ML20204J543
Text
-..
JUN 0 31988
~
NUMBER TIT 12 REY. ISSUE /DATE E S.O.1 REACTOR TRIP RESPONSE Rev. 4
{
A.
PURPOSE nis procedure provides the necessary instructions to stablize and control the plant followin8 a reactor tnp without a safety injection.
8.
SYMPTOMS OR ENTRY CONDITIONS nis procedure is entered from E-0, REACTOR TRIP OR S AFETY INJECTION, Step 4, when Si is neither actuated nor required.
0010250173 801007 DR ADOCK 05 23 Page 1 of 14
JUN031c80 NUMBER TTILE REV. ISSUE /DATE E S - 0.1 REACTOR TRIP RESPONSE Rev.4 i
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT 03 FALNED r
7 CAUTION:
IF St ACTUATION OCCURS DURING THIS PROCEDURE, E-0, REACTOR TRIP OR SAFETYINJECTION, SHOULD BE PERFORhfED.
y J
NOTE:
o FOLDOUT PAGE SHOULD BE OPEN.
o AFTER VERIFYING THAT.A TOTAL AFW FLOW OF GREATER THAT 320 GPhi CAN BE OBTAINED AND AfAINTAINED, AFW FLOW AfA Y BE THROITLED TO LESS THAN 320 GPhi TO AfD IN AIAINTAINING RCS TEhfPERATURE.
o AUTO AUX FEEDWATER,IF ACTUATED, AfUST BE DEFEATED BEFORE SG LEVEL 2 CAN BE CONTROLLED WITH THE FEEDWATER BYPASS AOVs.
1 CilECK RCS AVERAGE E LESS TIIAN 535' F TEh1PERATURE STABLE AT ASC DECREASING, OR TRENDING TO 535' F.
InES PERFORhi TIIE FOLLOWING:
1
- a. Stop dumping steam.
b.E cooldown continues, reduce total AUX feedwater flow to 320 GPhi until wide range levelin at l least one 50 is greater than 63 7c.
T11EN control AUX fet.dwater flow to maintain SG levels.
- c. E cooldow n continues.
TiiEN close sieam dump isolation valves.51S h!OV 520 and 51S hiOV 553.
l
- d. E cmidow n continues, TiiEN close all four main steam line tnp valves.
- f. E cooldown decreases TAVG 50' F below steady state TAVG ASD LOCA is SQIin progn:ss, IUliS Emergency Borate the RCS (SEE OPPOSITE PAGE) 1 Page 2 of 14
JUN 0 31988 NUMBER EH REY. ISSUE /DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4 l
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAISTD 1
E GREAT 1?R THAN 535' F AND INCREASING, THEN PERFORM THE FOLLOWING:
- a. Dump steam to the main condenser.
E main condenser EQI available.
THEN dum p steam using one DH more or the following:
- 1. Atmos 3heric vent valve.
- 2. Terry "abine steam sup sly valves.
- 3. Hog ht steam supply va ves.
l I
4
)
i l
Ii l
l Page 3 of 14
t JUN 0 31988 NUMBER TTTU REY. ISSUE /DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4
(
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED 2
CHECK FEEDWATER STATUS:
- a. Check RCS average temperature -
- a. Continue with Step 3, LESS TilAN 545 F WHEN temperature is less thw f /,5' F.
THEN do Steps 2 b, c, d arh.
valves CLOSED control valves.
i
- c. Close all four motor operated feedline
- d. Check one main feedwater pump -
- d. Check AUTO AUX icedwater actuated.
RUNNING E b'QI actuated, IliFE perfonn the following:
- 1. Manually stan AUX feedwater pumps.
- c. Verify total AUX feedwater now -
- e. Establish total AUX feedwater flow GREATER THAN 320 GPM greater than 320 GPM:
o Open feedwater bypass AOVs to each SG.
l DR o Manually stan AUX feedwater pumps.
I THEN open FW MOV 35 to feed all SGs simultaneously.
111EN perfonn the followmg:
- 1. Stop AFW pumps
111EN QQ IQ FR II.1, RESPONSE TO LOSS OF SECONDARY HEAT SINK, Step 1.
