|
---|
Category:LICENSEE EVENT REPORT (SEE ALSO AO
MONTHYEARML18017A9181999-10-0808 October 1999 LER 99-008-00:on 991008,CR Emergency Filtration Sys Tech Specs Occurred.Caused by Site Personnel Failed to Recognize That Blocking Open CR Emergency Filtration Sys.Procedures Revised.With 991008 Ltr ML18017A8671999-09-10010 September 1999 LER 99-007-00:on 990811,determined That Cvis ARMs High Alarm Setpoints Were Not within TS Limit.Caused by Not Having Procedure to Verify If Cvis ARM High Alarm Setpoints Were within TS Requirements.Revised Procedures.With 990910 Ltr ML18016B0481999-08-0404 August 1999 LER 99-006-01:on 981124,noted Failure to Comply with TS 4.0.4 & TS 3/4.6.3, Civs. Caused by post-maint Testing That Did Not Adequately Test Control Circuitry & Verify Isolation Time Following Maint.Procedure Was Revised ML18016A9801999-06-0404 June 1999 LER 99-006-00:on 981124,failed to Comply with TS 4.0.4 & TS 3/4.6.3, Civ. Caused by post-maint Testing That Did Not Adequately Test Control Circuitry & Verify Isolation Time Following Maint.Procedure Will Be Revised.With 990604 Ltr ML18016A9111999-04-12012 April 1999 LER 99-005-00:on 990313,plant Exceeded ESFAS TS 3.3.2,Action 21.Caused by Inadequate Procedure Rev Preparation.Licensee Revised Applicable Maint Surveillance Test Procedure (MST-10072) to Identify TS Required Actions.With 990412 Ltr ML18016A8971999-04-0808 April 1999 LER 99-004-00:on 990312,unit Trip Was Noted.Caused by Degraded Condition of SG Water Level Flow Control Valve. Replaced Positioners on All Three FW Regulating Valves.With 990408 Ltr ML18016A8261999-02-22022 February 1999 LER 99-003-00:on 990123,noted That Plant Was Outside Design Basis Due to Isolation of Fire Protection Containment Sprinkler Sys.Caused by Human Error.Restored Containment Sprinkler Sys to Operable Status.With 990222 Ltr ML18016A8111999-02-12012 February 1999 LER 99-002-00:on 990114,RT Due to Not Removing Temporary Device from Relay Following Calibration Was Noted.Caused by Human Error.Counseled Personnel Involved in Event.With 990212 Ltr ML18016A7971999-02-0505 February 1999 LER 99-001-00:on 990106,SF Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Fasteners Bending Under Specific Circumstances.Increased Water Level.With 990205 Ltr ML18016A7941999-01-29029 January 1999 LER 98-004-01:on 980313,identified Design Deficiency Re Potential Runout of Tdafwp.Caused by Inadequate Original AFW Sys Design.Operability Evaluation Was Completed on 980313 & Addl Engineering Analysis Was Performed by Vendor ML18016A7211998-11-17017 November 1998 LER 98-007-00:on 981023,turbine Control Anomaly Caused Manual Rt.Caused by Failure to Incorporate Verbal Vendor Guidance in Operating Procedures.Addl Vendor Guidance Will Be Verified & Added to Procedures.With 981117 Ltr ML18016A4841998-07-0707 July 1998 LER 97-002-01:on 970207,determined That Cold Weather Conditions Resulted in Mfiv Being Potentially Inoperable During Period 970117-20.Caused by Inadequate Design of HVAC Sys.Implemented Mods to Steam Tunnel HVAC Sys ML18016A4701998-06-30030 June 1998 LER 97-021-03:on 980210,discovered That SFP Water Level Had Not Been Verified Greater than 23 Feet Above BWR Fuel Assemblies.Caused by Misinterpretation of TS Requirements. Will Submit TS Change Request to Revise TS 3.9.1.11 ML18016A4491998-06-0808 June 1998 LER 98-006-00:on 980508,failure to Perform Insp & Preventive Maint on MCCB as Required by TS Was Noted.Caused by Inadequate Sps.Tested 9 Pressurizer Heater Bank Breakers by Cycling each.W/980608 Ltr ML18022B0551998-05-20020 May 1998 LER 98-005-00:on 980420,TS Verbatim non-compliance Was Determined.Caused by Misinterpretation of TS Requirements. Issued Memo to Reemphasize Need to Comply W/Literal Meaning of TS Requirements in Verbatim manner.W/980520 Ltr ML18016A4061998-04-30030 April 1998 LER 98-002-01:on 980121,determined Ssps (P-11 Permissive) Testing Deficiency.Caused by Inadequate Review of Initial Ts.Will Revise & Perform Surveillance Test Procedures to Verify Operability of P-11 Permissive ML18016A3841998-04-13013 April 1998 LER 98-004-00:on 980313,design Deficiency Related to Indequate Runout Protection for Turbine Driven AFW Pump Was Identified.Caused by Inadequate Original AFW Sys Design. Evaluation (ESR 98-00100) Will Be completed.W/980409 Ltr ML18016A3441998-03-12012 March 1998 LER 97-021-02:on 980210,identified Failure to Properly Test non-safety Related Pressurizer Porv.Caused by Inadequate Surveillance Test Procedures.Revised Operations Surveillance Test OST-1117 to Include Testing of Subject PORV ML18016A3291998-02-27027 February 1998 LER 98-003-00:on 980129,failure to Perform Shutdown Margin Calculation Required by TS Surveillance Requirements Occurred.Caused by Ambiguity in TS 3.1.3.1.c.Procedures revised.W/980227 Ltr ML18016A3211998-02-20020 February 1998 LER 98-002-00:on 980121,solid State Protection Sys Testing Deficiency Occurred.Caused by Inadequate Review of Initial Tech Specs.Ts Testing Frequency for P-11 Permissive Revised. W/980217 Ltr ML18016A3131998-02-0909 February 1998 LER 98-001-00:on 980109,potential Condition Outside Design Basis Related to Instrument Air Sys Leak Causing SG pre- Heater Bypass Isolation Valves to Be Inoperable Was Noted. Caused by Inadequate Design Control.Generated Jco 98-01 ML18016A2641997-12-18018 December 1997 LER 97-024-00:on 971118,SSPS Testing Deficiency Was Noted. Caused by Inadequate Testing Scheme Provided by Ssps Vendor. Revised procedure.W/971218 Ltr ML18016A2501997-11-24024 November 1997 LER 97-023-00:on 920721,RCS PIV Testing Deficiency Was Noted.Caused by Failure to Consider All Testing Variables During Initial Sp Development.Surveillance Tp OST-1506 Was Revised to Incorporate Correction factor.W/971124 Ltr ML18016A2201997-10-22022 October 1997 LER 97-021-01:on 970922,discovered That Spent Fuel Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Misinterpretation of TS Requirements.Revised Daily Surveillance Procedures ML18016A2081997-10-14014 October 1997 LER 97-016-01:on 970608,reactor Trip Occurred,Due to Personnel Error While Attempting to Adjust Power Range Nuclear Instrumentation Channel Following Performance of Calorimetric.Procedures revised.W/971014 Ltr ML18016A2111997-10-14014 October 1997 LER 96-008-02:on 960425,turbine Trip/Reactor Trip Occurred. Caused by High Resistance Connection Resulting from a Phase Switch Jaw & Blade Contacts.Failed a Phase Disconnect Switch on Breaker 52-7 Replaced ML18016A1931997-09-29029 September 1997 LER 97-022-00:on 970829,TS Required Shutdown Due to Expiration of AFW Lco.Caused by Personnel Error.Completed Repairs TDAFW Pump & Returned Plant to Svc on 970831. W/970926 Ltr ML18016A1891997-09-12012 September 1997 LER 97-020-00:on 970814,inadequate Fire Protection Provided for safety-related EDG Fuel Oil Transfer Pump Cables Resulted in Operation Outside Design Basis.Caused by Engineering Oversight.Established Fire watches.W/970912 Ltr ML18016A1881997-09-12012 September 1997 LER 97-021-00:on 970814,spent Fuel Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Misinterpretation of Ts.Directions Provided to Operations.W/970912 Ltr ML18012A8641997-08-18018 August 1997 LER 97-019-00:on 970720,turbine Trip/Reactor Trip Occurred. Caused by Three Phase Fault That Collapsed Excitation Field in Main Generator,Resulting in Generator Lockout.Exciter Rotor Assembly Was replaced.W/970818 Ltr ML18012A8581997-08-0808 August 1997 LER 96-018-01:on 960903,manual Reactor Trip Occurred Due to Loss of Normal Sw.Caused by Mechanical Failure of B Water Pump & a Normal SW to Remain Running Once Manually Started.Restored a Normal SW Pump to Svc ML18012A8551997-08-0808 August 1997 LER 96-013-02:on 961028,condition Outside of Design Basis Where RWST Had Been Aligned w/non-seismically Qualified Sys Was Identified.Caused by Failure to Reconcile Operating Procedure Lineups.Established Administrative Controls ML18012A8471997-07-31031 July 1997 LER 97-018-00:on 970701,determined That Plant Procedures Had Not Received Proper Reviews & Approvals.Caused by Failure to Comply W/Plant Administrative Procedure AP-006.Counseled Involved individuals.W/970731 Ltr ML18012A8371997-07-24024 July 1997 LER 97-S01-00:on 970405,unescorted Access Inappropriately Granted to Contract Outage Workers Was Determined.Caused by Personnel Error.Access Files for Individuals Inappropriately Granted Unescorted Access Were Placed on Access Hold ML18012A8291997-07-11011 July 1997 LER 97-017-00:on 970612,failed to Recognize Inoperable Reactor Afd Monitor.Caused by Personnel Error.Operators Involved in Event Will Be Counseled Prior to Assuming Shift duties.W/970711 Ltr ML18012A8301997-07-0808 July 1997 LER 97-016-00:on 970608,reactor Trip Occurred Due to Personnel Error in Adjusting Power Range (Pr) Nuclear Instrumentation (Ni).Issued Night Order Prohibiting Pr Ni Adjustment When Redundant Channel inoperable.W/970708 Ltr ML18012A8241997-07-0202 July 1997 LER 97-015-00:on 970602,inadequate Auxiliary Feedwater Sys Flow Control Valve Surveillance Testing Deficiency Was Identified.Caused by Failure to Recognize Impact on TS 4.7.1.2.1.Readjusted AFW FCV Actuator spring.W/970702 Ltr ML18022B0181997-06-13013 June 1997 LER 97-014-00:on 970514,SI Occurred During Ssps Surveillance Testing.Caused by Inattention to Detail During Recent Rev to Surveillance Test Procedure Being Used.Revised Deficient Surveillance procedures.W/970613 Ltr ML18012A8081997-06-0909 June 1997 LER 97-013-00:on 970508,entry Into Mode-6 Without Operable Components,Resulting in TS 3.0.4 Violation Occurred.Caused by Personnel Error.Personnel Involved counseled.W/970609 Ltr ML18012A8021997-06-0606 June 1997 LER 97-023-02:on 961114,design Deficiency Was Identified in Emergency DG Protection Circuitry.Caused by Inadequate Plant Design.Revised Surveillance Test Procedures OST-1013 & OST-1073.W/970606 Ltr ML18012A8011997-06-0404 June 1997 LER 97-012-00:on 970505,determined That Previous Auxiliary Control Panel Had Not Verified Operability of Interposing Relays.Caused by Misinterpretation of Tss.Reviewed Other Remote Shutdown Panel Transfer circuitry.W/970604 Ltr ML18012A7951997-05-29029 May 1997 LER 96-023-01:on 961114,design Deficiency in EDG Protection Circuitry Was Identified.Caused by Inadequate Original Plant Design.Surveillance Test Procedures OST-1013 & OST-1073 revised.W/970529 Ltr ML18012A7891997-05-22022 May 1997 LER 97-011-00:on 970422,inappropriate TS Interpretation Resulted in Violations of ECCS Accumulator TS & Entry Into TS 3.0.3.Caused by Procedural Inadequacy.Tsi 88-001 Cancelled 970508 & Procedures revised.W/970522 Ltr ML18012A7871997-05-19019 May 1997 LER 97-010-00:on 970418,design Deficiency Determined Re Reactor Coolant Pump Motor Oil Collection Sys.Caused by RCP Ocs Design Detail.Rcp Ocs Enclosures for Each of Three Installed RCP Motors Have Been modified.W/970519 Ltr ML18012A7761997-05-0707 May 1997 LER 97-009-00:on 970407,fuse Was Removed from CR Ventilation Isolation Signal Power Supply Circuitry Due to Personnel Error.Individuals Involved Were counseled.W/970507 Ltr ML18012A7751997-05-0505 May 1997 LER 97-008-00:on 970404,safety-related AHU Not Declared Inoperable During Maintenance on Associated Temperature Switches Resulting in Violation of Ts.Caused by Incorrect Interpretation.Operations Night Order issued.W/970505 Ltr ML18012A6291997-04-24024 April 1997 LER 97-007-00:on 970325,inoperable CCW Sys TS 3.0.3 Entry Made.Caused by Combination of Procedural Inadequacies, Improper Use of Procedure Guidance & Poor Communication. Applicable Individuals counseled.W/970423 Ltr ML18022B0151997-04-17017 April 1997 LER 97-006-00:on 970318,breach Was Identified in Thermo-Lag Fire Barrier Wall Due to Inadequate Initial Design,Poor Construction Methods & Incomplete as-built Design.Visual Insp of Thermo-Lag Barrier Walls performed.W/970417 Ltr ML18012A6041997-04-0303 April 1997 LER 97-004-00:on 970304,in-plant Spent Fuel Cask Handling Activities Conducted Outside Design Basis.Caused by Lack of Understanding of Requirements.Operations Placed on Hold Pending NRC Review & Approval of procedures.W/970331 Ltr ML18012A6031997-03-31031 March 1997 LER 97-003-00:on 970227,steam Generator Low Level Protection Circuitry Outside Design Basis Occurred.Caused by Inadequate Failure Modes & Effects Analysis Performed as-built Piping Configuration for S/G Level.Review performed.W/970331 Ltr 1999-09-10
[Table view] Category:RO)
