comm. Bernthal ELD AirRights9'MO MAIL:

Comm. Zech SP INP00  : ADM:DMB y SECY NSACT .

) D0T: Trans Only 'b j'b ACRS Applicable Resident Site CA .

J "

POR Regions AM, IIM'M , IV. Qts), V3 Licensee (CorporateOffice)4t&$

Rev. 07/06/84 0510250447 851018 PDR I4E  %

PNO-III-85-089 PDR