ML20236M152

From kanterella
Jump to navigation Jump to search
PNO-77-017:on 770201,Palisades Reported Heavy Icing of Transmission Lines & Towers from Cooling Tower Vapor Drift. Resident Inspector Communicated Matter to NRR
ML20236M152
Person / Time
Site: Palisades 
Issue date: 02/01/1977
From: Roy G, Thompson D, Warnick R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-77-017, PNO-77-17, NUDOCS 9807130317
Download: ML20236M152 (1)


Text

- _ _ _ _ - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _

l

% (' cu ]e %

f._

7 f.JJ k PRELIMINARY NOTIFICATION February 1, 1977 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-77-17 This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance.

The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

Facility: Consumers Power Company, Palisades

~ " '

Subject:

ICING OF TRANSMISSION LINES On February 1,1977, Palisades reported heavy icing of trar&smission lines and towers from cooling tower vapor drift. The licensee had in previous safety analyses considered the simultaneous loss of four reactor coolant pumps as being incredible, but based upon observed icing, no longer can support this position. The licensee is presently holding reactor. power et 60% power awaiting analysis of the loss of four reactor coolant pumps and reanalysis of the structural integrity M*E of the transmission towers.

The resident inspector has communicated this matter to NRR and is following this matter closely.

(

No press release by the licensee or NRC is planned at this time.

The State of Michigan has been notified.

I The resident inspector received notification of this situation by telephone from the Plant Manager at 10:20 a.m., February 1,1977.

Contact:

RFWarnick, IE x27261 GWRoy, IE x27261 DThompson, IE x27541 Distribution; Chairman Rowden Commissioner Kennedy S. J. Chilk, SECY Commissioner Gilinsky C. C. Kammerer, CA G. F. Murphy,, JCAE L. V. Gossick, EDO K. R. Chapman, NPSS R. G. Ryan, OSP S. H. Hana,uer, EDO E. Volgenau, OIE J. A. Harris, PA,

7 B. C. Rusche, NRR H. K. Shapar, ELD T. J. McTiernan, OIA

' /j Transmitted: PBldg H St >

MNBB 1 Luge PRELIMINARY NOTIFICATION I

'\\,,

s

  • l AA VW/(Lf tM,", t i V '=*'

Ar 9807130317 770201 ~ PDR I&E PNO-77-017 PDR t l}}