MONTHYEARML18017A9181999-10-0808 October 1999 LER 99-008-00:on 991008,CR Emergency Filtration Sys Tech Specs Occurred.Caused by Site Personnel Failed to Recognize That Blocking Open CR Emergency Filtration Sys.Procedures Revised.With 991008 Ltr ML18017A8671999-09-10010 September 1999 LER 99-007-00:on 990811,determined That Cvis ARMs High Alarm Setpoints Were Not within TS Limit.Caused by Not Having Procedure to Verify If Cvis ARM High Alarm Setpoints Were within TS Requirements.Revised Procedures.With 990910 Ltr ML18016B0481999-08-0404 August 1999 LER 99-006-01:on 981124,noted Failure to Comply with TS 4.0.4 & TS 3/4.6.3, Civs. Caused by post-maint Testing That Did Not Adequately Test Control Circuitry & Verify Isolation Time Following Maint.Procedure Was Revised ML18016A9801999-06-0404 June 1999 LER 99-006-00:on 981124,failed to Comply with TS 4.0.4 & TS 3/4.6.3, Civ. Caused by post-maint Testing That Did Not Adequately Test Control Circuitry & Verify Isolation Time Following Maint.Procedure Will Be Revised.With 990604 Ltr ML18016A9111999-04-12012 April 1999 LER 99-005-00:on 990313,plant Exceeded ESFAS TS 3.3.2,Action 21.Caused by Inadequate Procedure Rev Preparation.Licensee Revised Applicable Maint Surveillance Test Procedure (MST-10072) to Identify TS Required Actions.With 990412 Ltr ML18016A8971999-04-0808 April 1999 LER 99-004-00:on 990312,unit Trip Was Noted.Caused by Degraded Condition of SG Water Level Flow Control Valve. Replaced Positioners on All Three FW Regulating Valves.With 990408 Ltr ML18016A8261999-02-22022 February 1999 LER 99-003-00:on 990123,noted That Plant Was Outside Design Basis Due to Isolation of Fire Protection Containment Sprinkler Sys.Caused by Human Error.Restored Containment Sprinkler Sys to Operable Status.With 990222 Ltr ML18016A8111999-02-12012 February 1999 LER 99-002-00:on 990114,RT Due to Not Removing Temporary Device from Relay Following Calibration Was Noted.Caused by Human Error.Counseled Personnel Involved in Event.With 990212 Ltr ML18016A7971999-02-0505 February 1999 LER 99-001-00:on 990106,SF Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Fasteners Bending Under Specific Circumstances.Increased Water Level.With 990205 Ltr ML18016A7941999-01-29029 January 1999 LER 98-004-01:on 980313,identified Design Deficiency Re Potential Runout of Tdafwp.Caused by Inadequate Original AFW Sys Design.Operability Evaluation Was Completed on 980313 & Addl Engineering Analysis Was Performed by Vendor ML18016A7211998-11-17017 November 1998 LER 98-007-00:on 981023,turbine Control Anomaly Caused Manual Rt.Caused by Failure to Incorporate Verbal Vendor Guidance in Operating Procedures.Addl Vendor Guidance Will Be Verified & Added to Procedures.With 981117 Ltr ML18016A4841998-07-0707 July 1998 LER 97-002-01:on 970207,determined That Cold Weather Conditions Resulted in Mfiv Being Potentially Inoperable During Period 970117-20.Caused by Inadequate Design of HVAC Sys.Implemented Mods to Steam Tunnel HVAC Sys ML18016A4701998-06-30030 June 1998 LER 97-021-03:on 980210,discovered That SFP Water Level Had Not Been Verified Greater than 23 Feet Above BWR Fuel Assemblies.Caused by Misinterpretation of TS Requirements. Will Submit TS Change Request to Revise TS 3.9.1.11 ML18016A4491998-06-0808 June 1998 LER 98-006-00:on 980508,failure to Perform Insp & Preventive Maint on MCCB as Required by TS Was Noted.Caused by Inadequate Sps.Tested 9 Pressurizer Heater Bank Breakers by Cycling each.W/980608 Ltr ML18022B0551998-05-20020 May 1998 LER 98-005-00:on 980420,TS Verbatim non-compliance Was Determined.Caused by Misinterpretation of TS Requirements. Issued Memo to Reemphasize Need to Comply W/Literal Meaning of TS Requirements in Verbatim manner.W/980520 Ltr ML18016A4061998-04-30030 April 1998 LER 98-002-01:on 980121,determined Ssps (P-11 Permissive) Testing Deficiency.Caused by Inadequate Review of Initial Ts.Will Revise & Perform Surveillance Test Procedures to Verify Operability of P-11 Permissive ML18016A3841998-04-13013 April 1998 LER 98-004-00:on 980313,design Deficiency Related to Indequate Runout Protection for Turbine Driven AFW Pump Was Identified.Caused by Inadequate Original AFW Sys Design. Evaluation (ESR 98-00100) Will Be completed.W/980409 Ltr ML18016A3441998-03-12012 March 1998 LER 97-021-02:on 980210,identified Failure to Properly Test non-safety Related Pressurizer Porv.Caused by Inadequate Surveillance Test Procedures.Revised Operations Surveillance Test OST-1117 to Include Testing of Subject PORV ML18016A3291998-02-27027 February 1998 LER 98-003-00:on 980129,failure to Perform Shutdown Margin Calculation Required by TS Surveillance Requirements Occurred.Caused by Ambiguity in TS 3.1.3.1.c.Procedures revised.W/980227 Ltr ML18016A3211998-02-20020 February 1998 LER 98-002-00:on 980121,solid State Protection Sys Testing Deficiency Occurred.Caused by Inadequate Review of Initial Tech Specs.Ts Testing Frequency for P-11 Permissive Revised. W/980217 Ltr ML18016A3131998-02-0909 February 1998 LER 98-001-00:on 980109,potential Condition Outside Design Basis Related to Instrument Air Sys Leak Causing SG pre- Heater Bypass Isolation Valves to Be Inoperable Was Noted. Caused by Inadequate Design Control.Generated Jco 98-01 ML18016A2641997-12-18018 December 1997 LER 97-024-00:on 971118,SSPS Testing Deficiency Was Noted. Caused by Inadequate Testing Scheme Provided by Ssps Vendor. Revised procedure.W/971218 Ltr ML18016A2501997-11-24024 November 1997 LER 97-023-00:on 920721,RCS PIV Testing Deficiency Was Noted.Caused by Failure to Consider All Testing Variables During Initial Sp Development.Surveillance Tp OST-1506 Was Revised to Incorporate Correction factor.W/971124 Ltr ML18016A2201997-10-22022 October 1997 LER 97-021-01:on 970922,discovered That Spent Fuel Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Misinterpretation of TS Requirements.Revised Daily Surveillance Procedures ML18016A2081997-10-14014 October 1997 LER 97-016-01:on 970608,reactor Trip Occurred,Due to Personnel Error While Attempting to Adjust Power Range Nuclear Instrumentation Channel Following Performance of Calorimetric.Procedures revised.W/971014 Ltr ML18016A2111997-10-14014 October 1997 LER 96-008-02:on 960425,turbine Trip/Reactor Trip Occurred. Caused by High Resistance Connection Resulting from a Phase Switch Jaw & Blade Contacts.Failed a Phase Disconnect Switch on Breaker 52-7 Replaced ML18016A1931997-09-29029 September 1997 LER 97-022-00:on 970829,TS Required Shutdown Due to Expiration of AFW Lco.Caused by Personnel Error.Completed Repairs TDAFW Pump & Returned Plant to Svc on 970831. W/970926 Ltr ML18016A1891997-09-12012 September 1997 LER 97-020-00:on 970814,inadequate Fire Protection Provided for safety-related EDG Fuel Oil Transfer Pump Cables Resulted in Operation Outside Design Basis.Caused by Engineering Oversight.Established Fire watches.W/970912 Ltr ML18016A1881997-09-12012 September 1997 LER 97-021-00:on 970814,spent Fuel Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Misinterpretation of Ts.Directions Provided to Operations.W/970912 Ltr ML18012A8641997-08-18018 August 1997 LER 97-019-00:on 970720,turbine Trip/Reactor Trip Occurred. Caused by Three Phase Fault That Collapsed Excitation Field in Main Generator,Resulting in Generator Lockout.Exciter Rotor Assembly Was replaced.W/970818 Ltr ML18012A8581997-08-0808 August 1997 LER 96-018-01:on 960903,manual Reactor Trip Occurred Due to Loss of