IR 05000302/1979025

From kanterella
Jump to navigation Jump to search
IE Insp Rept 50-302/79-25 on 790616-19.No Noncompliance Noted.Major Areas Inspected:Feedwater Pipe Welds,Via Radiographic Methods
ML19249A672
Person / Time
Site: Crystal River 
Issue date: 07/09/1979
From: Economos N, Herdt A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19249A669 List:
References
50-302-79-25, NUDOCS 7908240127
Download: ML19249A672 (4)


Text

{{#Wiki_filter:, +f o, UNITED STATES ! .,.. ' ',g NUCLEAR REGULATORY COMMISSION .

-

','. c REGION ll ! 101 MARIETTA sT., N.W., sulTE 3100 o, g

ATLANTA, GEORGIA 30303 g, ,o W ..... . Report Nos. 50-302/79-25 Licensee:_ Florida Power Corporation 3201 34th Street, South St. Petersburg, Florida 33733 Facility Name: Crystal River Unit No. 3 Docket No. 50-302 License No. DPR-72 Inspection at Crys 1 River site nrar Crystal River, Florida Inspector: h,> f '7-6

n N. Edo mos Date Signed - Approved by: ' '[[ 7-f-7f A. R. Herdt, Section Chief, RCES Branch Date Signed SUMMARY Inspection on June 16-19, 1979 Areas Inspected This special, unannounced inspection involved 44 inspector hours on-site in the area of radiographic examination of fcedwater pipe welds.

Results No apparent items of noncompliance or deviation were identified.

_, 'l b i 7908240 i

. . DETAILS - 1.

Persons Contacted Licensee Employees

  • G. Beatty, Jr., Plant Manager
  • J. Cooper, Jr., Compliance Engineer
  • S. Johnson, II, Inservice Inspection Engineer J. Barrett, Maintenance Engineer
  • C. Hicks, Corporate Level III Examiner Other Organizations Branch Laboratories, Inc.

D.

Dodd, Level III Exauiner J.

Peterson, Level II NDE Technician

  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on June 19, 1979 with those persons indicated in Paragraph 1 above.

3.

Licensee Action on Previous Inspection Findings Not inspected.

4.

Unresolved Items Unresolved items were not identified during this inspection.

5.

Radiography of Main and Auxiliary Feedwater Lines This inspection was performed on account of the NRC's request that the licensee radiograph certain weldments in the emergency feedwater (EFW) and main feedwater (FW) lines of steam generator B in order to verify weld integrity. The,icensee and RII agreed to radiograph a total of sixteen welds which were as follows: (1) each of the four welds in one feedwater and one emergency feedwater riser; both located at or/near the ring-header tee, (2) the three welds in the main feedwater ring-header tee and, the last weld on the main feedwater line prior to the first restraint off the main feedwater ring-header, (3) the last veld in the vertical leg on the emergency feed line to the emergency ring-header and, the two subsequent 9;) .y.

- .. ,

. -2-

welds on the ring-header elbow. Numerical identification and other weld details are listed in the table below.

Main Feedwater Line, OTSG "B" Weld Number Description _I SO Size Comments FW-130B Ell to Pipe SK-106C 14"sch.80 Linear Indication (nonfusion) stations 3 and 5 FW-27A Pipe to Ell SK-106C 14"sch.80 FW-27 Ell to Tee SK-106C 14"sch.80 HK-124 Toe to B&W-to MK123 Header 134922 14"sch.80 tIK-124 Toe B&W-to MK120 to Header 134924 14"sch.80 MK-124 Toe to 3" lg.

B&W-14"sch.80 Linear Indication to HK125* W1d. Neck 134924 3"1g to (nonfusion) flange to wld.

station 3 Neck to 0 MK-132 to Flange to Pipe B&W-3"sch.80 Linear Indication 134924 (nonfusion) Station 1-2 MK-133 to Pipe to E1198 B&W-3"sch.80 MK-134* 134924 MK-134 to Ell to Upper B&W-3"sch.80 MK135* Flange 134924 Emergency Feedwater Line, OTSG "B" Weld Number Description ISO Size EF-58AF Pipe to Pipe SK-108C 6"sch.80 (dutchman) EF-59 to Ell SK-108C 6"sch.80 - 90 _,s Ell extra strong . hJ !Y' <

. -3-i Weld Number Description ISO Size . NK-173 to Ell to Header SK-108C 6"sch.80 MK-A174 MK-A174 to Flange to B&W-6"Sch.80/3" long MK-179 Header 134926 weld neck MK-132 to Flange to Pipe B&W-3"sch.80 MK-338 134925, -134923 MK-338 to Pipe to E11 B&W-3"sch.80 HK-134 134925 MK134 to Ell to Upper B&W-3"sch.80 MK-138 134925 134923 Both lines were originally fabricated and tested in accordance with USAS Power Piping Code B31.1.0 1967 Edition thru March 1969 Erratum.

According to Table 136.5.1 of this code, there was no requirement for surface or volumetric examination to be performed on these lines. Erection fabri-cation drawings did specify magnetic particle inspection (MT) on all weldments and radiography on the 14 inch diameter tee of the ring-header of the FW line. Radiography on the designated welds was being performed by Branch Radiographic Laboratories Inc. (BRLI) in accordance with RT pro-cedure ISI-300 R/8. Results of radiographic review disclosed no evidence of service related indications on any of the welds checked. Fabrication related indications were noted in three main feedwater line welds, two in the three inch riser and one in a 14 inch din eter shop fabricated weld.

The licensee has agreed to examine these welds again (monitor) during two subsequent ISI inspectionr and the inspector identified this matter as inspector followup item (79-25-01).

') ?) t , 9~ }}