NUMBER TTILE REV. ISSUE /DATE l

\\

ES 0.0 REDIAGNOSIS Rev. I JUN 3 1988 i

A.

PURPOSE i

This procedure provides a mechanism to allow the operator to determine or confmn the most appropriate post accident recovery guideline.

B.

SYMPTOMS OR ENTRY CONDITIONS i

This procedure is entered based on operatorjudgement.

l 4

Page 1 of 3 0810250154 8G1007 PDR ADOCK 05000213 P

PDR

NUhGER TTIE REV. ISSUESATE 5

E S.0.0 REDIAGNOSIS Rev.t l

JUN 3 1986 SEP ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED 1

NOTE:

o FOIDOUT PAGE SHOULD BE OPEN.

o THIS PROCEDURE SHOULD ONLY BE USED IF St IS IN SERVICE OR IS REQUIRED.

l 1

CHECK IF ANY SG IS NOT FAULTED:

a.

Check pressures in all SGs -

a. E a controlled cooldown is in ANY STABLE OR INCREASING
progress, THEN QDIQ Step 2.

IfNDI THEN the following applies:

o E main steamlines NQIisolated.

11EN you should be in E 2, FAULTED STEAM GENERATOR ISOLATION.

o E main steamhnc. m isolated, THEN you should be in ECA 2.1, UNCONTROLLED DEPRESSURIZATION OF ALL STEAM GENERATORS.

2 CHECK SECONDARY INTREGITY l

a.

Check all SG pressures -

a. E any SG pressure is decreasing in STABLE OR INCREASING an uncontrolled manner AND the SG is NQIisolated, THEN QQIQ E 2, FAULTED SG ISOLATION, Step 1.

I b.

Check all SG pressures -

b. E any SG is completely depressurized l

GREATER THAN 100 PSIG AND the SG is NQIlsolated, 111EN QDIQ E 2, FAULTED SG ISOLATION, Step 1.

I l

Page 2 of 3 1

NUMBER TTT12 REV. ISSUE /DATE ES.0.0 REDIAGNOSIS Rev.1 JUN 3 ISE6 STEP ACDON/ EXPECTED RESPONSE RESPONSE NOT OBTAINED 3

CHECK IF SG TUBES ARE YOU SHOULD B"IN AN E 1 RUMURED:

M ECA 1 SERIES PROCEDURE.

o Any SG levelincreasing in an uncontrolled tranner o Any SG with high radiation i

4 YOU SHOULD BEIN AN E 3 l

2 ECA 3 SERIES PROCEDURE l

END l

1 i

t i

1 l

I i

Page 3 of 3