Normal Sw.Caused by Mechanical Failure of B Water Pump & a Normal SW to Remain Running Once Manually Started.Restored a Normal SW Pump to Svc ML18012A8551997-08-0808 August 1997 LER 96-013-02:on 961028,condition Outside of Design Basis Where RWST Had Been Aligned w/non-seismically Qualified Sys Was Identified.Caused by Failure to Reconcile Operating Procedure Lineups.Established Administrative Controls ML18012A8471997-07-31031 July 1997 LER 97-018-00:on 970701,determined That Plant Procedures Had Not Received Proper Reviews & Approvals.Caused by Failure to Comply W/Plant Administrative Procedure AP-006.Counseled Involved individuals.W/970731 Ltr ML18012A8371997-07-24024 July 1997 LER 97-S01-00:on 970405,unescorted Access Inappropriately Granted to Contract Outage Workers Was Determined.Caused by Personnel Error.Access Files for Individuals Inappropriately Granted Unescorted Access Were Placed on Access Hold ML18012A8291997-07-11011 July 1997 LER 97-017-00:on 970612,failed to Recognize Inoperable Reactor Afd Monitor.Caused by Personnel Error.Operators Involved in Event Will Be Counseled Prior to Assuming Shift duties.W/970711 Ltr ML18012A8301997-07-0808 July 1997 LER 97-016-00:on 970608,reactor Trip Occurred Due to Personnel Error in Adjusting Power Range (Pr) Nuclear Instrumentation (Ni).Issued Night Order Prohibiting Pr Ni Adjustment When Redundant Channel inoperable.W/970708 Ltr ML18012A8241997-07-0202 July 1997 LER 97-015-00:on 970602,inadequate Auxiliary Feedwater Sys Flow Control Valve Surveillance Testing Deficiency Was Identified.Caused by Failure to Recognize Impact on TS 4.7.1.2.1.Readjusted AFW FCV Actuator spring.W/970702 Ltr ML18022B0181997-06-13013 June 1997 LER 97-014-00:on 970514,SI Occurred During Ssps Surveillance Testing.Caused by Inattention to Detail During Recent Rev to Surveillance Test Procedure Being Used.Revised Deficient Surveillance procedures.W/970613 Ltr ML18012A8081997-06-0909 June 1997 LER 97-013-00:on 970508,entry Into Mode-6 Without Operable Components,Resulting in TS 3.0.4 Violation Occurred.Caused by Personnel Error.Personnel Involved counseled.W/970609 Ltr ML18012A8021997-06-0606 June 1997 LER 97-023-02:on 961114,design Deficiency Was Identified in Emergency DG Protection Circuitry.Caused by Inadequate Plant Design.Revised Surveillance Test Procedures OST-1013 & OST-1073.W/970606 Ltr ML18012A8011997-06-0404 June 1997 LER 97-012-00:on 970505,determined That Previous Auxiliary Control Panel Had Not Verified Operability of Interposing Relays.Caused by Misinterpretation of Tss.Reviewed Other Remote Shutdown Panel Transfer circuitry.W/970604 Ltr ML18012A7951997-05-29029 May 1997 LER 96-023-01:on 961114,design Deficiency in EDG Protection Circuitry Was Identified.Caused by Inadequate Original Plant Design.Surveillance Test Procedures OST-1013 & OST-1073 revised.W/970529 Ltr ML18012A7891997-05-22022 May 1997 LER 97-011-00:on 970422,inappropriate TS Interpretation Resulted in Violations of ECCS Accumulator TS & Entry Into TS 3.0.3.Caused by Procedural Inadequacy.Tsi 88-001 Cancelled 970508 & Procedures revised.W/970522 Ltr ML18012A7871997-05-19019 May 1997 LER 97-010-00:on 970418,design Deficiency Determined Re Reactor Coolant Pump Motor Oil Collection Sys.Caused by RCP Ocs Design Detail.Rcp Ocs Enclosures for Each of Three Installed RCP Motors Have Been modified.W/970519 Ltr ML18012A7761997-05-0707 May 1997 LER 97-009-00:on 970407,fuse Was Removed from CR Ventilation Isolation Signal Power Supply Circuitry Due to Personnel Error.Individuals Involved Were counseled.W/970507 Ltr ML18012A7751997-05-0505 May 1997 LER 97-008-00:on 970404,safety-related AHU Not Declared Inoperable During Maintenance on Associated Temperature Switches Resulting in Violation of Ts.Caused by Incorrect Interpretation.Operations Night Order issued.W/970505 Ltr ML18012A6291997-04-24024 April 1997 LER 97-007-00:on 970325,inoperable CCW Sys TS 3.0.3 Entry Made.Caused by Combination of Procedural Inadequacies, Improper Use of Procedure Guidance & Poor Communication. Applicable Individuals counseled.W/970423 Ltr ML18022B0151997-04-17017 April 1997 LER 97-006-00:on 970318,breach Was Identified in Thermo-Lag Fire Barrier Wall Due to Inadequate Initial Design,Poor Construction Methods & Incomplete as-built Design.Visual Insp of Thermo-Lag Barrier Walls performed.W/970417 Ltr ML18012A6041997-04-0303 April 1997 LER 97-004-00:on 970304,in-plant Spent Fuel Cask Handling Activities Conducted Outside Design Basis.Caused by Lack of Understanding of Requirements.Operations Placed on Hold Pending NRC Review & Approval of procedures.W/970331 Ltr ML18012A6031997-03-31031 March 1997 LER 97-003-00:on 970227,steam Generator Low Level Protection Circuitry Outside Design Basis Occurred.Caused by Inadequate Failure Modes & Effects Analysis Performed as-built Piping Configuration for S/G Level.Review performed.W/970331 Ltr 1999-09-10
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML18017A9181999-10-0808 October 1999 LER 99-008-00:on 991008,CR Emergency Filtration Sys Tech Specs Occurred.Caused by Site Personnel Failed to Recognize That Blocking Open CR Emergency Filtration Sys.Procedures Revised.With 991008 Ltr ML18017A9151999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Shearon Harris Npp. with 991012 Ltr ML20217A9931999-09-30030 September 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data ML18017A8671999-09-10010 September 1999 LER 99-007-00:on 990811,determined That Cvis ARMs High Alarm Setpoints Were Not within TS Limit.Caused by Not Having Procedure to Verify If Cvis ARM High Alarm Setpoints Were within TS Requirements.Revised Procedures.With 990910 Ltr ML18017A8621999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Harris Nuclear Plant.With 990908 Ltr ML18016B0481999-08-0404 August 1999 LER 99-006-01:on 981124,noted Failure to Comply with TS 4.0.4 & TS 3/4.6.3, Civs. Caused by post-maint Testing That Did Not Adequately Test Control Circuitry & Verify Isolation Time Following Maint.Procedure Was Revised ML18017A8361999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Shearon Harris Nuclear Power Plant.With 990811 Ltr ML18016B0151999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Shearon Harris Npp. with 990713 Ltr ML20196H8621999-06-30030 June 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data, June 1999 Rept ML18016A9801999-06-0404 June 1999 LER 99-006-00:on 981124,failed to Comply with TS 4.0.4 & TS 3/4.6.3, Civ. Caused by post-maint Testing That Did Not Adequately Test Control Circuitry & Verify Isolation Time Following Maint.Procedure Will Be Revised.With 990604 Ltr