Application for Amends to Licenses DPR-39 & DPR-48.Amends Clarify Tech Spec Sections 3.5 & 4.5 Following Recent Mod to Reactor Containment Fan Coolers & Convert Entire Section Into STS Format.Fee Paid
ML20211P479
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 12/04/1986
From: Leblond P
COMMONWEALTH EDISON CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML20211P483 List:
References
2440K, NUDOCS 8612190082
Download: ML20211P479 (3)


Text

4

.n

  • r \ COmmOmfealth EstisOn
  • l One First Nabonal Plaza, Chcago, INinois

_ 3

(" L Address Reply to: Post Omco Box 767 Chca00, Iginois 60690 - 0767 December 4, 1986 Mr. Harold R. Denton U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Reculation l Washington, DC. 20555 1

Subject:

Zion Nuclear Power Station Units 1 & 2 Proposed Amendment to Facility Operating License Nos. DPR-39 and DPR-48 Reactor Containment Fan Coolers NRC Docket Nos. 50-295 and 50-304

Dear Mr. Denton:

Attachment 1 to this letter is a proposed amendment to Facility Operating License Nos. DPR-39 and DPR-48, Appendix A, Sections 3.5 and 4.5-Reactor Containment Fan Coolers. This proposed amendment clarifies these sections following a recent modification to the reactor containment fan coolers (RCFC) and converts the entire section into the Standardized Technical Specification format.

The RCFCs at Zion Station had been modified to remove the moisture separators and filters and to make the accident air flow path the only path available. The existing Zion Technical Specifications include a requirement to stroke each RCFC damper to the accident position every refueling outage.

This amendment effectively changes the verb " stroke" to the verb " verify" to reflect the fact that the flow dampers are permanently positioned in the accident mode. This proposed amendment also alters the format of Section 3.5 and 4.5 to the Standardized Technical Specification format.

Attachment 2 contains Commonwealth Edison Company demonstration that this proposed amendment does not involve a significant hazards consideration. This change has received on-site and off-site review and approval.

A $150.00 remittance is enclosed in accordance with 10 CFR 170. As

, provided by 10 CFR 50.91, the State of Illinois is being notified of this amendment request by transmittal of a copy of this letter and the attachments.

\

po

\ \

l i 8612190092 861204 PDR ADOCK 05000295 i a y/9oo P PDR p&ec cl

Mr. H. R. Denton December 4, 1986 If you have any questions re5arding this matter, please direct them to this office.

Three (3) signed originals and thirty-seven (37) copies of this transmittal and its attachments are hereby provided for your review.

Very truly yours, P. C. LeBlond Nuclear Licensing Administrator

/klj cc: Resident Inspector-Zion J. A. Norris-NRR M. C. Parker-State of Ill.

SUBSCR ED and S N to befor e this# - day oC / N1Y,JVA , 1986 M - 040

" Notary Public 2440K

D ATTACHMENT 1 PROPOSED CHANGES TO APPENDIX A TECHNICAL SPECIFICATION SECTIONS 3.5 and 4.5 REACTOR CONTAINMENT PAN COOLERS Pages Modified 11 146 147 148 149 2440K