MONTHYEARML20217M0211999-09-20020 September 1999 Part 21 Rept Re Possible Deviation of NLI Dc Power Supply Over Voltage Protection Circuit Actuation.Caused by Electrical Circuit Conditions Unique to Remote Engine Panel. Travelled to Hope Creek to Witness Startup Sequence of DG ML18107A3441999-06-0101 June 1999 Interim Part 21 Rept Re Premature Over Voltage Protection Actuation in Circuit Specific Application in Dc Power Supply.Testing & Evaluation Activities Will Be Completed on 990716 ML18106B0931999-02-25025 February 1999 Part 21 Rept Re Possible Defect in Swagelok Pipe Fitting Tee,Part Number SS-6-T.Caused by Crack Due to Improper Location of Heated Bar.Only One Part Out of 7396 Pieces in Forging Lot Was Found to Be Cracked.Affected Util,Notified ML18106B0551999-02-0101 February 1999 Part 21 Rept Re Possible Matl Defect in Swagelok Pipe Fitting Tee,Part Number SS-6-T.Defect Is Crack in Center of Forging.Analysis of Part Is Continuing & Further Details Will Be Provided IAW Ncr Timetables.Drawing of Part,Encl ML18106B0441999-01-29029 January 1999 Part 21 Rept Re Possible Defect in Swagelok Pipe Fitting Tee Part Number SS-6-T.Caused by Crack in Center of Forging. Continuing Analysis of Part & Will Provide Details in Acoordance with NRC Timetables ML20202F6861999-01-26026 January 1999 Engine Sys,Inc Part 21 (10CFR21-0078) Rept Re Degradation of Synchrostat Model ESSB-4AT Speed Switches Resulting in Heat Related Damage to Power Supply Card Components.Caused by Incorrect Sized Resistor.Notification Sent to Customers ML17354B0971998-09-0909 September 1998 Part 21 Rept Re Possible Machining Defect in Certain One Inch Stainless Steel Swagelok Front Ferrules,Part Number SS-1613-1.Caused by Tubing Slipping Out of Fitting at Three Times Working Pressure of Tubing.Notified Affected Utils ML20236N6751998-07-0909 July 1998 Part 21 & Deficiency Rept Re Notification of Potential Safety Hazard from Breakage of Cast Iron Suction Heads in Apkd Type Pumps.Caused by Migration of Suction Head Journal Sleeve Along Lower End of Pump Shaft.Will Inspect Pumps ML20217D5701998-03-20020 March 1998 Part 21 Rept 40 Re Governor Valve Stems Made of Inconel 718 Matl Which Caused Loss of Governor Control.Control Problems Have Been Traced to Valve Stems Mfg by Bw/Ip.Id of Carbon Spacer Should Be Increased to at Least .5005/.5010 ML20210E3591997-03-27027 March 1997 Part 21 Rept Re Sorrento Electronics Inc Has Determined Operation & Maint Manual May Not Adequately Define Requirements for Performing Periodic Surveillance of SR Applications.Caused by Hardware Failures.Revised RM-23A ML20096A4021995-12-28028 December 1995 Interim Part 21 Rept Failure of Scram Discharge Vol Drain Valve 1BFHV-F011.Possible Causes of Failure,Includes Spring mis-adjustment,change in Spring Adjuster Setting & Spring Relaxation.Further Investigation Ongoing ML20082S7401995-04-26026 April 1995 Part 21 Rept Re Hinge Arms Associated W/Sixteen Swing Check Valves Mfg by Anchor-Darling Valve Co ML20081L7701995-03-29029 March 1995 Initial Part 21 Rept Re Anchor-Darling Check Valve Hinge Arms.Cs Pump B Discharge Check Valve Failed to Close in Nov 1994 Because Butt Stop on Hinge Arm Not of Sufficient Length.New Butt Stop Hinge Arm,Hinge Pin & Disc Installed ML20063M1701994-03-0202 March 1994 Part 21 Rept Clarifying & Supplementing Info Provided by Licensee Re Deficiency in Qualified Life Calculation for Microswitches Mfg by Comsip,Inc. Subj PTW-5300 Dc Indicators Supplied