I Drne go ssra .

lG HQ& Vs N 00py KANSAS GAS AND ELECTRIC COMPANY T*+ ELECT rbC COP WAP4v QLENN L MOESTER w<rPossios%t %vc a me July 31, 1981 Mr. G.L. Madsen, Chief ,

m Reactor Projects Branch e[gb M/ f s U.S. Nuclear Regulatory Commission g /j Region IV 611 Ryan Plaza Drive, Suite 1000

'N

\  % [ ,h\

Arlington, Texas 76011 b_

p

%g j

ebs r 3' V

a 5:  ?

j ,~.

KMLNRC 81-103 ,q\ % Y v,9$ -

Re Docket No. STN 50-482 \6 #

/\ '#

Subj: Potential 10CFR50.55(e) Report on 7p \

Grinding Mark on Main Steam Pipe -

Dear Mr. Madsen:

On July 1,1981, Mr. D.W. Prigel (KG&E) made a telephone report to Mr. W, Crossman (NRC) regarding a grinding mark on a main steam pipe.

The Contractor initiated Deficiency Report No. ISD7271M which documented the UT examination for wall thickness and procedures for base metal repair. A liquid penetrant examination was con-ducted prior to the base metal repair and a radiograph and ultrasonic examination conducted after the repair wCrk. The final disposition of the Deficiency Reoort has indicated that the minimum wall thickness was not violated and that the grinding mark has been repaired using the proper repair procedures. There-fo re , since there was neither a significant defect nor a break-down of QA Procedures which would adversely affect the safety of the plant, we have concluded that this matter is not reportable under Regulation 10CFR50.55 (e) .

If you require any additional information, please contact us.

Yours very truly, ggy AW j

g Glenn L. Koester Vice President - Nuclear gQ7 S

GLK:bb pg cc: TVandel, Resident NRC Inspector 8108110440 810731

{DRADOCK 05000482 PDR:

201 N. Market - Wichita, Kansas - Mail Address: RO. Box 208 i Nchita, Kansas 67201 - Telephone: Area Code (316) 261-6451

_