ML18016A9851999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Shearon Harris Nuclear Plant,Unit 1.With 990614 Ltr ML18017A8981999-05-12012 May 1999 Technical Rept Entitled, Harris Nuclear Plant-Bacteria Detection in Water from C&D Spent Fuel Pool Cooling Lines. ML18016A9581999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Shearon Harris Nuclear Plant,Unit 1.With 990513 Ltr ML18016A9011999-04-12012 April 1999 Part 21 Rept Re Defect in Component of DSRV-16-4,Enterprise DG Sys.Caused by Potential Problem with Connecting Rod Assemblies Built Since 1986,that Have Been Converted to Use Prestressed Fasteners.Affected Rods Should Be Inspected ML18016A9111999-04-12012 April 1999 LER 99-005-00:on 990313,plant Exceeded ESFAS TS 3.3.2,Action 21.Caused by Inadequate Procedure Rev Preparation.Licensee Revised Applicable Maint Surveillance Test Procedure (MST-10072) to Identify TS Required Actions.With 990412 Ltr ML18016A8971999-04-0808 April 1999 LER 99-004-00:on 990312,unit Trip Was Noted.Caused by Degraded Condition of SG Water Level Flow Control Valve. Replaced Positioners on All Three FW Regulating Valves.With 990408 Ltr ML18016A8941999-04-0505 April 1999 Revised Pages 20-25 to App 4A of non-proprietary Version of Rev 3 to HI-971760 ML18016A9101999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Shearon Harris Nuclear Power Plant.With 990413 Ltr ML18016A8661999-03-31031 March 1999 Shnpp Operator Training Simulator,Simulator Certification Quadrennial Rept. ML18017A8931999-02-28028 February 1999 Risks & Alternative Options Associated with Spent Fuel Storage at Shearon Harris Nuclear Power Plant. ML18016A8551999-02-28028 February 1999 Monthly Operating Rept for Feb 1999 for Shearon Harris Npp. with 990312 Ltr ML18016A8261999-02-22022 February 1999 LER 99-003-00:on 990123,noted That Plant Was Outside Design Basis Due to Isolation of Fire Protection Containment Sprinkler Sys.Caused by Human Error.Restored Containment Sprinkler Sys to Operable Status.With 990222 Ltr ML18016A8531999-02-18018 February 1999 Non-proprietary Rev 3 to HI-971760, Licensing Rept for Expanding Storage Capacity in Harris SFP 'C' & 'D'. ML18016A8111999-02-12012 February 1999 LER 99-002-00:on 990114,RT Due to Not Removing Temporary Device from Relay Following Calibration Was Noted.Caused by Human Error.Counseled Personnel Involved in Event.With 990212 Ltr ML18016A7971999-02-0505 February 1999 LER 99-001-00:on 990106,SF Pool Water Level Was Not Maintained Greater than 23 Feet Above Stored BWR Fuel Assemblies.Caused by Fasteners Bending Under Specific Circumstances.Increased Water Level.With 990205 Ltr ML18022B0631999-02-0404 February 1999 Rev 0 to Nuclear NDE Manual. with 28 Oversize Uncodable Drawings of Alternative Plan Scope & 4 Oversize Codable Drawings ML20202J1161999-02-0101 February 1999 SER Accepting Relief Requests Associated with Second 10-year Interval Inservice Testing Program ML18016A8041999-01-31031 January 1999 Monthly Operating Rept for Jan 1999 for Shearon Harris Nuclear Power Plant.With 990211 Ltr ML18016A7941999-01-29029 January 1999 LER 98-004-01:on 980313,identified Design Deficiency Re Potential Runout of Tdafwp.Caused by Inadequate Original AFW Sys Design.Operability Evaluation Was Completed on 980313 & Addl Engineering Analysis Was Performed by Vendor ML18016A7801998-12-31031 December 1998 Monthly Operating Rept for Dec 1998 for Shearon Harris Npp. with 990113 Ltr ML18016A7671998-11-30030 November 1998 Monthly Operating Rept for Nov 1998 for Shnpp,Unit 1.With 981215 Ltr ML18016A9731998-11-28028 November 1998 Changes,Tests & Experiments, for Harris Nuclear Plant.Rept Provides Brief Description of Changes to Facility & Summary & of SE for Each Item That Was Implemented Under 10CFR50.59 Between 970608-981128.With 990527 Ltr ML18016A8351998-11-28028 November 1998 ISI Summary 8th Refueling Outage for Shearon Harris Power Plant,Unit 1. ML18016A7411998-11-25025 November 1998 Rev 1 to Shnpp Cycle 9 Colr. ML18016A7211998-11-17017 November 1998 LER 98-007-00:on 981023,turbine Control Anomaly Caused Manual Rt.Caused by Failure to Incorporate Verbal Vendor Guidance in Operating Procedures.Addl Vendor Guidance Will Be Verified & Added to Procedures.With 981117 Ltr ML18016A7071998-11-0303 November 1998 Rev 0 to Harris Unit 1 Cycle 9 Colr. ML18016A7201998-10-31031 October 1998 Monthly Operating Rept for Oct 1998 for Shearon Harris Nuclear Power Plant.With 981113 Ltr ML20154F8701998-10-0606 October 1998 Safety Evaluation Authorizing Proposed Alternative to Requirements of OMa-1988,Part 10,Section 4.2.2.3 for 21 Category a Reactor Coolant Sys Pressure Isolation Valves ML18016A6201998-09-30030 September 1998 Monthly Operating Rept for Sept 1998 for Harris Nuclear Power Plant.With 981012 Ltr ML18016A5971998-09-21021 September 1998 Rev 1 to Harris Unit 1 Cycle 8 Colr. ML18016A5881998-08-31031 August 1998 Monthly Operating Rept for Aug 1998 for Shnpp,Unit 1.With 980914 Ltr ML18016A5071998-07-31031 July 1998 Monthly Operating Rept for Jul 1998 for Shearon Harris Nuclear Plant.W/980811 Ltr ML18016A9431998-07-0707 July 1998 Rev 1 to QAP Manual. ML18016A4841998-07-0707 July 1998 LER 97-002-01:on 970207,determined That Cold Weather Conditions Resulted in Mfiv Being Potentially Inoperable During Period 970117-20.Caused by Inadequate Design of HVAC Sys.Implemented Mods to Steam Tunnel HVAC Sys ML18016A9371998-06-30030 June 1998 Technical Rept on Matl Identification of Spent Fuel Piping Welds at Hnp. ML18016A4861998-06-30030 June 1998 Monthly Operating Rept for June 1998 for SHNPP.W/980715 Ltr ML18016A4701998-06-30030 June 1998 LER 97-021-03:on 980210,discovered That SFP Water Level Had Not Been Verified Greater than 23 Feet Above BWR Fuel Assemblies.Caused by Misinterpretation of TS Requirements. Will Submit TS Change Request to Revise TS 3.9.1.11 ML18016A4491998-06-0808 June 1998 LER 98-006-00:on 980508,failure to Perform Insp & Preventive Maint on MCCB as Required by TS Was Noted.Caused by Inadequate Sps.Tested 9 Pressurizer Heater Bank Breakers by Cycling each.W/980608 Ltr ML18016A4521998-05-31031 May 1998 Monthly Operating Rept for May 1998 for Shearon Harris Nuclear Power Plant.W/980612 Ltr ML18016A7711998-05-26026 May 1998 Non-proprietary Rev 2 to HI-971760, Licensing Rept for Expanding Storage Capacity in Harris Spent Fuel Pools 'C' & 'D'. 1999-09-30
[Table view] |
Text
0 REGULATORY INFORMATION DISTRIBUTION SYSTEM (BIDS)
ACCESSION NBR: 8802230245 DOC. DATE: 88/02/15 NOTARIZED: NO DOCKET FACIL: 50-400 Shearon Harris Nuclear Poeer Planti Unit ii Carolina 05000400 AUTH. NAME - AUTHOR AFFILIATION HOWE'. Carolina Poeer & Light Co.