by Comsip,Inc,Mfg by Microswitch Corp ML20046C6591993-08-0505 August 1993 Part 21 Rept:On 930429,deficiency Identified Re Heat Damage to Comsip Series PTW-5300 Dc Powered Microswitches.Initially Reported on 930709.Safety-related Dc Microswitches Will Be Replaced Prior to 931230 ML20128H9931993-02-0909 February 1993 Interim Deficiency Rept Re Defect in Replacement EDG Fuel Oil Pumps Supplied by Colt Industries (Fairbanks Morse Engine Div).Initially Reported on 930111.Plugs & O-rings Repositioned.Vendor Requested to Perform Evaluation ML18096B2421993-02-0101 February 1993 Part 21 Rept Re Possible Matl Defect in Stainless Steel Swagelock Tube Fittings.Initially Reported on 921218.List of Part Numbers,Heat Codes & Addl Affected Customers Encl ML20127K8811993-01-0606 January 1993 Part 21 Rept Re Engine Driven Fuel Oil Pump Being Returned for Proper Configuration Due to Portion of O Ring Missing from Plug ML20116L4311992-10-20020 October 1992 Followup to Part 21 Rept from Consolidating Power Supply, Inc Re Purchase & Procurement of 24-inch Flange at Facility Which Failed to Meet ASME Code Class III Requirements.Flange Purchased by Conex Pipe Sys,Inc.Investigation Underway ML20101L0791992-06-29029 June 1992 Final Part 21 Rept Re Defect in Assembly Process for Gh Bettis Containment Atmosphere Control Sys Valve Replacement Actuators.Initially Reported on 920529.Air Filter Installed in Compressor Main Air Line to Prevent Contamination ML20102B2071992-06-24024 June 1992 Part 21 Rept Re Cracking of Stellite 21 Hardfacing on Guide Nose of Poppets Supplied as Part of MSIV Leakage Improvement Mod.Initially Reported by Clei on 920522. Recommends That Liquid Penetrant Exam Be Performed ML20097D9111992-06-0303 June 1992 Part 21 Rept Re Design Defect in Degraded Grid Trip & Bus Transfer Scheme for Class IE Vital Busses Supplied by Bechtel Power Corp.Initially Reported on 920508.Design Change Package 4EC-3341 Issued & Implemented ML20097H1581992-05-29029 May 1992 Initial Part 21 Rept Re Failure of Gh Bettis Actuators Used at Plant.Gh Bettis Has Ordered Replacement SOVs & Pilot Valves for Installation at Butterfly Valve Mfg,C&S Valve ML20102B1041992-05-0808 May 1992 Part 21 Rept Re Defect Discovered in Degraded Grid Trip/Bus Transfer Scheme for Class IE Vital Bus Equipment.Time Delay of .7 Incorporated in Loading Scheme to Allow Loads to Drop Off of auto-swapped Class IE Buses ML20077N3491991-08-0909 August 1991 Part 21 Rept Re Potential for Malfunction of Filtration Recirculator Ventilation Sys Heater Control Panels at Plant Due to Excessive Heat Rise.Heater Control Panel Doors Removed ML20077J9641991-07-30030 July 1991 Interim Deficiency Rept Re Potential Deviation of Design Safety Function of Filtration Recirculator Ventilation Sys Heaters Controls Panels.Further Investigation Required to Determine If Defect Requires Notification,Per 10CFR21 ML19332C5831989-11-20020 November 1989 Part 21 Rept Re Misapplication of Magnetrol Level Switches Supplied by GE W/Hpci & RCIC Turbine Assemblies.Switches Declared Inoperable & Electrically Disconnected.Magnetrol Will Modify Spare Level Switch Assemblies ML20205F3211988-10-10010 October 1988 Part 21 Rept Re Potential Deviation from Tech Spec Concerning Ry Indicators Due to Operating Temp Effect on Analog Meter Movement.Initially Reported on 881006.Customers Verbally Notified on 881006-07 ML20215G2441987-06-16016 June 1987 Part 21 Rept Re Failure of Load Sequencing Equipment Supplied