ML20154N459

From kanterella
Revision as of 23:45, 10 December 2024 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Forwards Rev 0 to Mark I Wetwell to Drywell Differential Pressure Load & Vacuum Breaker Response for Vermont Yankee Generation Station, in Response to 860117 Request for Addl Info
ML20154N459
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 03/10/1986
From: Capstick R
VERMONT YANKEE NUCLEAR POWER CORP.
To: Rooney V
Office of Nuclear Reactor Regulation
Shared Package
ML20154N464 List:
References
FVY-86-19, GL-83-08, GL-83-8, GL-83-89, NUDOCS 8603170328
Download: ML20154N459 (2)


Text

f 5

kERMONT YANKEE NUCLEAR POWER CORPORATION FVY 86-19 RD 5, Box 169, Ferry Road, Brattleboro, VT 05301

,,go

. y ENGINEERING OFFICE 1671 WonCESTER ROAD FRAWGHAM. MASSACHUSETTS 01701 March 10, 1986 T EL E PHONE 617-872-4100 United States Nuclear Regulatory Commission Washington, DC 20555 Attention:

Office of Nuclear Reactor Regulation Mr. Vernon L

_ooney, Project Manager BWR Project.,irectorate No. 2 Division of BWR Licensing

References:

(a) License L3. DPR-28 (Docket No. 50-271)

(b) Letter, USNRC to VYNPC, NYY 83-23, Ceneric Letter 83-08, dated February 2, 1983 (c) Letter, VYNPC to UONRC, FVY 83-36, dated May 11, 1983 (d) Letter, USNRC to VYNPC, NVY 86-10, dated January 17, 1986

Subject:

Modifications of Vacuum Breakers on Mark 1 Containments (Generic Let.t.ec 83-08)

Dear Sir:

By letter dated January 17, 1983 (Reference (d)), you requested additional information related to the Vermont Yankee torus-to-drywell vacuum breaker modification in order to complete your review initiated under Ceneric Letter 83-08 (Reference (b)).

In response to your request, attached please find the information requested in the enclosure to your letter.

We trust this information is satisfactory; however, should you have any quertions or require additional information, please contact this office.

Very truly yours, VERMONT YANKEE NUCLEAR POWER CORPORATION J

R. W. Capstick Licensing Engineer RWC/no Attachment Me 4cb y M (J u t e A M S r

i B60317032g gso3go g g,' ypgg gggo kIg l

DR ADOCK O 1

  1. d/

as vsAs, et),

g g

'l' i

i

C f

Response to NRC Request for Additional Information Related to the Modification of Vacuum Breakers on Mark I containment at Vermont Yankee Nuclear Power Station.

Question 1:

Is the chugging source rate used in the Vermont Yankee evaluation the same as the one developed in CDI Report

(#84-3)? If not the same, provide the chugging source rate with the supporting justification.

Answer:

Yes. The methodology followed in CDI Report Number 84-3 (Reference 1) is identical to the methodology used in the Vermont Yankee evaluation (Reference 2 - attached) and detailed in response to NRC Question Number 5 in Reference 3.

Question 2:

Did the Vermont Yankee calculation apply the 1.07 load factor to account for the uncertainty in calculating the underpressure (Section IV of the staff's generic evaluation).

Answer:

A load factor, used to assure conservative prediction of the underpressure and detailed in response to NRC Question 2 in Reference 3, was. applied to the Vermont Yankee evaluation (Reference 2).

In fact, the load factor used in the plant unique evaluation was 1.06 and yields a conservative prediction of the underpressure.

Question 3:

Have the Vermont Yankee calculations used the drywell model Which results in the most conservative prediction (Section V of

-the generie avaluatinn)?

Answer:

Yes.

Drywell modeling was examined in response to NRC Question 6 in Reference 3.

For the Vermont Yankee evaluation (Reference 2), the capacitance model results in a more conservative forcing function, and was therefore used.

REFREENCES 1.

"Kark I Wetwell to Drywell Vacuum Breaker Load Methodology, Revision 0,"

Continuum Dynamics, Inc., Report Number 84-3, February 1984.

2.

" Nark I Wetwell to Drywell Differential Pressure Load and Vacuum Breaker Response for the Vermont Yankee Generation Station, Revision 0,"

Continuum Dynamics, Inc., Technical Note Number 84-24, January 1985 3.

" Response to NRC Request for Additional Information on Mark I Containment Program Wetwell to Drywell Vacuum Breaker Load Methodology, Revision 0,"

Continuum Dynamics, Inc. Technical Note Number 84-11, October 1984

,---