WATSONI R. A. Carolina Power & Light Co.
RECIP. NAME'ECIPIENT AFFILIATION
SUBJECT:
LER 88-001-00: on 880115'mergency operating procedure (EOP) deficiency for seitchover to recirculation after LOCA discovered. Caused bg failure to incorporate FSAR change into plant procedures. EOPs revised. W/880215 ltr.
DISTRIBUTION CODE: IE22D COPIES RECEIVED:LTR J ENCL I SIZE: ID TlTLE: 50. 73 Licensee Event Report (LER)z Incident Rpti etc.
NOTES: Application for permit reneeal f iled. 05000400 REC IP IENT COPIES 'RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-1 LA 1 PD2-1 PD 1 1 BUCKL'EY> B 1 1 INTERNAL: ACRS MICHELSON 1 1 ACRS MOELLER 2 2 AEOD/DOA 1 1 AEOD/DSP/NAS 1 1 AEOD/DSP/RQAB 2 2 AEOD/DSP/TPAB ARM/DCTS/DAB 1 1 DEDRO 1 NRR/DEBT/*DS 1 0 NRR/DEST/CEB 1 1 NRR/DEST/ELB 1 NRR/DEST/ I CSB 1 1 NRR/DEST/MEB 1 1 NRR/DEST/MTB 1 NRR/DEST/PSB 1 1 NRR/DEST/RSB 1 1 NRR/DEST/SGB 1 1 NRR/DLPG/HFB 1 1 NRR/DLPG/GAB 1 1 NRR/DOEA/EAB 1 NRR/DREP/R*B 1 1 NRR/DREP/RPB 2 2 NRR/DRIS/SIB 1 NRR /P MAS/ ILR8 1 1 1 RES TELFORDi J 1 1 ES/DE/EIB 1 1 RES/DRPS DIR 1 1 RGN2 FiLE 01 1 1 EXTERNAL: EG&G GROHi M 5 5 FORD BLDG HOYLE A 1 1 H ST LOBBY WARD 1 1 LPDR 1 1 NRC PDR 1 1 NSIC HARR IS. J 1 1 NSIC NAYS> G 1 TOTAL NUMBER QF.COPIES REQUIRED: LTTR 46 ENCL 45
NRC Form 355 UA. NUCLEAR REOULATORY COMMISSION (903) APPROVED OMB NO. 31500)OI EXPIRES: 5/31/SS LICENSEE EVENT REPORT (LER)
DOCKET NUMBER (2) PA E 3 FA<<L>>YNA"<<>> SHEARON HARRIS POWER PLANT UNIT ONE 0 5 0 0 0 1 OF EMERGENCY OPERATING PROCEDURE DEFICIENCY FOR SWITCHOVER TO RECIRCULATION AFTER A N
EVENT DATE (5) LER NUMBER (SI REPORT DATE'7) OTHER FACILITIES INVOLVED (Sl MONTH OAY YEAR YEAR >c SSOUKNTSAL Revs~
'cc: NUMeeR MONTH DAY YEAR FACILITYNAMES OOCKFT NUMBER(SI NUMBER 0 5 0 0 0 0 1 1 588 88 001 0 0 0 2 1 5 8 8 0 5 0 0 0 THIS REPORT IS SUBMITTED PURSUANT TO THE REOUIREMENTS OF 10 CF R (I: (Ch<<k one or more of the follovflnPI (11)
OPERATING MODE (9) 20A02(e) 20AOS(cl 50.734) (2) (Iv) 73.71(e)
POWER 20AOS (e)(1 l(0 SOM(cl(1) 50.73(el(2)(v I 73.71(cl LEUEL 1 0 0 OTHER (Specify In Aestrect (10) 20AOS(el(1)(4) 50.35(cl(2) 50.73(el(2)(vli) helovr end In Text, HIIC Form 20A05(e) (I l(iii) 50.73(el(2)(i) 50.73(el(2)(viiil(A) SSSA) 20AOS(el(1 l(iv) 50.73(e l(2) (ii) 50,73(e) (2((vill)(8) 20AOS (e I (1 I (v I 50.73(el(2) (Iii) 50.73(e) (2 I (x)
LICENSEE CONTACT FOR THIS LER I12)
NAME TELEPHONE NUMBER ANDREW HOWE SR. ENGINEER REGULATORY COMPLIANCE AREA CODE 91 936 2- 2719 COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT (13)
REPORTABLE; >N5%:, MANUFAC. EPORTASLE CAUSE SYSTEM COMPONENT MANUFAC TURER TO NPRDS (c)'>
xg
. CAUSE SYSTEM COMPONENT TUBER TO NPRDS SUPPLEMENTAL REPORT EXPECTED Ile) MONTH S~S DAY YEAR EXPECTED SUBMISSION DATE (15)
YES (If yes, complete EXPECTED SIIShtISSIOH DATE/ NO ABSTRACT (LImit to tc00 speces, I e., epproxlmetely fifteen tlnple specs typervrltten Ilneel (19)
On January 15, 1988, it was discovered that a procedure deficiency had previously existed in the Emergency Operating Procedures (EOPs) which could have resulted in the failure of the Emergency Core Cooling System (ECCS) during the recirculation phase of an accident, under a scenario of a single failure of one Residual Heat Removal Pump (RHRP). The deficiency involved an improper valve lineup which could cause a RHRP to exceed its design flow limit during ECCS recirculation, if one of the two RHRPs had failed during a loss of coolant accident (LOCA) leaving only one operating RHRPP and if the LOCA was sufficiently large to completely depressurize the Reactor Coolant System.
This procedure deficiency resulted from the failure to completely incorporate into plant procedures a change made to the Final Safety Analysis Report.
The deficiency existed beginning in December of 1986, when the EOP containing the error was approved, and initial operation of the plant began. When the safety significance of the discrepancy was discovered, the EOPs were revised to correct the error. This occurred on December 16, 1987.