in Aug 1977 During Scheduled Testing.Caused by Open Electrical Connection on One Crimp Lug.Since 1978,insulated Lugs Used on All Equipment ML20211P7211987-02-23023 February 1987 Part 21 Rept Re Rockbestos Coaxial Cable Used in Sorrento Electronics Digital & Analog high-range Radiation Monitor. Insulation Resistance at High Temp Not High Enough for Ion Chamber & Associated Electronics to Operate Properly ML20210S3351987-02-0404 February 1987 Part 21 Rept Re Cracking in O-ring on Latch Mechanism on Contactors in Nuclear Exciters.Initially Reported on 861216. Sprecher & Schuh Changed O-ring Matl to Viton E60C. Contactors Will Be Returned to Vendor & Rebuilt ML20214E9231987-01-28028 January 1987 Part 21 Rept Re Incorrect Valve Stem Matl on Dragon Valves. Evaluation Underway.Owners or Architects/Engineers & NRC Will Be Notified of Results of Evaluation & Recommendations ML20215B9681986-09-26026 September 1986 Part 21 & Deficiency Rept Re Synchro-Start Type Essb Speed Switches.Initially Reported on 860822.Speed Switches Currently in Svc or Designated for Svc Will Be Tested for Relay Contact Closure & Relay Contact Condition ML20212N1371986-08-25025 August 1986 Part 21 Rept Re Potentially Defective Operation of Synchro-Start Products,Inc Synchronizing Speed Switches Used in Auxiliary Generating Equipment.Initally Reported on 860820.Next Rept Will Be Submitted by 860926 ML20211C6181986-06-0909 June 1986 Part 21 Rept Re Unknown Qualification of Yokogawa Type AB 40 Voltmeters & Ammeters Due to Unreported Design & Configuration Changes.Three Nuclear Plants Receiving 23 Items as Class 1E Spare Parts Notified.List of Users Encl ML20141E4361986-04-0101 April 1986 Final Significant Const Deficiency Rept Re Failure of Electrical Amplifier Assembly in Tobar Transmitters to Function During Irradiation Testing.Initially Reported on 860303.Seven Transmitters Will Be Replaced ML20141E4411986-04-0101 April 1986 Final Significant Const Deficiency Rept Re Anchor-Darling Testable Check Valves Not Opening/Closing Under Normal Operating Conditions.Initially Reported on 860305.Valves Modified to Improve Mechanism for Opening/Closing Disc ML20140J4261986-03-31031 March 1986 Part 21 Rept Re Nuclear Valves Shipped to Pse&G.Internal Parts Lapped Which Could Reduce or Eliminate Nickel Plating Resulting in Seat Leakage & Shifting Problems ML20210E0031986-03-17017 March 1986 Part 21 Rept Re Failure of Amplifiers at Hope Creek Plant During Gamma Radiation Testing.Initially Reported on 860314. Util Supplied W/List of Model 32 Transmitters Which Meet Criteria ML20199E9161986-03-0707 March 1986 Final Significant Const Deficiency Rept Re Overspeed Trip on Emergency Diesel Generator Mfg by Colt Industries.Initially Reported on 860213.All Colt-Pielstick PC-2 Engines Will Be Modified by 860415 ML20141N6501986-03-0505 March 1986 Final Deficiency Rept Re Environ Qualification of Tobar Pressure Transmitter Terminations.Initially Reported on 860205.Pressure Transmitters Reworked & Discrepancy & Startup Deviation Repts Issued ML20154H2191986-03-0303 March 1986 Part 21 & Deficiency Rept Re Tobar Model 32-2 Transmitters W/Steel,Not Polyester or Aluminum Amplifier Housings. Initially Reported on 860227.Preliminary Investigation Confirms Adequacy of Transmitters ML20141N7011986-02-26026 February 1986 Suppl to Final Significant Const Deficiency Rept Re Anchor/Darling Swing Check Valves.Eight Valves W/O Lock Welds Reworked ML20151Y8141986-02-0404 