MONTHYEARML23184A0862023-07-11011 July 2023 6/23/2023 Summary of Pre Application Public Meeting with Xcel Energy on Prairie Island ISFSI Amendment Application ML23179A2102023-06-28028 June 2023 Summary of June 5, 2023, Public Meeting with Northern States Power Company Regarding Neutron Fluence Values for Reactor Pressure Vessel Welds ML23157A0232023-06-0606 June 2023 Summary of the May 24, 2023, Public Outreach to Discuss the NRC 2022 End-of-Cycle Plant Performance Assessment of Prairie Island Nuclear Generating Plant, Units 1 and 2 ML23123A3942023-05-15015 May 2023 Summary of Public Meeting with Northern States Power Company Regarding Planned License Amendment Request to Revise Technical Specification 3.7.8, Cooling Water System ML22130A7172022-05-10010 May 2022 Summary of the May 3, 2022, Public Outreach to Discuss the NRC 2021 End-Of-Cycle Plant Performance Assessment of Monticello and Prairie Island Nuclear Generating Plant, Units 1 and 2 ML21294A0442021-11-0808 November 2021 Summary of Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to a License Amendment to Extended the Allowed Outage Time for the Vertical Motor Driven Cooling Water System Pump ML21229A1692021-08-23023 August 2021 Summary of August 11, 2021, Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to a Planned License Amendment Allow Bypass Testing of the Power Range Nuclear Instrumentation System Channels ML21167A1842021-06-16016 June 2021 Summary of the June 9, 2021, Public Outreach to Discuss the NRC 2020 End-Of-Cycle Plant Performance Assessment of Monticello Nuclear Generating Plant and Prairie Island Nuclear Generating Plant, Units 1 and 2 ML21137A1042021-05-20020 May 2021 Summary of May 6, 2021, Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to a Planned License Amendment to Transition to a 24 Month Operating Cycle ML21040A4612021-02-11011 February 2021 Summary of February 3, 2021, Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to a Planned License Amendment to Combine the Emergency Plans and Create a Common Emergency Operations Facility ML20296A2382020-11-0303 November 2020 Summary of Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to the License Amendment to Adopt TSTF-505 Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b ML20274A2442020-10-16016 October 2020 Summary of 9/23/2020 Meeting with Northern States Power Co., Doing Business as Xcel Energy, on Potential License Exemption Request Related to Biennal Emergency Preparedness Exercise for Prairie Island Nuclear Generating Plant, Units 1 & 2 ML20216A6452020-08-0303 August 2020 Summary of the July 16, 2020, Public Webinar to Discuss the NRC 2019 End-of-Cycle Plant Performance Assessment of the Prairie Island Generating Plant ML20114E2302020-04-23023 April 2020 Meeting Summary from Call with S. Beimers Mnshpo and NRC January 2020 Prairie Island ISFSI EA ML20111A1322020-04-21021 April 2020 April 9, 2020, Summary of Meeting with Northern States Power Company, Doing Business as Xcel Energy, on Potential License Amendment Request Related to Adopt TSTF-569 at Prairie Island Nuclear Generating Plant, Unit 1 and 2 ML20057D3912020-03-0909 March 2020 Summary of February 18, 2020, Meeting with Northern States Power Company, Doing Business as Xcel Energy, on Potential License Ament Request Related to Low Temperature Overpressurization Protection ML19347D1592020-01-0707 January 2020 Summary of December 12, 2019, Meeting with Northern States Power Co., Doing Business as Xcel Energy, and Tennessee Valley Authority Planned License Amendment Requests for Prairie Island, Units 2 and 2, and Watts Bar, Units 1 and 2 ML19289A5322019-10-28028 October 2019 Summary of September 26, 2019, Teleconference with Northern States Power Company on Potential License Amendment Request to Adopt TSTF-505, Revision 2 ML19210D5432019-08-20020 August 2019 Summary of Teleconference with Northern States Power Company on Potential License Amendment Request to Adopt Probabilistic Risk Assessment Model ML19136A0272019-05-15015 May 2019 Memorandum to C. Regan Summary of March 28, 2019, Public Meeting with Xcel Energy to Discuss Seismic Consideration for a Proposed License Amendment Increasing the Amount of Special Nuclear Material Authorized for Storage at Prairie Island I ML19058A4672019-03-11011 March 2019 Summary of Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to the Amendment Request to Modify Renewed Facility Operating License Paragraph 2.C(4)(c) ML18065A5582018-03-12012 