Page 4 of 14
i JUN03138.'
NUMBER TT M REV. lSSUE/D ATE ES.O.i REACTOR TRIP RESPONSE Rev.4 i
STEP ACTION / EXPECTED RESPONSE AESPONSE NOT OBTAINED 3
VERIFY ALL COh'IROL RODS IETWO OR MORECONTROLRODS FULLY INSERTED EOI FULLY INSERTED, lifEN EMERGENCY BORATE 200 PPM FOR EACH CONTROL ROD EQI FULLY INSERTED (SEE OPPOSITE PAGE).
4 VERIFY GENERATOR OUTPUT MANUALLY OPEN GENERATOR BREAKERS,14B 3T 2 AND OUTPUT BREAKERS 14B 3T 2 14B 4T-2, OPEN AFTER AND 14B 4T 2.
52 SECOND TIME DELAY
( OUTPUT BREAKERS TRIP IMMEDIATELY ON ELECIRICAL FAULT) l Page 5 of 14
t JUN O 31988 NUMBER TTTIE REV.If"*E' * ""
ES 0,1 REACTOR TRIP RESPONSE R-4 STEP ACTION /EXPEC1ED RESPONSE RESPONSE NOT OBTAINED 5
VERIFY ALL AC BUSES ENERGIZED VERIFY EhtERGEF"! BUSES BY OFFSITE POWER ENERGIZED BY DIESEL GENERATORS THEN PERFORM THE FOLLOWING:
o Verify MCC 5 enerr!:cd.
E EQIenergized.
THEN energize MCC-5 E MCC-5 can EQIbe energized, THEN GQIQ EOP 3.150, LOSS OF MCC 5, Step 1.
o Start CARFANS a q2 ired.
o Stop all radiologic.u and chemical releases.
o Isolate steam to the Air Ejectors.
o Check RCP cooling status:
- 1. Elower bearinE temperature is less than 170 F, i
THEN perform the following:
- a. Start one CCW pump.
4
- b. Start one charging pump.
- c. Initiate RCP seal water flow.
- 2. Elower bearing temperature is greater than 170' F.
THEN perform the following:
- c. Start one CCW pump,
- d. Start one charging pump.
f, WHEN lower hearing temperature b uss than 170' F, THEN slo a n.itiate RCP seal watt! Itv.
i i
o Try to restore ottsite power I
(SEE OPPOSITE PAGE).
j Page 6 of 14
JUN 0 31986 o
NUMBER TITLE REY. lSSUE/DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4
(
STEP ACT10N/ EXPECTED RESPONSE RESPONSE NOT OBTAlhTD 6
CHECK PRZR LEVEL CONTROL:
- a. Check PRZR level-
- a. Perfonn the following:
GREATER TIIAN 11.5 %
- 1. Verify letdown orifice isolation valves closed.
- 2. Place orifice isolation valve control switches in the closed position.
- 3. Venf all PRZR heaters are off.
IE '
off.
THEN manually turn off all heaters.
- 4. Control charging flow to increase PRZR level to greater than 11.5 %.
- b. Verifyletdown IN SERVICE
- b. Manually place letdown in senice (SEE OPPOSITE PAGE)
- c. Verify charging -IN SERVICE
- c. Manually place charging in senice,
- d. Check PRZR level-
- d. Control charging and letdown flow to TRENDING TO 25 %
maintain PRZR.evel at approximately 25 %.
i I
i 1
l I
l a
i Page 7 of 14 i
'~
JUN 0 31985 NUMBER TTHE REV. ISSUE /DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4 i
(
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAISTD 7
CIIECK PRZR PRESSURE CONTROL:
- a. Check PRZR pressure -
- a. Verify Si actuation.
GREATER THAN 1700 PSIG E NQIactuated, manually actuate SI, IllEN GQIQ E 0, REACTOR TRIP OR SAFETY INJECTION, Step 5.
- b. Place spray valve control switch (es)in closed for loop (s) with stopped RCP(s)
- c. Check PRZR pressure -
- c. E pressure is less than 2000 PSIL STABLE AT QR TRENDINO LN'D decreasing, TO 2000 PSIO DiEN pe-form the following:
- 1. Venf PRZR PORV(s) closed.
