PS~G*

Public Service Electric and Gas Company Sc;i.lem Nuclear Generating Station P.O. Box #168 May 9, Director Off ice of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555 MONTHLY OPERATING REPORT SALEM GENERATING STATION In compliance with Section 6.9, Reporting Requirements for the Salem Technical Specifications, the following Monthly Operating Reports for the month of April, 1977 are being sent to you.

(original plus 10 copies)

Appendix B - Average Daily Unit Power Level Appendix C - Operating Data Report Appendix D - Unit Shutdowns and Power Reductions Additional copies of the Monthly Operating Reports are being sent to:

1. Mr. James P. O'Reilly (1 Copy)

Director of US NRC Off ice of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, PA 19406

2. Director, Office of Management Information (2 Copies) and Program Control US Nuclear Regulatory Commission Washington, D.C. 20555 H. J. Heller Manager - Salem Generating Station Enc.

Pg. 1-4 8-1-7. Rl The Energy People

APPENDIX B AVERAGE DAILY.UNIT POWER LEVEL OOCKET NO. 50-272 UNIT' Salem #1 DATE 5/9/77 COMPLETED BY J.M. Zupko, Jr.

TELEPHONE 609.,-3 65-7000 Ext. 507 MONTH April, 1977 DAY AVERAGE DAILY POWER LEVEL DAY AVERA.GE DAILY POWER LEVEL (MWe-NET) (MWE-NET) 1 0 17 545 2 0 18 548 3 50 19 546 4 141 20 550 5 729 21 927 6 777 22 906 7 842 23 789 8 918 24 750 831 992 9 25 986 880 10 26 462 927 11 27 12 0 28 1006 13 0 29 427 434 90 14 30

15. 493 31 16 . 555 Pg. 2-4 8.1-7.RL,

APPF.NDIX C OPERA'I'.ING DATA REroRT e 50-272 OOCKET NJ. - - - - - - - - -

UNIT Salem #1 DATE 5-9-77

............. . . CCMPLE'l'ED 'f5'f J. M. Zupko, Jr .

OPERATING STA'IUS TELEPHONE*609-365-7000 X507

1. REPORTING PERIOD: April, 1977 GROSS HOURS IN REPORTING PERIOD:
    • 1r:D
  • 719 To be .
2. CURRell'LY AtJIRORIZED POWER LEVEL ()il'lt) :3338 MAX.DEPEND.CAPACITY(MWe-NEl') :Detemu.ned DESIGN ELECTRICAL RATING (MWe-Net) : 109~
3. Pa'IER LEVEL TO WHICH RESTRICTED (IF ANY) ()!We-Net) :

None

4. REASONS FOR RESTRICTION (IF .ANY): .

THIS MJN'IH YR TO DATE Ct.lMlJLATIVE

5. DfBER OF BJURS REACTOR WAS CRITICAL * ... 588.3 2112.3 2413.9 0 *O 0
6. REACTOR RESERVE SHUI'OOWN HOURS * * * * * *
  • 560.6 1815.5 1855.8
1. HOURS GENERATOR ON LINE * *
  • 0 0 0 8.

9.

UNIT RESERVE SHUI'OOWN HOURS * * * * * * *

  • GROSS 1HEm-1AL ENERG'l GENERATED(MMQ. * *
  • 1,320, 790 3,176,988 3,225,685
10. GROSS ELECTRICAL ENERGY GENERATEDQin'iH) * *
  • _ _ 43_6_,1_1_0 987 ,070 990,300
11. NET ELECTRICAL ENERGY' GENERATED{Ml41H).
  • 405,161 880,708 880,708
12. REACTOR SERVICE FACTOR * * * * * * * * *
  • N/A N/A N/A
13. REACI'OR AVAILABILITY FACTOR * . . . . . . .. ---- N/A N/A N/A
14. UNIT SERVICE FACTOR * * * * * * * * * * *
  • N/A N/A N/A N/A N/A N/A lS. UNIT AVAILABILITY' FACTOR * * * * *
16. UNIT CAPACITY FACTOR(Using MDC). * .... *---- N/A N/A N/A
17. UNIT OOM:.rrl FACTOR(Using Design MWe)
  • N/A N/A N/A N/'A N/A N/A
18. UNIT FORCED ourAGE RATE * * * * * * * * * *
19. SHUTIXJ'IJNS SCllEDULED OVER NEcr 6 MJNI'HS('I"fPE,DATE,.AND DURATlON OF EACH): 9_.,..12.,..77 Modification of IDw Pressure Turbine Blading, Eight Weeks.

IF SHUT OOWN AT END OF REPORT PERIOD, ESTIMATED DATI: OF SI'.~:

. "' ZO.

21. UNITS IN TEST STATIJS (PRIOR TO CGMERCIAL OPERATION) : FO~CAST N/A AailEVED INITIAL CRITICALIT'f 9-30-76 12-11-76 INITIAL ELECI'RIClT'f 11-01-76 12-25-76 Pg. :3~4 8-1-7.Rf CCM'1ERCIAL OPERATION 12-20-76

APPENDIX D DOCKET NO. 50-272 r ,~ .

UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME Salem #1 .,

DATE May 9_, 1977 COMPLETED BY J. M. Zupko, Jr.

TELEPHONE 609-365-7000 X507 REPORT MONTH April, .1977 METHOD OF TYPE OUTAGE SHUTTING DOWN F: FORCED DURATION THE REACTOR OR NO. DATE S: SCHEDULED (HOURS) REASON REDUCING POWER CORRECTIVE ACTIONS/COMtvlENTS 77.,..26 770331 Forced 54.1 A 3 13/14 Main Strn. Valve Closure 77.,..27 770403 Forced 12.5 H 3 11 Strn. Gen. Feed Pump Trip 77-28 770404 Forced 12.7 F 2 10 GPM Unidentified RCS Leakage.

77-29 770406 Forced 0 B 4 Clean Condensate Pump Strainers 77-30 770411 Forced 21.0 A 3 High Negative Rate/N31, N32 BlarVn Fuse on Control Rod lA2 77.,..31 770412 Forced 33.4 H 3 14 S.G. High High Level/Restarting of 14 RCP above p.,..7, 77.,..32 770426 Forced 0 B 4 Clean Condensate Pump Strainers 77-33 770429 Forced 24.7 G 2 Inadvertant Isolation of EH Pressure SWitch.

SUMMARY

*LOAD REDUCTION.

Pg.4-4 8.1-7.R-l