February 1986 Part 21 Rept Re Colt-Pielstick Engine Tripping Out on High Speed When Started for Test Purposes at Seabrook.Caused by Source of Air Pressure Staying On.Engines Will Be Modified to Positively Vent Air from Rack Boost Cylinder ML20137U8461986-02-0303 February 1986 Significant Const Deficiency Rept Re Inadequate Power to Tobar Pressure Transmitters.Initially Reported on 860115. Design Change Package (DCP-7153) Issued to Modify Power Supply Circuits ML20140A5281985-12-19019 December 1985 Part 21 Rept Forwarding Ltr Sent to Customers Re Check Valves Missing Lock Welds on Hinge Supports or Hinge Support Capscrews,Per 851121 Request.List of Customers Receiving Ltr Also Encl ML20137Z1611985-11-21021 November 1985 Final Part 21 & Significant Deficiency Rept Re Ruskin Mfg Co Spring Closure Fire Dampers.Initially Reported on 841224. Dampers Reworked & in-place Testing Program to Identify Limiting Airflow Conditions Implemented ML20137S1031985-11-0606 November 1985 Final Part 21 & Significant Const Deficiency Rept Re Heat Buildup Inside Generator Control Cabinets.Initially Reported on 850403.Design Change Packages 570 & 7079 Implemented. Current Transformers Replaced ML20138K2731985-10-11011 October 1985 Final Part 21 & Const Deficiency Rept Re Missing Lock Welds on Anchor/Darling Swing Check Valves.Initially Reported on 850911.Set Screws Staked During Insp & Disc Nut Pins Peened as Alternative to Lock Welding ML20133N8211985-10-10010 October 1985 Final Const Deficiency Rept Re Misoperation of Bailey Controls Co 862 Sys Logic Module Logic Memories During Environ Qualification Testing.Initially Reported on 850909. Gap in Circuit Board Pads Increased & Area Cleaned 1999-09-20
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217F1501999-10-12012 October 1999 Special Rept:On 990929,south Plant Vent (SPV) Range Ng Monitor Was Inoperable.Monitor Was Inoperable for More than 72 H.Caused by Electronic Noise Generated from Noise Suppression Circuit.Replaced Circuit ML20217A9931999-09-30030 September 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data ML20217N6531999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Hope Creek Generating Station,Unit 1.With ML20217M0211999-09-20020 September 1999 Part 21 Rept Re Possible Deviation of NLI Dc Power Supply Over Voltage Protection Circuit Actuation.Caused by Electrical Circuit Conditions Unique to Remote Engine Panel. Travelled to Hope Creek to Witness Startup Sequence of DG ML20211N5531999-09-0808 September 1999 Safety Evaluation Supporting Amend 121 to License NPF-57 ML20211B3781999-08-13013 August 1999 Special Rept 99-002:on 990730,NPV Radiation Monitoring Sys Was Declared Inoperable.Caused by Voltage Induced in Detector Output by Power Cable to Low Range Sample Pump. Separated Cables & Secured in Place to Prevent Recurrence ML20210U4721999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Hope Creek Generating Station,Unit 1.With ML20216D8331999-07-26026 July 1999 Safety Evaluation Concluding That Licensee IPEEE Complete Re Info Requested by Suppl 4 to GL 88-20 & That IPEEE Results Reasonable Given HCGS Design,Operation & History ML20216D8721999-07-26026 July 1999 Review of Submittal in Response to USNRC GL 88-20,Suppl 4: 'Ipeees,' Fire Submittal Screening Review Technical Evaluation Rept:Hope Creek Rev 1:980518 ML20210F3331999-07-22022 July 1999 Safety Evaluation Granting Relief Requests RR-B1,RR-C1,RR-D1 & RR-B3.Finds That Proposed Alternative for