ML20195D278

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 880411-0522.Violation Noted:Instrument Rack 20C026 Did Not Conform to GE Design Drawing 133D9020
ML20195D278
Person / Time
Site: Limerick Constellation icon.png
Issue date: 06/15/1988
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20195D265 List:
References
50-353-88-10, NUDOCS 8806230085
Download: ML20195D278 (1)


Text

_ ._. _ . ._ _ _ __

4 APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Company Docket No. 50-353 Limerick Unit 2 License No. CPPR-107 As a result of the inspection conducted on April 11, 1988 to May 22, 1988, and in accordance with 10 CFR 2, Appendix C (Enforcement Policy 1988), the following violation was identified.

10 CFR 50, Appendix B, Criterion X requires that inspections be performed to assure conformance of work activities with appropriate design drawings.

The Limerick Summary Description of the Quality Assurance Program for Design and Construction Section D.5.3 states that equipment procured by General Electric, whether manufactured by General Electric or other vendors, will be subject to a quality control inspection program to assure that the design drawing requirements are fulfilled. General Electric drawing 13309020, Revision 7, depicts the General Electric instrument rack weld configuration.

Contrary to the above, on April 29, 1988, examination of safety related '

instrume.,t rack 20C026 found that'the instrument rack did not conform to General Electric design drawing 13309020. The required double sided square groove welds were welded to one side only on a rack reinforcement plate and one quarter inch fillet welds were undersized at multiple locations.

This is a Severity Level IV Violation (Supplement II).

Pursuant to the provision of 10 CFR 2.201, Philadelphia Electric Company is  :

hereby required to submit to this office within 30 days of the date of the '

letter transmitting this Notice, a written statement of explanation in reply i to the violation to include: (1) the corrective steps which have been taken and the results achieved; (2) the corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending 1 time.

OFFICIAL RECORD COPY IR LIM 2 88 0003.0.0

" 06/10/88 8806230085 880615 '

l PDR ADOCK 05000353 I O DCD . j