~ l.
JUN' 31986 1
NUMBER mu REV. ISSUE /DAR F R.Z.1 RESPONSE TO HIGH CONTAINMENT Rev. 2 PRESSURE
(
A.
PURPOSE nis procedure provides acdons to respond to a high containment pressure.
B.
SYMPTOMS OR ENTRY CONDITIONS nis procedure is entered frorn F-0.5, CONTAINMENT Crideal Safety Funcdon Status Tree on a RED or ORANGE condition.
i i
l r
Page 1 of 3 8810250320 081007 PDR ADOCK 05000213 p
PDR i
JUN 3 1988 NUMBER TTT12 P2V. ISSUE /DATE FR.Z.1 RESPONSE TO HIGH CONTAINMENT Rev.2 PRESSURE I
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED 1
VERIFY CONTAINMENTISOLATION IE FLOW PATH b'QINECESSARY, VALVES CLOSED THEN CLOSE VALVES.
(SEE OPPOSITE PAGE) 2 CHECK IF CONTAINMENT SPRAY IS REQUIRED:
- a. Check containment pressure -
a QQIQ Step 3.
GREATER THAN 40 PSIO
- b. Check two LPSI pumps -
b, Open RII MOV 31 RUNNING (fire main to containment spray),
WTEN containment pressure dect:ases to 35 PSIO.
11EN close RH MOV 31.
- c. Open containment s xay valves Ril MOV 23 and Rfi MOV 34 WlEN containment pressure decreases to 35 PSIO.
THEN close containment sway valves RH MOV 23 and RH MOV 34 3
VERIFY CARFANs RUNNING IN PERFORM "ITIE FOLLOWTNG:
EMERGENCY MODE %Tni SERVICE WATER FLOW
- a. Place face damp contml switches ESTABLISIED in the test posinon.
- b. Manually start all available CARFANs.
- c. Verify service water flow to exh containment CARFAN cooler.
4 CLOSE MAIN STEAMLINE LOCAL 1Y CLOSE MAIN STEAMLINE TRIP VALVES NON RETTJRN VALVES.
Page 2 of 3
JUN 3 1986 5MiBER TIT U REV. ISSUE /DATE i
FR Z.1 RESPONSE TO IIIGli CONTAINh!ENT Rev.2 PRESSURE
(
STEP ACT10N/ EXPECTED RESPONSE RESPONSE NOT OBTAINED r
7 CAUTION:
AT LEAST ONE SG MUST BE MNNTAINED AVNLABLE FOR RCS COOLDOWN.
L J
5 CllECK IF FEEDWATER FLOW SHOULD BE ISOLAED TO ANY SG:
- a. Check pressures in all SGs -
- a. QQ IQ Step 6.
o ANY SG DECREASING IN AN UNCONTROLLED htANNER o
ANY SG COhtPLETELY DEPRESSURIZED
o Isolate main feedwater o
Isolate AUX feedwater 6
.'lIECK CONTAINMENT alYDROGEN CONCENTRATION:
- a. Current hydrogen concentration
- a. Otuin a PASS containment measurement AVAILABLE atmospheric sample and measure hydrogen concentration.
7 NOTIFY PLAST ENGINEERING STAFF OF IIYDROGEN CONCENTRATION IN CONTAINhtENT 8
Bell!RNIQ PROCEDURE AND STEP IN EFFECT EST) l l
Page 3 of 3