Final Deficiency Rept Re Standby Diesel Generator B Left Bank Turbocharger.Initially Reported on 840504.Caused by Loose Lock Nut on Left Bank Turbocharger Lubricating Oil Pump Centrifuge.Damaged Turbocharger Repaired & Inspected
ML20104A867
Person / Time
Site: Wolf Creek 
Issue date: 01/13/1985
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Denise R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
KMLNRC-85-021, KMLNRC-85-21, NUDOCS 8502010541
Download: ML20104A867 (1)


Text

M KANSAS GAS,}W @CTRIC'COMPANUn DVJ[G l

EW Q

JAN 211985 r eacrac cc -wu N

OLENN L MOESTER l

January 13, 1985 v.u m.,o.

r.

vem.

l l

l Mr. R.P. Denise, Director Wolf Creek Task Force U.S. Nuclear Regulatory Commission Region IV I

l 611 Ryan Plaza Drive, Suite 1000 l

Arlington, 'lexas 76011

{

EMIRRC 85-021 Re:

Docket No. STN 50-482 Ref:

Interim Report KMLNBC 84-083, dated 6/1/84 l

Frcxn GLKoester, KG&E, to EHJohnson, NRC Subj: Final 10CFR50.55(e) Report - Standby Diesel Generator "B" Ieft Bank Turbocharger (53564-K138)

Dear Mr. Denise:

{

'1his letter provides the final report submitted pursuant to 10CFR50.55(e) concerning the "B" standby diesel generator left bank turbocharger at Wolf

}

Creek Generating Station. Wis matter was initially reported on May 4, 1984 with supplanental information provided in the reference.

As indicated in the reference the turbocharger failure was apparently the result of a loose lock nut on the left bank turbocharger lubricating oil i

pump centrifuge. We damaged turbocharger has been repaired and the other I

standby diesel generator turbochargers were instpected to preclude any l

similar failures.

l We aforementioned corrective actions have been completed. If you have any questions concerning this matter, please contact me or Mr. Otto Maynard of my staff.

Yours very truly, futl Glenn L. Koester Vice President - Nuclear CLK: dab e

^

xc: RCDeYoung PO'Connor M; )_1 HBurdy NGuldemond

' 0 8502010541 850113 PDR ADOCK 05000482 S

PDR 201 N. Market -WocNta. Kansas -Mail Address: RO. Box 208 I Wichita, Kansas 67201 -Telephone: Area Code (316) 261-6451