E'
- closed, THEN manually close PORV(s).
E PORV(s) can b'QI be closed,
'niEN close PORY block valve (s).
- 2. Verify PRZR spray valves closed.
E b'QIclosed, DIEN manually close spray valves.
E spray valves can b'QI be closed, THEN stop RCP(s) supplying failed spray valve (s).
- 3. Verify PRZR heaters on.
E h'0I on, j
THEN manually turn on heaters.
E pressure greater than 2000 PSIG ASI! increasing THEN perform the fo!!owing:
- 1. Verify PRZR heaters off I
E h'DI off, THEN manually tum heaters off.
- 2. Control pressure with normal spray, j
E normal spray b'QIavailable Ab'D letdown is in senice, TliEN use auxiliary spray.
j I
E auxiliary spray b'QIavailable, THEN use one PORV.
f l
Page 8 of 14
JUN O 31988 NUMBER TT!1E REY. ISSUE /DATE
{
ES 0.1 REACTOR TRIP RESPONSE Rev.4
(
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED l
8 CilECK SG LEVELS:
- a. Check wide range levels -
- a. hiaintain total AUX feedwater flow I
4 GREATER THAN 63 %
peater than 320 GPhi until wide range i
.evelin at least one SG is greater than 63 %
- b. Control AUX feedwater flow to
- b. IE any SG wide range level continues maintain wide range levels between to increase, 63 % to 69 %
THEN stop Aux feedwater flow to that SG.
9 INSURE lilGH PRESSURE STEAh!
DUhtP STEAh! USING ONE DUh1P OPERATES TO htAINTAIN QR h1 ORE OF THE FOLLOWING:
1 TAVG AT535' F l
6
- a. Atmos 3heric vent valve.
I
- b. Terry "urbine steam sup aly valves.
]
- c. Hog Jet steam supply va ves.
1 10 CliECK THE STATUS OF THE FOLLOWING SYSTEhtS:
l l
J ENERGIZED LOSS OF MCC 5, Step 1.
- b. Check Semi vital buses -
- b. GQ IQ EOP 3.1-46, ENERGlZED TOTAL LOSS OF SEMI VTTAL i
l POWER, Step 1.
i i
- c. Check Control Air pressure -
3 AIR SUPPLY, Step 1.
1
- d. Check Circulating Water System -
- d. GD IQ EOP 3.123, OPERATING LOSS OF CIRCULATING WATER, t
Step 1.
I 1
- c. Check condenser vaccum -
- c. GQ IQ EOP 3.18, GREATER THAN 21.5" Hg CONtPLETE LOSS OF CONDEFSER VACCUht, Step 1.
i i
i l
I l
Page 9 of 14 i
JUN 0 31986 NUMBER 1TTIE REV. ISSUE /DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4
(
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTEt RCPs SHOULD BE RUN IN ORDER OF PRIORTY TO PROWDE NORMAL PRZR SPRAY.
11 CliECK RCP STATUS:
- a. Check RCPs -
- a. Try to start one RCP:
AT LEAST ONE RUNNING
- 1. Establish conditions for starting an RCP:
- a. Close1 Tc isolation valve.
- b. Open loo bypass valve.
- c. Start oil 1 t pump.
- d. Insure seal water and component cooling water supplied to RCP.
- e. Insure lower bearing temperature is less than 170 F.
(seal water return trip valves)
- 1. Open seal water retum MOV.
- 2. Start selected RCP.
THEN perform the following:
- a. Oxn loop Tc isolation valve.
- b. C ose loop bypass valve.
IE RCP can NQI be started, THEN perform the following:
- a. Open loop Te isolation valve,
- b. Close loop bypass valve.
- c. Verify natural circulation (SEE A1TACHMENT A).
IE natural circulation NOI verified,
'lliEN increase dumping steam.
- d. Attempt to start another RCP.
