ML20210H067
| ML20210H067 | |
| Person / Time | |
|---|---|
| Site: | Comanche Peak |
| Issue date: | 11/07/1986 |
| From: | Patterson A, Perrino L EVALUATION RESEARCH CORP. |
| To: | |
| Shared Package | |
| ML20210F162 | List:
|
| References | |
| QI-071-01, QI-71-1, NUDOCS 8702110375 | |
| Download: ML20210H067 (2) | |
Text
e f
Page 1 of 2 V
EVALUATION RESEARCH CORPOP.ATION COMANCHE PEAK RESPONSE TEAM QUALITY INSTRUCTION FOR ISSUE-SPECIFIC ACTION PLAN ISAP VII.c.
UNCONTROLLED COPY CHANGE NOTICE: 001 INSTRUCTION NO: QI-071 REVISION NO:
1 ISSUE DATE: -11/07/86 REINSPECTION OF LIGHTING CABLE /I-E-LITG Prepared by:
47tc Date:
/( /R Approved by: / IW
'~
Date:
/#
Issue Coordinator Approved by:
Date: /d /d
[
On-Site QA g resentative I
Arproved by:
k/
n[
Date:
/d
/4 h5 QA,7. vie.Te_Le.e.r 8702110375 870126 PDR ADOCK 05000445 PDR
t'
'l 1
(,
Changs Notice 001 QI-071 Rev. 1 Change Paragraph 5.9 Table 2 to:
TABLE 2 Number of Conductors in boxes:
MIN. MAXIMUM NUMBER OF CONDUCTORS Box Dimension, Inches CU. IN.
Trade Size or Type CAP
- 14
- 12
- 10
- 8
- 6 4 x 1 1/4 Round or Octagonal 12.5 6
5 5
4 0
4 x 1 1/2 Round or Octagonal 15.5 7
6 6
5 0
4 x 2 1/8 Round'or Octagonal 21.5 10 9
8 7
0 4 x 1 1/4 Square 18.0 9
8 7
6 0
4 x 1 1/2 Square 21.0 10 9
8 7
0 4 x 2 1/8 Square 30.3 15 13 12 10 6*
.4 11/16 x 1 1/4 Square 25.5 12 11 10 8
0 4 11/16 x 1 1/2 Square 29.5 14 13 11 9
0 4 11/16 x 2 1/8 Square 42.0 21 18 16 14 6
3 x 2 x 1 1/2 Device 7.5 3
3 3
2 0
I 3 x 2 x 2 Device 10.0 5
4 4
3 0
3 x 2 x 2 1/4 Device 10.5 5
4 4
3 0'
0 3 x 2 x 2 1/2 Device 12.5 6
5 5
4' O
3 x 2 x 2 3/4 Device 14.0 7
6 5
4 0
3 x 2 x 3 1/2 Device 18.0 9
8 7
6 0
4 x 2 1/8 x 1 1/2 Device 10.3 5
4 4
3 0
i 4.x 2 1/8 x 1 7/8 Device 13.0 6
5 5
4 0
l-4 x 2 1/8 x 2 1/8 Device 14.5 7
6 5
4 0
3 3/4 x 2 x 2 1/2 Masonry Box / gang 14.0 7
6 5
4 0
3 3/4 x 2 x 3 1/2 Masonry Box / gang 21.0 10 9
8 7
0 FS--Minimum Internal Depth 1 3/4 Single Cover / gang 13.5 6
6 5
4 0
FD--Minimum Internal Depth 2 3/8 Single Cover / gang 18.0 9
8 7
6 3
l FS--Minimum Internal Depth l
-1 3/4 Multiple Cover / gang 18.0 9
8 7
6 0
FD--Minimum Internal Depth 2 3/8 Multiple Cover / gang 24.0 12 10 9
8 4
- Not to be used as a pull box. For termination only.
O
-