Other FSAR changes made in this time period involving a change to procedures were reviewed to ensure they were properly implemented. Members of the Plant Nuclear Safety Committee have been advised of this situation and reminded of their responsibility regarding the reportability of such situations'RC 8802230245 880215 PDR ADOCK 05000400 S
Form 355
NRC fIfIA SCCA U.S. NUCLEAR REOULATORY COMMISSION (043 l LICENSEE EVENT REPORT {LER) TEXT CONTINUATiON APPROVED OMS NO. 3150WIOC EXPIRES: 0/31/(6 fACILITYNAME ill DOCKET NUMSER (2I LER NUMSER (5) PACE (3I YEAR CCOVCNT/AL AEVI5ION NUM C II Nl/M N SHEARON HARRIS NUCLEAR POWER PLANT C UNIT ONE 0 0 0 2 OF 0 o s o o o 4 0 0 8 8 0 0 1 6 TEXT ////IIPIP N>>cf /I IPCMCPI/. VffR(5C/fnel H/IC form 3HIA'f/(IT)
DESCRIPTION:
Note.'The following drawings supplement the narrative of this report:
Attachment A - ECCS Recirculation Flowpath Existing Prior to September 1986 Attachment B ECCS Recirculation Flowpath Required in FSAR After September 1986 Attachment C - ECCS Recirculation Flowpath Implemented in Procedures, December 1986 The switchover procedure for transferring the Emergency Core Cooling System (ECCS) from injection to recirculation is outlined in FSAR Table 6.3.2-6. The initial practice required closing isolation valves to separate the ECCS headers into two separate trains, thus providing protection for passive failures of the piping. The resulting valve lineup for recirculation is shown in Attachment A. On September 27, 1985, and on August 21, 1986, Westinghouse Electric Corporation, the Nuclear Steam Supply System designer for the Shearon Harris Nuclear Power Plant (SHNPP), issued letters (serial CQL-9018 and CQL-9445) to Ebasco Services, Inc., the architect/engineer for SHNPP. The letters documented recommendations for changes to the procedure described in FSAR Table 6.3.2-6 for the switchover. Westinghouse recommended deletion of the procedure steps which separated the two ECCS trains, since these steps did not provide complete passive failure protection, and since their elimination would allow a single RHRP to supply both CSIPs. In addition, the second correspondence identified the need for new check valves to be installed in the piping connecting the discharge of an RHRP to the CSIP suction, to prevent potential backflow through an idle RHRP during recirculation.
These proposed changes were approved for implementation at SHNPP, since they improved operational flexibility following an accident. In addition, a separate issue regarding requirements for local leak rate testing (LLRT) on ECCS containment penetrations was also resolved by implementing this proposed change.
NRC fORM 3CCA eU.S.OPO:1055W52l 530/155 (043 I
NRC POrAl 344A US. NUCLEAR REOULATORY COMMISSION 104)3)
LICENSEE EVENT REPORT ILER} TEXT CONTINUATION APPROVED OMB NO. 3150&104 EXPIRES: 8/31/IEI PACILITY NAME 11) DOCKET NUMBER I2) LER NUMBER (4) PACE (3)
SHEARON HARRIS NUCLEAR POIItER PLANT yEAR ~sR 44QVENT/AL
~?? NVM ER i . /IEV/4/CN
)@ NVM EN UNIT ONE o s o o o4 00 8 8 0 1 0 0 0 30F 0 6 TEXT /8'/NP/0 N>>C ~ /4/PIP/PPE P44 OANOnel ///IC Ans 3034'4/ IIT)
DESCRIPTION: (continued)
An FSAR change (serial HPOS-845) was initiated to incorporate these changes.
As part of the review of these changes, Technical Support determined that a single RHRP could not supply two CSIPs and both low pressure ECCS injection headers, as the proposed recirculation lineup required. However, by isolating one of the two low pressure safety injection (LPSI) header containment isolation valves, an acceptable configuration was created. This revised lineup demonstrated that the RHRP would not run out (Preoperational Test 2085-P-05, completed October 5, 1986). Therefore, the FSAR change included the new requirement to close one of the two LPSI containment isolation valves to ensure that runout of the RHRP would not occur during recirculation if the other RHRP failed.
This change was incorporated into the FSAR change which was approved on September 24, 1986. A letter was also submitted to the NRC describing this change.
The change required significant revisions be made to the EOPs', however, due to other commitments, revisions were already in progress. The additional changes required due to the FSAR change were not therefore formally identified and tracked. On December 22, 1986, Revision 2 to procedure EOP-EPP-010, Transfer to Cold Leg Recirculation, was issued. However, the revision did not fully implement the requirements of the FSAR in that the requirement to close one LPSI containment isolation valve, identified in FSAR change HPOS-845, was not included. The procedure change package references this FSAR change in its safety analysis, but the engineers developing the procedure revision were not fully cognizant of all the new requirements.
The SHNPP On-site Nuclear Safety (ONS) unit was responsible for the review of INPO Significant Event Reports (SER), and during review of SER 2-87, they identified the discrepancy between the FSAR and the EOPs. On July 10, 1987, an action item was established for the plant engineering department to evaluate the discrepancy to determine whether the procedure or the FSAR was inaccurate. On December 3, 1987, the engineering department confirmed the deficiency was in the EOPs.
NRC PORM 344*
1083) t U.S.OPO:1085.0524 538/455
NRC Fans 300A US. NUCLEAR REOULATORY COMMISSION (003 l LICENSEE EVENT REPORT ILERI TEXT CONTINUATION APPROVEO OMS NO. 3IEOW(04 EXPIRES: 0/31/%
FACILITY NAME (Il OOCKET NUMSER (2l LER NUMSER (0) ~ AOE I3) saavENTIAL sKV>>ION NUM ER nvM Es SHEARON HARRIS NUCLEAR POWER PLANT UNIT ONE 0 5 0 0 0 4 0 0 8 8 0 1 0 004 oF0 TEXT ///more <<>>ca II mavkw/, oaa Ada/h/ana///hC Fons 3///)A3/ (IT)
DESCRIPTION: (continued)
Separately, Operations personnel noted that the Monitor Light Box (MLB) for ECCS recirculation was engraved to require one LPSI containment isolation valve to be close while the other was open. Believing this to be a simple engraving error, a Plant Change Request (PCR) (serial PCR-2384) was initiated on September 25, 1987, to change the engraving to require the valve to be open during recirculation, in agreement with the plant EOPs. The PCR was rejected by Technical Support personnel, since they were aware of the previous FSAR change requiring the valve to be closed to prevent RHR pump runout. The Operations engineer who initiated the PCR then wrote a feedback report (serial 305) in accordance with plant procedure OMM-001, Operations " Conduct of Operations, on October 26, 1987. A procedure change was determined to be required, and was to be addressed in the next revision which was to be issued in the fall of 1988.
In both cases, personnel were not cognizant of the safety significance of the procedure deficiency.
However, when ONS received the response for INPO SER 2"87 from engineering on December 3, 1987, the ONS unit contacted Operations and made them aware of the serious nature of the deficiency. A change to procedure EOP-EPP-010 was issued on December 16, 1987, correcting the error and making the procedure consistent with the FSAR. In addition, procedure EOP-EPP-003, Loss of All AC
~
Power Recovery with Safety Injection Required, which also addresses the recirculation lineup, was issued on January 6, 1988.
On January 15, 1988, this matter was discovered by Regulatory Compliance personnel. The situation existing for nearly one year in which the emergency operating procedures were in disagreement with the FSAR was investigated and determined to be reportable.
SAFETY SIGNIFICANCE:
The ECCS, and hence all procedures governing operation of this system, were required to be in place when the plant first entered Mode 4 in December of 1986, as per Technical Specification 3.5.3. In the event of a large break loss of coolant accident simultaneous with the single failure of an RHRP, when the recirculation phase of ECCS operation was initiated in accordance with plant procedures, the plant would have been in an unanalyzed condition.
