JUN 3 1988 NUMBER
'ITTIE REV. ISSUE /DATE I
FR H.4 RESPONSE TO LOSS OF NORMAL STEAM Rev. 2
{
RELEASE CAPABILITIES l
(
A.
PURPOSE nis procedt.re provides actions to rtspond to a failure of the steam generator atmospheric vent valve and condenser steam dump valves.
B.
SYAfPTOh!S OR ENTRY CONDITIONS Dis procedure is entered from F-0.3, HEAT SINK Critical Safety Function Status Tree on YELLOW condition.
i f
1 J
Page 1 of 2 8810250310 001007 l
DR ADOCK 0500 13
JUN 3 1988 NUMBER TTTLE REV. ISSUE /DATE FR oll.4 RESPONSE TO LOSS OF NORMAL STEAM Rev.2 RELEASE CAPABILITIES
(
STEP ACDON/ EXPECTED RESPONSE RESPONSE NOTOBTAINED NOTE:
THROUGHOUT THIS PROCEDURE, "AFFECTED" REFERS TO ANY SG IN WHICH PRESSURE IS GREATER THAN 985 PSIG.
r 7
CAUTION:
IF AFFECTED SG(s) WIDE RANGE LEVEL INCREASES TO GREATER THAN 72 % (68 % FOR ADVERSE CONTAINMENT),
STEAM SHOULD NOT BE RELEASED FROM THE AFFECTED SG(s).
L J
1 TRY TO RESTORE NORMAL STEAM IE NORMAL STEAM RELEASE RELEASE CAPABILITY OF CAPABILITIES NQE RESTORED, AFFECTED SG(s):
THEN USE ONE QB BOT 11OFTHE FOLLOWING:
o Atmospheric vent valve
- 1. Terry Turbine steam supply valves.
o Condenser steam dump valves 2
CHECK SG PRESSURES MANUALLY DE LOCALLY LESS T11AN 935 PSIG DUMP STEAM FROM SG(s)
WITTI PRESSURE GREATER THAN 985 PSIG.
3 RETURN IQ PROCEDURE AhTJ STEP IN EFFECT END Page 2 of 2
..