ML20104A817

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Subcooling Core Monitor Alarm & Caution Relays.Initially Reported on 840821.Interposing Relays & Diodes Added to Sys to Minimize Potential for & Suppress Effects of Any Arcs Generated
ML20104A817
Person / Time
Site: Wolf Creek 
Issue date: 01/13/1985
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Denise R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
KMLNRC-85-024, KMLNRC-85-24, NUDOCS 8502010525
Download: ML20104A817 (1)


Text

( [?] W_COMPANY Q.y KANSAS GAS AND LECTRIC

~

i

?

,l

. (,I L

~

/t' THE ELECTAC COMPANY l

q JAN 211995 f GLENN L MOESTER vsCE PersicaNT seuC(Ema W

January 13, 1985 N

Mr. R.P. Denise, Director Wolf Creek Task Force U.S. Nuclear Regulatory Cmmission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlirgton, Texas 76011 EMIRRC 85-024 Re:

Docket No. STN 50-482 Ref:

Interim Report EMLNRC 84-162, dated 9/20/84 Fran GLKoester, KG&E, to DRHunter, NRC Subj: Final 10CFR50.55(e) Report - Subcooling Core Monitor Alann and Caution Relays (53564-K150)

Dear Mr. Denise:

'Ihis letter provides the final report subnitted pursuant to 10CFR50.55(e; concerning the subcooling core monitor system installed at Wolf Creek Generating Station (NCGS). 'Ihis matter was initially reported on August 21, 1984 with supplenental information provided in the Reference.

It was determined that when the 125 volt direct current power supply to the non-lE annunciator systen for the subcoolirg core monitor system is interrupted an are resulting voltage spike may occur. A voltage spike of this type could danage integrated circuits or interrupt the central processing unit of the subcooling core monitor systen. In order to alleviate this concern, interposing relays and diodes have been added to the existing systen to minimize the potential for, and suppress the effects of any arcs generated.

'Ihe aforementioned corrective actions will be conpleted prior to fuel load.

If you have any questions concerning this matter, please contact me or Mr.,

Otto Maynard if my staff.

Yours very truly, Hf f5 8502010525 850113 Glenn L. Koester PDR ADOCK 05000482 Vice President - Nuclear S

PDR

']

GLK: dab b

I I(O xc: RCDeYoung P0'Connor HBundy NGuldenord 201 N. Market - Wichita, Kansas - Mail Address: PO. Box 208 i Wichita, Kansas 67201 - Telephone: Area Code (316) 261-6451