The single operating RHRP could have exceeded its design flow limit, which would cause the RHRP to trip on overcurrent, subsequently causing the failure of the CSIPs, since these pumps rely on the RHRP as the source of water for recirculation operation. Operator action outside of plant procedures would have been required to recover the situation. The RHRP would be available once the operator had reset the overcurrent trip.
NRC FORM 340A o U.S.OPO:10SHH2A.S30/4dd (043)
NRC FOtIA 3EEA, UAL NUCLEAR REOULATORY COMMISSION
/043)
LICENSEE EVENT REPORT {LER) TEXT CONTINUATION APPROVED OMS NO. 3180W104 EXPIRES: 8/31/88 FACILITY NAME III DOCKET NUMSER I2) LER NUMSER (EI PACE ISI SHEARON HARRIS NUCLEAR POWER PLANT YEAR @.: SEQUENTIAL " IIEVISION NUM EII 8 NUM EII UNIT ONE 0 5 0 0 0 P 0 0 001 0 0 05 o" 0 TEXT /I/ mSIS SPECS /S /NPIPWE IMP SdtAMNM//VIICAVm 3R/A3/ I ITl SAFETY SIGNIFICANCE: (continued)
The following indications would have been available to the operator to alert him of the problem'.
Flow indication for the RHRP Motor amperage indication for the RHRP Alarms for the MLB due to the valve lineup error Alarm for the RHRP tripping The condition is reportable in accordance with 10CFR50.73(a)(2)(v) as a procedural error which could have prevented the fulfillment of the safety function of systems which mitigate the consequences of an accident.
CAUSE'here is no single reason that this procedure deficiency came into existence, but the following contributed to the error.
- 1. Personnel responsible for the EOPs were aware of the Westinghouse proposals to revise the ECCS recirculation lineup, and when the FSAR was changed to implement this new lineup the additional requirement to close the LPSI isolation valve was not noted. The modification to close one of the two LPSI containment isolation valves affected only one page of a change package which was 32 pages in length, and the majority of this package discussed containment isolation valve design, not ECCS recirculation procedures.
- 2. Changes made to the FSAR, which would require changes to plant procedures, were not routinely identified and tracked prior to licensing of the plant due to the significant number of changes and due to the fact that procedures were being revised prior to initial use in preparation for the operation of the plant.
- 3. FSAR changes are not immediately made available in the copies of the FSAR, since updates are only required annually by regulations.
The discrepancy between the FSAR and EOPs was identified by many groups during 1987. However, the technical issue as to which document was accurate was not obvious. Investigation of the discrepancy was not given appropriate urgency, given the potential consequences of the discrepancy. When the investigation was completed, the problem was corrected within a reasonable period of time, but the potential reportability of the situation was not identified.
No similar situations have previously occurred.
NIIC POIIM 344A AU.S.OPO;1080O824 838/4dd I843 I
NRC form 388A US. NUCLEAR REOULATORY COMMISSION IE83 I LICENSEE EVENT REPORT (LERI TEXT CONTINUATION APPROVED OMS NO. 3180&)85 EXPIRES: 8/3) IES FACILITY NAME III DOCKET NUMSER Ill LER NUMSER (8) IIAOE I3)
SHEARON HARRIS NUCLEAR POWER PLANT YEAR 5COVCNTIAL NUM 5 Ir IICVI5ION NVM CII UNIT ONE o s o o o 400 0 1 000 oF 06 TEXT INmore e>>ce ic eeerrierf. Iree FIF8eovNF HRC forrrr ~'cl I IT)
CORRECTIVE ACTIONS:
The EOPs were revised prior to the discovery of this situation.
The events which led to this procedure deficiency occurred prior to licensing of the plant. Upon issuance of the operating license, many changes went into effect regarding how plant design changes are controlled:
Changes to the plant components which require a PCR receive a complete safety analysis in accordance with 10CFR50.59.
PCRs are reviewed by the appropriate units to determine the impact on plant procedures for which they are responsible.
FSAR changes now follow, rather than precede, the changes made to the plant and/or procedures.
The following additional measures are to be taken'.
Changes to the FSAR approved in 1986 have been reviewed to verify that those changes which alter procedures described in the FSAR were properly implemented in the plant. No similar situations were discovered.
Members of the Plant Nuclear Safety Committee have been informed of this event and reminded of their responsibility to ensure potentially reportable items are brought to the attention of management.
NIIC POIIM 355A *U.S.OPO;1888 0 825 838MSS
)183)
BIT LER 88-001 ATTACHMENT A COLD LEG ECCS RECIRCULATION FLOWPATH EXISTING PRIOR TO SEPTEMBER 1986 1B-SB HPSI-IOT LEG 1C-SAB INSIDE CONTAINMENT CONTAINMENT 1A-SA RECIRCULATICN IfSl-COLD LEG SUMPS CHARGI NG/Sl PUMPS I
HX LPSI-COLD LES 1B-SB LPSI" RHR PUMPS HOT LEG HX LPSI-COLD LEG IA-SA INSIDE CONTAINMENT
BIT LER 88-001-00 ATTACHMENT B IPSI.
ECCS RECIRCULATION FLOWPATH COLO QG REQUIRED IN FSAR AFTER SEPTEMBER 1986 I B-SB HPSI-IO'I LIG 1C-SAB INSIDE CONTAINt1ENT CONTAINMENT 1A-SA PEPSI RECIRCULATION COLO llG SUl1P8 CHARGING/S I PUMPS isi-~I HX U'SI-COLD LEG IB-SB
~:
LPSI-RHR PUMPS INT LEG lsi-swo HX LPSI-ID LEG IA-SA INSIDE CONTAINMENT
BIT LER 88-001-00 ATTACHMENT C ICOSI ECCS RECIRCULATION FLOWPATH CQ.D GG IMPLEMENTED IN PROCEDURE, DECEMBER 1986 'I B-SB HPSI-HOT LfG 1C-SAB INSIDE CONTAINt1ENT CONTAIHMEHT 1A-SA tPSI RECIRCULATION COLD LEG SUMPS CHARGING/Sl PUMPS LPSI-COLDLEG 1B-SB LPSI-RHR PUMPS HOT LEG HX LPSI-COLD lEG IA-SA INSIDE CONTAINMENT
Carolina Power & Light Company HARRIS NUCLEAR PROJECT P.O. Box 165 New Hill, NC 27562 FEB i." l9se File Number'SHF/10-13510C Letter Number: HO-880057 (0)
U.S. Nuclear Regulatory Commission ATTN: NRC Document Control Desk Washington, DC 20555 SHEARON HARRIS NUCLEAR POWER PLANT UNIT 1 DOCKET NO. 50-400 LICENSE NO. NPF-63 LICENSEE EVENT REPORT 88-001-00 Gentlemen.'n accordance with Title 10 to the Code of Federal Regulations, the enclosed Licensee Event Report is submitted. This report fulfills the requirement for a written report within thirty (30) days of a reportable occurrence and is in accordance with the format set forth in NUREG-1022, September, 1983.
R. A. Watson Vice President Harris Nuclear Project MGW:sbg Enclosure cc: Dr. J. Nelson Grace (NRC - RII)
Mr. B. Buckley (NRR)
Mr. G. Maxwell (NRC - SHNPP)
MEM/LER-88"001/1/Osl