KANSAS GAS AND ELECTRIC COMPANY THE ELECTAC COMPANY OLENN L. NOESTER

= =.=~,. = aa May 1, 1985 Mr. R.P. Denise, Director Wolf Creek Task Force

/

U.S.#uclear Regulatory Comissim MAY 6125 N

Region IV 611 Ryan Plaza Drive, Suite 1000 f)

Arlington, Texas 76011 KMLNRC 85-100 Re:

Docket No. EfN 50-482 Subj: Potential 10CFR21 Notification - Concerning Ruskin Fire Danpers

Dear.v. Denise:

r This letter provides notification pursuant to 10CFR21.21 concerning Ruskin Pire Danpers installed at Wolf Creek Generating Station (NCGS). This matter was initially reported by Mr. H. K.

Chernoff of Kansas Gas ar.d Electric Conpany (KG&E) to Mr. L. E.

Martin of the M2 clear Regulatory Comission, Region IV, on April 26, 1985.

The subject fire danpers were acnufactured by Ruskin Manufacturing Co., of Grandview, Missouri.

Some danpers were found to have less than the designed clearance between the fire danper frame and the penetration sleeve. During a fire, thermal expansion of a fire danper, without the design clearances, could result in buckling of the fire danper frame.

This could potentially affect the integrity of the danper.

A reinspection of the affected Ruskin Fire Danpers is currently being performed.

Those danpers found in a discrepant condition will be reworked in order to assure the integrity and proper functioning of the fire danpers.

g5090248850501 s

ADOCK 05000482 hh h~

'\\f 2o, N. u.a., - war.. x.., - ua Asa.,,: ea soaos mar.. x-,. enor - ran.>.. cos. o re> 2e >#s >

P Mr. R. P. Denise May 1, 1985 KMUEC 85-100 Further information on this subject will be provided in Licensee Event Report 85-017.

If you have any questions concerning this matter, please contact me or Mr. Otto Maynard of my staff.

Yours very truly,

t. Glenn L. Koester Vice President - Nuclear GE: dab xc: PO'Connor (2)