RR-B3 Provides Acceptable Level of Quality & Safety & Authorizes Alternative Pursuant to 10CFR50.55a(a)(3)(i) ML20210C4731999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Hope Creek Generating Station,Unit 1.With ML20216D8901999-06-30030 June 1999 IPEEEs Technical Evaluation Rept High Winds,Floods & Other External Events ML20196H8621999-06-30030 June 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data, June 1999 Rept ML18107A3441999-06-0101 June 1999 Interim Part 21 Rept Re Premature Over Voltage Protection Actuation in Circuit Specific Application in Dc Power Supply.Testing & Evaluation Activities Will Be Completed on 990716 ML20196A1511999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Hope Creek Generating Station,Unit 1.With ML20206Q4731999-05-14014 May 1999 SER Accepting Response to GL 97-05, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves, for Plant ML20206U1571999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Hope Creek Generating Station,Unit 1.With ML20216D8451999-04-30030 April 1999 Rev 1, Submittal-Only Screening Review of Hope Creek Unit 1 IPEEE (Seismic Portion). Finalized April 1999 ML20206C8481999-04-22022 April 1999 SER Authorizing Pse&G Proposed Relief Requests Associated with Changes Made to Repair Plan for Core Spray Nozzle Weld N5B Pursuant to 10CFR50.55a(a)(3)(i) LR-N990157, Special Rept 99-001:on 990315, C EDG Valid Failure Occurred During Surveillance Testing.Testing Resulted in Unsuccessful Loading Attempt,Due to Failure EDG Output Breaker to Close.Faulty Card Replaced1999-04-12012 April 1999 Special Rept 99-001:on 990315, C EDG Valid Failure Occurred During Surveillance Testing.Testing Resulted in Unsuccessful Loading Attempt,Due to Failure EDG Output Breaker to Close.Faulty Card Replaced ML20205R5901999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Hope Creek Generating Station,Unit 1.With ML20205G6051999-03-19019 March 1999 SER Accepting Relief Request Re Acme Code Case N-567, Alternate Requirements for Class 1,2 & 3 Replacement Components,Section Xi,Div 1 ML20205F8911999-03-18018 March 1999 Safety Evaluation Authorizing Licensee Requests for Second 10-year Interval for Pumps & Valves IST Program ML20204F7951999-02-28028 February 1999 Monthly Operating Rept for Feb 1999 for Hope Creek Generating Station,Unit 1.With ML18106B0931999-02-25025 February 1999 Part 21 Rept Re Possible Defect in Swagelok Pipe Fitting Tee,Part Number SS-6-T.Caused by Crack Due to Improper Location of Heated Bar.Only One Part Out of 7396 Pieces in Forging Lot Was Found to Be Cracked.Affected Util,Notified ML18106B0551999-02-0101 February 1999 Part 21 Rept Re Possible Matl Defect in Swagelok Pipe Fitting Tee,Part Number SS-6-T.Defect Is Crack in Center of Forging.Analysis of Part Is Continuing & Further Details Will Be Provided IAW Ncr Timetables.Drawing of Part,Encl ML18106B0441999-01-29029 January 1999 Part 21 Rept Re Possible Defect in Swagelok Pipe Fitting Tee Part Number SS-6-T.Caused by Crack in Center of Forging. Continuing Analysis of Part & Will Provide Details in Acoordance with NRC Timetables ML20202F6861999-01-26026 January 1999 Engine Sys,Inc Part 21 (10CFR21-0078) Rept Re Degradation of Synchrostat Model ESSB-4AT Speed Switches Resulting in Heat Related Damage to Power Supply Card Components.Caused by Incorrect Sized Resistor.Notification Sent to Customers ML18107A1871998-12-31031 December 1998 PSEG Annual Rept for 1998. ML20199E7271998-12-31031 