March 2018 Summary of February 20, 2018, Teleconference with Northern States Power Company, Doing Business as Xcel Energy, on Potential License Amendment Request to Adopt TSTF-425 ML17341A1292017-12-11011 December 2017 Summary of Meeting with Northern States Power Company, Doing Business as Xcel Energy, on Changes to the Security Plans at the Monticello Nuclear Generating Plant and Prairie Island Nuclear Generating Plant, Units 1 and 2 ML17261B0362017-09-25025 September 2017 Meeting with Northern States Power Company, Doing Business as Xcel Energy, on Potential Digital Feedwater Modifications at Prairie Island Nuclear Generating Plant, Units 1 and 2 ML17235B1802017-08-23023 August 2017 Summary of Open House to Discuss the 2016 End-Of-Cycle Plant Performance Assessment of Prairie Island ML17209A1192017-07-17017 July 2017 Summary of July 17, 2017, Meeting with Northern States Power Company, Doing Business as Xcel Energy, on Potential License Amendment Request Related to Heavy Lifting Devices L-PI-17-014, Summary of Public Meeting and Plan for NRC Request for Additional Information Regarding License Amendment Request for Spent Fuel Pool Criticality Technical Specification Changes (CAC Nos. MF7121...2017-04-19019 April 2017 Summary of Public Meeting and Plan for NRC Request for Additional Information Regarding License Amendment Request for Spent Fuel Pool Criticality Technical Specification Changes (CAC Nos. MF7121... ML17093A6012017-04-0606 April 2017 March 9, 2017, Summary of Meeting with Northern States Power Company, Doing Business as Xcel Energy, Related to the Spent Fuel Pool Criticality License Amendment Request ML17034A1202017-02-0909 February 2017 Summary of January 24, 2017, Meeting with Northern States Power Company, Doing Business as Xcel Energy, on Potential Revision to the Emergency Action Level ML16111B1912016-04-28028 April 2016 Summary of Meeting with Northern States Power Company, a Minnesota Corporation, Doing Business as Xcel Energy, on National Fire Protection Association (NFPA) 805 License Amendment Request ML15271A2072015-10-0202 October 2015 July 9, 2015 Summary of Closed Meeting Between Representatives of the U.S. Army Corps of Engineers, U.S, Nuclear Regulatory Commission and Northern States Power Company- Minnesota to Discuss Flood Analysis Associated with Monticello Nuclear ML15141A5092015-05-21021 May 2015 Meeting Summary with Public to Discuss the Results of the 2014 Problem Identification and Resolution Inspection for Prairie Island Nuclear Generating Plant ML15107A0592015-05-15015 May 2015 Summary of the April 14, 2015, Public Meeting with Xcel Energy and Westinghouse to Discuss a Future License Amendment Request Regarding the Use of Ifba Rods in Nuclear Fuel at the Prairie Island Nuclear Generating Plant ML15131A4482015-05-0707 May 2015 Reactor Oversight Process Task Force FAQ Log - April 16, 2015 ML14220A2832014-09-0808 September 2014 Summary of August 5, 2014, Closed Meeting Between Representatives of the U.S. Army Corps of Engineers, NRC, and Northern States Power Company - Minnesota to Discuss Flooding Analysis Associated with Monticello and Prairie Island Nuclear Gen ML14223A8012014-08-11011 August 2014 Public Meeting Summary to Discuss the 2013 Performance of Prairie Island Nuclear Generating Plant Units 1 and 2 ML14227A8852014-07-0202 July 2014 E-mail P Longmire, NRC, Re e-mail Fr Samuel Chesnutt, Xcel Energy, Re Meeting Summary for the June 16, 2014 Prairie Island ISFSI License Renewal Application RAI Discussion ML14153A0252014-06-20020 June 2014 Meeting Summary - Public Meeting on May 16, 2014, to Discuss Xcel Energy'S Flood Hazard Reevaluation Extension Request for the Monticello and Prairie Island Nuclear Generating Plants ML14168A0182014-05-16016 May 2014 Xcel Energy Responses to NRC Questions Regarding Flood Hazard Reevaluation Report Extension Requests ML14056A4942014-03-10010 March 2014 Summary of the February 19, 2014, Pre-Application Meeting to Discuss the Diesel Generator Voltage and Frequency Limits License Request ML13210A3022013-07-29029 July 2013 Summary of Public Meeting with Northern States Power Company to Discuss the 2012 Prairie Island Nuclear Generating Plant End-of-Cycle Performance Assessment ML13171A2472013-06-20020 June 2013 7/11/2013 - Notice of Public Meeting to Discuss 2012 End-Of-Cycle Performance Assessment for Prairie Island Nuclear Generating Plant, Units 1 and 2 ML13004A3722013-01-11011 January 2013 December 6, 