PNO-I-86-019, on 860124,diesel Generator E-2 Scavenging Air Blower Failed After 21 H Continuous Operation at Low Load. Caused by Excessive Low Load Operation,As Reported by Vendor.Blower Replaced W/Higher Tolerance Blower

From kanterella
Jump to navigation Jump to search
PNO-I-86-019:on 860124,diesel Generator E-2 Scavenging Air Blower Failed After 21 H Continuous Operation at Low Load. Caused by Excessive Low Load Operation,As Reported by Vendor.Blower Replaced W/Higher Tolerance Blower
ML20153E798
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 02/20/1986
From: Gallo R, Johnson T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
References
PNO-I-86-019, PNO-I-86-19, NUDOCS 8602250158
Download: ML20153E798 (1)


DCS No: 50277860219 Date: February 20, 1986 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-I-86-19 This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance. The information is as initially received without verification or evaluation, and is basically all that is known by the Region I staff or, this date.

Facility: Licensee Emergency Classification:

Philadelphia Electric Company Notification of Unusual Event Peach Bottom Units 2 & 3 Alert Delta, Pa Site Area Emergency ON 50-277; 50-278 _ _ General Emergency X Not Applicable

Subject:

DIESEL GENERATOR SCAVENGING AIR BLO'/ER FAILURE On February 19, 1986, the licensee informed NRC Region I of a potential 10 CFR 21 report regarding the emergency diesel generator (DG) aluminum scavenging air blower.

On January 24, 1986, the E-2 DG scavenging air blower failed after 51 hours5.902778e-4 days <br />0.0142 hours <br />8.43254e-5 weeks <br />1.94055e-5 months <br /> of continuous operation at low load (see daily report of January 27,1985). The vendce, Fairbanks Morse, reports the blower was not designed for low or no load conditions and should not be operated under those conditions in excess of a few minutes. A similar failure occurred at Duane Arnold in June 1984 and was the subject of two Fairbanks Morse service information letters which recommended annual internal tolerance checks and cautioned against no load operation. The Peach Bottom E-2 OG failed blower was replaced with a modified blower with larger internal tolerances. The licensee is continuing the evaluation of the failure.

The Commonwealth of Pennsylvania has been nntified.

CONTACT: T. Johnson R. Gallo (717) 456-7614 8-488-1234 DISTRIBUTION:

H. St. MNBB Phillips E/W Willste Mail: ADM:DMB Chairman Palladino E00 NRR IE NMSS 00T:Trans only Comm. Zech PA OIA RES Comm. Bernthal ELD AE00 Comm. Roberts Comm. Asselstine j.

ACRS Air Rights INP0-,f7 SECY SP NSAC # --

y7 CA PDR Regional Offices TMI Resident Section J:5'4 .

RI Resident Office ; 5f __

Licensee: -