Notice of Violation from Insp on 880425-0503.Violation Noted:Licensee Personnel Observed Resurfacing (Lapping) D Emergency Diesel Generator Crankshaft Main & Connecting Rod Bearing Journals W/O Documented Instructions
ML20154M061
Person / Time
Site: Limerick 
Issue date: 05/25/1988
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20154M043 List:
References
50-353-88-12, NUDOCS 8806010158
Download: ML20154M061 (1)


Text

..

^:

t APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Co Docket No. 50-353 Limerick Unit 2 Nuclear Power Plant License No. CPPR-107 As a result of the inspection conducted during the period April 25 through May 3, 1988 and in accordance with the General Statement of Policy and Procedure for NRC Enforcement Action,10 CFR Part 2, Appendix C (Enforcement Policy 1988),

the following violation was identified.

10 CFR Part 50, Appendix B Section V states that "Activities affecting quality shall be prescribed by documented instruction, procedures, or drawings of a type appropriate to the circumstances and shall be ac-complished in accordance with these instructions, procedures, or drawings.

Instructions,-procedures, or drawings shall include appropriate quanti-tative or qualitative acceptance criteria for determining that important activities have been satisfactorily accomplished."

Contrary to the above, on April 25, 1988 licensee personnel were observed resurfacing (lapping) the "0" emergency diesel generator crankshaft main and connecting rod bearing journals without documented instructions to establish proper lapping materials, lapping procedures, and acceptance criteria. As a consequence newly installed bearings were found with substantial residual contaminating abrasive lapping compound left in the bearings.

4 r

This is a Severity Level IV violation (Supplement II).

Pursuant to the provisions of 10 CFR 2.201, Philadelphia Electric Company is hereby required to submit to this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in l

reply, including: (1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further i

violations; and (3) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending this response time.

l-i i

l 8806010158 880525 7

PDR ADOCK 05000333 O

DCD

-.. -