2012, Summary of Meeting to Discuss the Licensee'S Proposed FLEX Strategy in Response to NRC Order EA-12-049 ML12326A9702012-11-21021 November 2012 Summary of October 24, 2012, Meeting with the Northern States Power Company, D/B/A Excel Energy Regarding Security Requirements and Changes Pertaining to Prairie Island TAC L24689 W/ Encl 1 (Attendees) and Encl 2 (Agenda) ML12292A4202012-11-0707 November 2012 September 27, 2012 - Summary of Pre-Application Meeting to Discuss the Diesel Generator Voltage and Frequency Limits License Amendment Request ML12214A2332012-07-31031 July 2012 July 17, 2012 Summary of Public Meeting to Discuss the Prairie Island Nuclear Generating Plant, Units 1 and 2, End-of-Cycle Plant Performance Assessment ML12121A5842012-05-17017 May 2012 Meeting Summary with Northern States Power Co, to Discuss the National Fire Protection Association Standard 805 (NFPA 805) License Amendment Request ML12128A4152012-05-14014 May 2012 Summary of Conference Telephone Call Regarding the 2012 Steam Generator Tube Inspections ML1124207612011-09-20020 September 2011 Summary of Pre-Application Meeting to Discuss the Future Extended Power Uprate License Amendment Request ML1122005212011-08-10010 August 2011 6/22/2011 Summary of Pre-Application Meeting Regarding the Diesel Fuel Oil System License Amendment Request 2023-07-11
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION REGION III 2443 WARRENVILLE ROAD, SUITE 210 LISLE, IL 60532-4352 July 21, 2010 EA-10-070 LICENSEE: Northern States Power Company, Minnesota FACILITY: Prairie Island Nuclear Generating Plant
SUBJECT:
MEETING
SUMMARY
FOR REGULATORY CONFERENCE On July 13, 2010, representatives of Northern States Power Company (Xcel Energy), the licensee for Prairie Island Nuclear Generating Plant, Units 1 and 2, met with U. S. Nuclear Regulatory Commission (NRC) personnel in the Region III office located in Lisle, Illinois, to discuss the apparent violation identified in NRC Inspection Report 05000282/2010-010; 050000306/2010010. The regulatory conference was held at the request of the licensee.
The purpose of the meeting was to discuss a potentially greater-than-green item regarding the protection of safety-related systems following a turbine building flood.
The licensee discussed Prairie Island Nuclear Generating Plants licensing and design basis for internal flooding, along with a discussion of their understanding of licensing commitments. The licensee also presented their significance determination evaluation along with corrective actions that will be implemented to improve the station. The licensees position was that Prairie Island Nuclear Generating Plant remained in compliance with all NRC regulations regarding high energy line breaks and internal flooding.
The attendance list is attached to this summary. Also, a copy of the licensees slides presented during the conference can be found in the Agencywide Documents Access and Management System (ADAMS) as ML101890903.
Northern States Power Company, Minnesota There were five members of the public present at this meeting or via teleconference. In accordance with 10 CFR 2.390 of the NRCs Rules of Practice, a copy of this summary and its enclosure will be made available to the Public.
Sincerely,
/lRA/
Robert J. Orlikowski, Chief (Acting)
Branch 4 Division of Reactor Projects Docket Nos. 50-282; 50-306;72-010 License Nos. DPR-42; DPR-60; SNM-2506
Enclosure:
Attendance List cc w/encl: Distribution via ListServ
Northern States Power Company, Minnesota There were five members of the public present at this meeting or via teleconference. In accordance with 10 CFR 2.390 of the NRCs Rules of Practice, a copy of this summary and its enclosure will be made available to the Public.
Sincerely,
/RA/
Robert J. Orlikowski, Chief (Acting)
Branch 4 Division of Reactor Projects Docket Nos. 50-282; 50-306;72-010 License Nos. DPR-42; DPR-60; SNM-2506
Enclosure:
Attendance List cc w/encl: Distribution via ListServ See Previous Concurrences DOCUMENT NAME: G:\PRAI\Prairie Island Reg Conference meeting letter July 2010.docx G Publicly Available G Non-Publicly Available G Sensitive G Non-Sensitive To receive a copy of this document, indicate in the concurrence box "C" = Copy without attach/encl "E" =
Copy with attach/encl "N" = No copy OFFICE RIII RIII NAME SOrth ROrlikowski DATE 07/21/10 07/21/10 OFFICIAL RECORD COPY
Letter to Northern States Power Company, Minnesota, from R. Orlikowski dated July 21, 2010.