December 1998 Monthly Operating Rept for Dec 1998 for Hope Creek Generating Station,Unit 1.With ML18107A1881998-12-31031 December 1998 PECO 1998 Annual Rept. LR-N980580, Monthly Operating Rept for Nov 1998 for Hope Creek Generating Station,Unit 1.With1998-11-30030 November 1998 Monthly Operating Rept for Nov 1998 for Hope Creek Generating Station,Unit 1.With ML20198N4161998-11-12012 November 1998 MSIV Alternate Leakage Treatment Pathway Seismic Evaluation LR-N980544, Monthly Operating Rept for Oct 1998 for Hcgs,Unit 1. with1998-10-31031 October 1998 Monthly Operating Rept for Oct 1998 for Hcgs,Unit 1. with ML20155J9861998-10-31031 October 1998 Non-proprietary TR NEDO-32511, Safety Review for HCGS SRVs Tolerance Analyses LR-N980491, Monthly Operating Rept for Sept 1998 for Hope Creek Generating Station,Unit 1.With1998-09-30030 September 1998 Monthly Operating Rept for Sept 1998 for Hope Creek Generating Station,Unit 1.With ML17354B0971998-09-0909 September 1998 Part 21 Rept Re Possible Machining Defect in Certain One Inch Stainless Steel Swagelok Front Ferrules,Part Number SS-1613-1.Caused by Tubing Slipping Out of Fitting at Three Times Working Pressure of Tubing.Notified Affected Utils LR-N980439, Monthly Operating Rept for Aug 1998 for Hope Creek Generating Station Unit 1.With1998-08-31031 August 1998 Monthly Operating Rept for Aug 1998 for Hope Creek Generating Station Unit 1.With LR-N980401, Monthly Operating Rept for July 1998 for Hope Creek Generating Station,Unit 11998-07-31031 July 1998 Monthly Operating Rept for July 1998 for Hope Creek Generating Station,Unit 1 ML20236N6751998-07-0909 July 1998 Part 21 & Deficiency Rept Re Notification of Potential Safety Hazard from Breakage of Cast Iron Suction Heads in Apkd Type Pumps.Caused by Migration of Suction Head Journal Sleeve Along Lower End of Pump Shaft.Will Inspect Pumps LR-N980354, Monthly Operating Rept for June 1998 for Hope Creek Generating Station,Unit 11998-06-30030 June 1998 Monthly Operating Rept for June 1998 for Hope Creek Generating Station,Unit 1 ML20236E9491998-06-30030 June 1998 Rev 0 to non-proprietary Rept 24A5392AB, Lattice Dependent MAPLHGR Rept for Hope Creek Generating Station Reload 7 Cycle 8 ML18106A6821998-06-24024 June 1998 Revised Charting Our Future. ML18106A6681998-06-17017 June 1998 Charting the Future. LR-N980302, Monthly Operating Rept for May 1998 for Hope Creek Generating Station,Unit 11998-05-31031 May 1998 Monthly Operating Rept for May 1998 for Hope Creek Generating Station,Unit 1 ML20248C7381998-05-22022 May 1998 Rev 0 to Safety Evaluation 98-015, Extension of Allowed Out of Service Time for B Emergency Diesel Generator LR-N980247, Monthly Operating Rept for Apr 1998 for Hope Creek Station, Unit 11998-04-30030 April 1998 Monthly Operating Rept for Apr 1998 for Hope Creek Station, Unit 1 LR-N980196, Monthly Operating Rept for Mar 1998 for Hope Creek Generating Station,Unit 11998-03-31031 March 1998 Monthly Operating Rept for Mar 1998 for Hope Creek Generating Station,Unit 1 ML20217D5701998-03-20020 March 1998 Part 21 Rept 40 Re Governor Valve Stems Made of Inconel 718 Matl Which Caused Loss of Governor Control.Control Problems Have Been Traced to Valve Stems Mfg by Bw/Ip.Id of Carbon Spacer Should Be Increased to at Least .5005/.5010 ML18106A5851998-03-0303 March 1998 Emergency Response Graded Exercise,S98-03. Nuclear Business Unit Salem,Hope Creek Emergency Preparedness, 980303 1999-09-08
[Table view] |
Text
_.
