KANSAS GAS AND [LECTRIC COMPANY THE ELECTFWC COMPANY CLENN L MOESTER voce Pass
- DENT NucLeas December 7, 1984 Mr. R.P. Denise, Director PQ J$
Wolf Creek Task Force li.S. Nuclear Regulatory Commission Region IV g l}g 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 j
KMLNRC 84-215 Re:
Docket No. STN 50-482 Ref Interim Report KMLNRC 84-097 dated 6/21/84 from GLKoester, KG&E, to EHJohnson, NRC Subj: Supplemental Final 10CFR50.55(e) Report -
Hollow Metal Fire Door Frame Installation (53564-K140)
Dear Mr. Denise:
The purpose of this letter is to provide a supplemental final report submitted pursuant to 10CFR50.55(e) concerning the installation of three-hour rated (Class A) hollow metal fire door frames at Wolf Creek Generating Station (WCGS). This matter was initially reported on May 25, 1984 and a final report was submitted in the Reference.
The Reference indicated the following:
(Kansas Gas and Electric Company) KG&E has elected to replace the existing combustible caulking surrounding all Class A hollow metal fire door frames with an approved flame retardent adhesive sealant...
In order to more accurately reflect the actions taken by KG&E, the afore-mentioned statement is revised as follows:
... KG&E had actually elected to replace the existing caulking surrounding all Class A hollow metal fire door frames that provide a three-hour fire rated barrier separating all safe shutdown equipment, as required by 10CFR50 Appendix R, with an approved flame retardent adhesive sealant.
8501020274 841207 DR ADOCK 05000 201 N. Market -Wichtta Kansas - mar Address: RO. Box 208 i Wictuta, Kansas 67201 - Telephone: Area Code (316) 261-6451
l I
.e b
i 1
Mr. R.P. Denise KMLNRC 84-215-December 7, 1984-All other Class A hollow metal fire door frames have been installed according to the appropriate manufacturers' drawing detail.
If you have any questions concerning this subject, please contact me or Mr. Otto Maynard of my staff.
Yours very truly, lN Glenn L. Koester Vice President - Nuclear GLKabb xc:RCDeYoung PO'Connor (2)