SUBJECT:
MEETING
SUMMARY
FOR REGULATORY CONFERENCE DISTRIBUTION:
Susan Bagley RidsNrrPMPrairieIsland RidsNrrDorlLpl3-1 Resource RidsNrrDirsIrib Resource Cynthia Pederson Steven Orth Jared Heck Allan Barker Carole Ariano Linda Linn DRPIII DRSIII Patricia Buckley Tammy Tomczak ROPreports Resource
ATTENDEE LIST REGULATORY CONFERENCE PRAIRIE ISLAND (EA-10-070) - JULY 13, 2010 Northern States Power Company (Xcel Energy)
D. Koehl, Vice President & Chief Nuclear Officer M. Schimmel, Site Vice President J. Anderson, Regulatory Affairs Manager G. Salamon, Director, Nuclear Licensing & Emergency Preparedness (EP)
R. Rippy, Licensing Engineer D. Smith, Shift Manager T. Roddey, Engineering Design Manager R. Rohrer, Fleet Program Engineering Manager M. Huting, Fleet Program Engineering Director C. Hessen, General Manager, Engineering D. Potter, Fleet Program Engineering Supervisor J. Ritter, PRA Engineer D. Moore, Consultant, DLMoore Consulting R. Dremel, Consultant, Maracer C. Warchol, Consultant, Vice President of Engineering, AES D. DeGrush, Consultant, Principal Engineer, AES D. Kettering, Site Engineering Director, Prairie Island (via phone)
U. S. Nuclear Regulatory Commission (some participated via phone)
M. Satorius, Regional Administrator, Region III A. Boland, Director, Division of Reactor Safety (DRS), Region III S. West, Director, Division of Reactor Projects (DRP), Region III S. Orth, Enforcement Officer, Region III N. Valos, Senior Reactor Analyst, DRP, Region III R. Orlikowski, Branch Chief, Projects Branch 4, DRP, Region III K. Stoedter, Senior Resident Inspector, Prairie Island, DRP, Region III G. Shear, Deputy Director, Division of Reactor Projects (DRP), Region III L. Kozak, Senior Reactor Analyst, DRP, Region III J. Hanna, Senior Reactor Analyst, DRP, Region II V. Mitlyng, Public Affairs, Region III P. Chandrathil, Public Affairs, Region III A. Barker, Regional Government Liaison, Region III J. Heck, Regional Counsel, Region III J. Lara, Team Leader TSS, DRP, Region III S. Bakhsh, Enforcement Coordinator, Region III B. Bartlett, Acting Branch Chief, Projects Branch 3, DRP, Region III F. Tran, License Reviewer, DNMS, Region III Enclosure
E. Coffman, Reactor Engineer, DRP, Region III C. Schmidt, Administrative Assistant, DRP, Region III M. Ashley, Technical Assistant (Enforcement), Office of Nuclear Reactor Regulation (NRR),
NRR/DIRS/IDST M. Cunningham, Director, Division of Risk Assessment, NRR/DRA J. Mitman, Senior Reliability and Risk Analyst, NRR/DRA/APOB L. James, Branch Chief, PRA Operational Support Branch, NRR/DRA/APOB B. Mizuno, Attorney, Assistant General Counsel for Operating Reactors (AGCOR),
OGC/GCHEA/AGCOR M. Chawla, Project Manager, Plant Licensing Branch III-1, NRR/DORL/LPL3-1 P. Bonnett, Senior Reactor Analyst, Performance Assessment Branch, NRR/DIRS/IPAB G. Gulla, Enforcement Specialist, OE/EB P. Hernandez, General Scientist, Concerns Resolution Branch, OE/CRB E. Davidson, General Engineer, Balance of Plant Branch, NRR/DSS/SBPB M. Smith, Attorney, Assistant General Counsel for Operating Reactors (AGCOR),
OGC/GCHEA/AGCOR S. Weerakkody, Branch Chief, Fire Protection Branch, NRR/DRA/AFPB M. Spencer, Attorney, Assistant General Counsel for Operating Reactors (AGCOR),
OGC/GCHEA/AGCOR R. Pascarelli, Branch Chief, Plant Licensing Branch III-1, NRR/DORL/LPL3-1 S. Lee, Deputy Director, Division of Risk Assessment, NRR/DRA Members of the Public (some participated via phone)
P. Mahowald, General Counsel, Prairie Island Indian Community J. Howe, Mayor, City of Redwing, MN J. Stine, Assistant Commissioner, Minnesota Department of Health S. Meilahn, Wisconsin Division of Emergency Management E. Ludy, Redwing Republican Eagle Enclosure