05000296/LER-2006-001, Re Main Steam Relief Valve Inoperability LCO Exceeded as a Result of Lift Setpoint Drift

From kanterella
(Redirected from 05000296/LER-2006-001)
Jump to navigation Jump to search

Re Main Steam Relief Valve Inoperability LCO Exceeded as a Result of Lift Setpoint Drift
ML061780354
Person / Time
Site: Browns Ferry 
Issue date: 06/23/2006
From: O'Grady B
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER 06-001-00
Download: ML061780354 (9)


LER-2006-001, Re Main Steam Relief Valve Inoperability LCO Exceeded as a Result of Lift Setpoint Drift
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function
2962006001R00 - NRC Website

text

June 23, 2006 U.S. Nuclear Regulatory Commission 10 CFR 50.73 ATTN: Document Control Desk Mail Stop OWFN, P1-35 Washington, D. C. 20555-0001

Dear Sir:

TENNESSEE VALLEY AUTHORITY - BROWNS FERRY NUCLEAR PLANT (BFN) -

UNIT 3 - DOCKET 50-296 - FACILITY OPERATING LICENSE DPR LICENSEE EVENT REPORT (LER) 50-296/2006-001-00 The enclosed report provides details of a failure to meet the requirements of a Technical Specifications (TS) Limiting Condition for Operation (LCO) because two main steam relief valves (MSRV) had become inoperable as a result of setpoint drift. The setpoint drift was discovered during bench testing at an off-site facility subsequent to the MSRV pilot cartridges removal from BFN Unit 3. The Unit 3 MSRVs likely operated with these as-found setpoints outside the allowable TS values for longer than the allowable LCO time.

As such, in accordance with 10 CFR 50.73(a)(2)(i)(B), TVA is reporting this event as any operation or condition prohibited by the units TS. There are no commitments contained in this letter.

Sincerely, Original signed by:

Brian OGrady cc: See page 2

U.S. Nuclear Regulatory Commission Page 2 June 23, 2006 Enclosure cc (Enclosure):

Ms. Margaret Chernoff, Project Manager U.S. Nuclear Regulatory Commission (MS 08G9)

One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852-2739 Mr. Malcolm T. Widmann, Branch Chief U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, Georgia 30303-8931 Ms. Eva A. Brown, Project Manager U.S. Nuclear Regulatory Commission (MS 08G9)

One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852-2739 NRC Resident Inspector Browns Ferry Nuclear Plant 10833 Shaw Road Athens, Alabama 35611-6970

U.S. Nuclear Regulatory Commission Page 3 June 23, 2006 WDC:DTL:PSH:BAB Enclosure cc (Enclosure):

B. M. Aukland, POB 2C-BFN M. Bajestani, NAB 1A-BFN A. S. Bhatnagar, LP 6A-C J. C. Fornicola, LP 6A-C R. F. Marks, PAB 1C-BFN R. G. Jones, NAB 1A-BFN K. W. Singer, LP 6A-C E. J. Vigluicci, ET 11A-K NSRB Support, LP 5M-C INPO:LEREvents@inpo.org EDMS WT CA-K S:lic/submit/lers/296-2006-01.doc

NRC FORM 366 (7-2001)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION (6-2004)

LICENSEE EVENT REPORT (LER)

(See reverse for required number of digits/characters for each block)

APPROVED BY OMB NO. 3150-0104 EXPIRES 06/30/2007

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

1. FACILITY NAME Browns Ferry Unit 3
2. DOCKET NUMBER 05000296
3. PAGE 1 OF 6
4. TITLE Main Steam Relief Valve Inoperability LCO Exceeded as a Result of Lift Setpoint Drift
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL NUMBER REV NO.

MONTH DAY YEAR FACILITY NAME none DOCKET NUMBER N/A 05 03 2006 2006-001-00 06 23 2006 FACILITY NAME none DOCKET NUMBER N/A

11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §:(Check all that apply)
9. OPERATING MODE 1

20.2201(b) 20.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii) 20.2201(d) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(A) 20.2203(a)(1) 20.2203(a)(4) 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 20.2203(a)(2)(i) 50.36(c)(1)(i)(A) 50.73(a)(2)(iii) 50.73(a)(2)(ix)(A) 20.2203(a)(2)(ii) 50.36(c)(1)(ii)(A) 50.73(a)(2)(iv)(A) 50.73(a)(2)(x) 20.2203(a)(2)(iii) 50.36(c)(2) 50.73(a)(2)(v)(A) 73.71(a)(4) 20.2203(a)(2)(iv) 50.46(a)(3)(ii) 50.73(a)(2)(v)(B) 73.71(a)(5) 20.2203(a)(2)(v) 50.73(a)(2)(i)(A) 50.73(a)(2)(v)(C)

OTHER

10. POWER LEVEL 100 20.2203(a)(2)(vi)

X 50.73(a)(2)(i)(B) 50.73(a)(2)(v)(D) specify in Abstract below or in (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of NRC Form 366A) (17) B.

Previous LERs on Similar Events Numerous previous reports on similar events have been made from BFN and other nuclear plants. The physical phenomenon affecting MSRV lift setpoints which results in this reportable condition is well-understood, and it has been the subject of much industry study. Different mitigative approaches have been tested, but none have successfully eliminated the issue. The installation of the instrumentation logic/circuitry which will automatically open the MSRVs as appropriate during pressurization transients largely negates the conditions safety impact.

Though this phenomenon has only a relatively small impact on the MSRV function and because of the compensatory hardware mitigation which has been installed at BFN, BFN is continuing to work with other industry stakeholders toward the total elimination of this issue.

C.

Additional Information

Browns Ferry corrective action document PER 102298 D.

Safety System Functional Failure Consideration:

The condition being reported involves only setpoint drift of 2 of 13 MSRVs. The safety/relief function of this set of valves was not compromised. A safety system functional failure did not result from this condition.

E.

Loss of Normal Heat Removal Consideration:

N/A. This condition being reported did not involve a reactor scram.

VIII. COMMITMENTS

None