ALouisAllis 4 o, m a uap w rc 427 E. Stewart St., P.O. Box 2020, Milwaukee, WI 53201-2020 414-481-6000 TWX 910-262-3115 April 23, 1985 Mr. J. M. Taylor, Director Office on Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington D. C.
20555
Subject:
10CFR 21 Report Inspection Procedure Revision
Reference:
H. H. Leusink Letter dated April 15, 1985
Dear Mr. Taylor:
Please find enclosed Revision 1 to the inspection procedure prepared for the purpose ai investigating the emergency diesel generators, which was included with my April 15, 1985 letter.
A copy of this revision vill be forwarded to each site's Quality Assurance Department as indicated below.
Sincerely, du H. H. Leusink Vice President, Engineering HHL:sd Attachment cc: Project Manager Nuclear Quality Assurance Nuclear Quality Assurance Public Service Electric & Gas Company Washington Public Power System P.O. Box 236 P.O. Box 968 Hancock's Bridge, Nov Jersey 08038 Richland, Washington 99352 Quality Assurance Manager Quality Engineering Manager Kansas Gas & Electric Company Public Service of Indiana P.O. Box 208 Marble Hill Nuclear Division Wichita, Kansas 67201 P.O. Box 190 New Washington, Indiana 47162 Quality Assurance Manager 8
Union Electric Company PDj4300459 850423 P.O. Box 149 ADOCK 0500 2
St. Louis, Missouri 63166 S
cM 9,/2y (,
Louis Allis:
> hp >f-%
J. Borman
.-gg( 3 '
/
D. Bryant M. Buckna M
g (p I/0 7 fc A. Giesecke
~ 7; 19 H. Schreiber J. Treibic
(T' ' '[c. O I
I k
.,8
& w_UISAHIS LO y-m.,.u,m M9537 - 4/82 ar; ENGINEERING REPORT rite NUMBER dk ALTERNATORS CONTROLS ROTARY COMPRESSORS ATE R EFE R ENCE 10CFR 21 - Emergency Stand By Generators gy4 ) 9\\ 399q PREPARED BY N>
5*
APPROVED Sus;ECT Inspection Procedures for Fractured Welds on BY H. H. Leusink Air Deflectorn The purpose of this instruction is to outline a procedure for the visual inspection of the emergency standby generators referenced for possible i
fractured or cracked velds.
By copy of this communication, we are requesting the site Quality Assurance Group make this inspection and to report back their findings to:
Mr. Herbert A. Schreiber 3
Manager Customer Service Louis Allis Division MagneTek, Inc.
427.E. Steuart St.
P.O. Box 2020 Miluaukee, Wisconsin 53201-2020 j
Telephone: 414/481-6000 X289 3
f, The procedure is as follous:
' ji 1.
Remove the protective screens from each end of the generator coil guards as indicated on the attached Sketch A.
?)~.
Ui 2.
Visually inspect the fillet veld securing the conical air g
TO deflector that is velded to the three piece coil guards.
t!!
The air deflector is secured to the coil guard by a 3/16" T
fillet veld, 1" long on centers of 4".
There vill be F.c approximately sixty (60) of these velds around the
=,g[
circumference of this joint.
ww.
siI All findings should be. reported immedia'.ely to the Manager of Customer
'5E.
Service at Louis Allis.
- Se M
3S~
3 3Mi R<
Y 3
~
kE o
55 di 04
a s.
t
&LOUISAillS m->a uu*+
ssEET 2 OF 2 SO[*
M9537 - 4/82 41!
ENGINEERING REK;RT rile NUMBER dk ALTERNATOR.S - CONTROLS - ROTARY COMPRESSORS
(
DATE April 15, 1985 F5 REFERENCE 10CFR 21 - Emergency Stand By Generators
.~
W4 NUMBER PREPARED BY E
SUBJECT Inspection Procedure for Fractured Welds on
^$ PROVED Air Deflectors 3 PIEde 5 pirsce cou. Gu c e D i