Page 10 of 14
JUN 0 31988 NUMBER 1TTLE REV. ISSUE /DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4
(
STEP ACT10N/EXPEC11ED RESPONSE RESPONSE NOT OBTAISID 12 CITECK SOURCE RANGE DEHCTORS ENERGIZED:
- a. Check intermediate range flux -
- a. Continue with step 13, LESS TIIAN 5 x 1010 Ah1PS WHEN less than 5 x 1010 Ah1PS, THEN do steps 12 b, e and d.
- b. Verify source range detectors -
- b. hianually energize source range ENERGlZED detectors.
- c. Transfer nuclear flux recorders to source range scale
- d. TranS,
>R meters to source rar,20 13 SHUTit,'
NECESSARY PLAhT F u.
T
- a. Stop one main feedwater pump
- b. Stop one condensate pump i
- c. Place standby heater drain pump in TPO
- d. Place running heater drain pump in TPO 14 h1AthTAIN STABLE PLANT CONDmONS:
o PRZR pressure - AT 2000 PSIG o PRZR level APPROXIhtATELY 25 %
o SG wide range levels -
BEDVEEN 63 % AND 69 %
o RCS awrage temperature -
BEDVEEN 533' F AND 535' F 15 DETERht!NE IF NATURAL CIRCULATION COOLDOWW IS REQUIRED:
I
- a. RCPs available
- a. GQIQ ES 0.2, NATURAL CIRCULATION I
COOLDOWN, Step 1.
l Page 11 of 14
JUN 0 31988 NUMBER TTT U REV. ISSLTJDATE E S.0.1 REACTOR TRIP RESPONSE Rev.4 i
STEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED 16 PERFORM THE FOLLOWING ACTIONS:
o Place 32012R 5 control switch in TPO o Place exciter field breaker control switch in TPO o Place voltage regulator control switch in manual o Open turbine drain valves o Stan idle RCPs as necessary to control RCS temperature:
- a. Stan RCPs one at a time by performing the following:
- 1. Close loop Tc isolation valve
- 2. Open loop bypass valve
- 3. Start oil hft pump
- 4. Insure seal water and com mnent cooling v'4ter supplied to TCP
- 5. Insure lo' ver bearing tem;<rature is less thta 170' F
- 7. Check open CH TV 240,
C i T%334.
(scal water return trip valves)
- 8. Check oyn CC TW1411
- 9. Open seal water return MOV
- 10. Stan selected RCP
- 11. Oxn loop Tc isolation valve
- 12. C ose loop bypass valve Page 12 of 14
=_.
JUN 0 31988 l
NUMBER 1TTLE REV. ISSUE /DATE ES 0.1 REACTOR TRIP RESPONSE Rev.4 STEP ACTION /EXPECAD RESTCNSE RESPONSE NOT OBTAINED NOTE:
o WHEN PLANT CONDITIONS ARE STABLE, REVIEW THE i
STATUS OF ANNUNICATORS AND SYSTEM PARAMETERS.
COMPARE OBSERVATIONS WITH EXPECTED INDICATIONS.
j IMMEDIATELY REPORT OFF NORMAL OR UNEXPLAINED CONDITIONS TO THE SHIFT SUPERVISOR.
o NOTIFY DUTY OFFICER AND FILE A PIR.
t l
l 17 GQ IQ NOP 2.14, I
RECOVERY FROM A REACTOR TRIP, STEP 1 1
I END
{
l i
1, l
i l
1 l
l l
l l
I i
I f
l i
l i
l i
1 i
l Page 13 of 14 i
JUN 0 31988 NUMBER TTHE REV. ISSUE /DATE ES.0.1 REACTOR TRIP RESPONSE
.Rev.4 i
(
ATTACIBTENT A J
'Ihe following conditions support or indicate natural circulation flow:
o RCS subcooling based on core exit thermocouples is greater than 32' F.
o SO pressures are stable or decreasing.
o RCS temperature based on core exit thermocouples and average temperature indications is stable or decreasing.
o RCS cold leg temperatur:s are at saturation temperature for SG pressures.
1 4
)
)
I i
5
)
1 i
I 1
1 I.
1 j
i 1
1 I
Page 14 of 14 i
1
_,,,,, _,