1 ENGINE SYSTEMS,INC.
[_
- . 301, South Church St., Suite 100 / P.O. Box 1928 / Rocky Mount, NC 27802-1928 / Telephone: (919) 977-2720 / Fax (919) 446-3830 January 26,1999 U.S. Nuclear Regulator Commission Document Control Desk Mail Stop 0-11 A1 Washington, DC 20555
Subject:
10CFR21 Reporting of Defects and Non-Compliance -
Engine Systems, Inc. Report No.10CFR21-0078 Synchrostart model ESSB-4AT speed switch (p/n SA-2110)
I
Dear Sir:
The enclosed report addresses a reportable defect and the corrective action to be taken by users of the subject speed switch. This notification is being sent to all of our nuclear customers.
Should you have any questions, please feel free to call.
Please sign below, acknowledging receipt of this report, and return a copy to the attention of Engineering Document Control at the address below (or, fax to number 919/446-1134) within l 10 working days after receipt.
Yours very truly, I ENGINE SYSTEMS, INC.
O Q.d& '
Jo-Ann Mason Engineering Document Control Please let us know if ANY of your mailing information changes - name of recipient,
]6I7 name of company / facility, address, etc. Mark the changes on this acknowf.edgment form and send to us by mail or FAX to the number above.
RECEIVED:
(91)
DATE:
9902040139 990126' 9~
PDR S ADOCK0500035k( PDR Quality Performance With Pride
, a
LE I i ENGINE SYSTEMS,INC. ! d;;d )
301 South Church St., Suite 100 / P.o. Box 1928 / Rocky Mount, NC 27802-1928 / Telephone: (919) 977-2720 / Fax (919) 446-3830 )
l Report No.10CFR21-0078 l Rev. 0: January 25,1999 l l
l i
10CFR21 REPORTING OF DEFECTS AND NON-COMPLIANCE COMPONENT: Synchrostart ESSB-4AT speed switch SYSTEM: Staridby EMD diesel generator control systems CONCLUSION: Defect is reportable in accordance with 10CFR21.
i PREPARED BY:
- DATE: 'NMW Donald D. Galeazzi Engineering Manager REVIEWED BY: Ndah hh DATE: x\w\e Michael Nubing Quality Assurance Manager Quality Performance With Pride
REPORT NO.10CFR21-0078 REVISION 0: 1/25/99 PAGE: 1OF3
SUMMARY
Engine Systems Inc. has received notification that Hope Creek generating station experienced the degradation of three Synchrostat model ESSB-4AT speed switches. As reported in Operating Expenence document OE9504 (see Exhibit 1), all three degradations occurred because an incorrect i resistor was installed on the speed switch's power supply card. This resulted in heat related damage to l the power supply card components. The cited speed switches were supplied by Coltec. !
The Synchrostart ESSB-4AT speed switch is a standard component in Engine Systems' safety related l EMD diesel generator control systems. As applied by Engine Systems, the speed switch provides a safety related function. Failure of the speed switch could disable generator field flashing, resulting in failure of the diesel generator to build output voltage. Because of the safety related application of the ESSB-4AT speed switch, Engine Systems is sending this notification to all nuclear customers.
COMPONENT:
Synchrostart ESSB-4AT speed switch (p/n SA-2110). l i
CUSTOMERS AFFECTED:
i All nuclear users of EMD diesel generators.
DEFECT:
The speed switch power supply card contained an correctly sized resistor. An 82 ohm resistor was installed in place of the correctly sized 1200 ohm reastor.
CORRECTIVE ACTION:
According to the information contact identified in OE9504, severe heat damage to the power supply card components became visibly evident within the first 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> of engine operation. A DC system ground or erratic speed indication occurred after approximately 40 to 60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> of operation. The circuitry at Hope Creek only applies power to the speed switch during engine operation. Engine Systems' circuit design applies power to the speed switch continuously (operating as well as standby modes); therefore, speed switch degradation would occur within 3 days following completion of installation. As a result, speed switches with incorrect resistors would have been identified during periodic testing of the diesel generator; therefore, installed speed switches are not suspect.
- 1. All users with ESSB-4AT speed switches should check their spare ESSB-4AT speed switches to ensure that the correct resistor is installed.
A. Remove the four cover mounting screws.
B. Lift the cover (with attached circuit cards) out of the switch housing.
I. ;
l: . ,
REPORT NO.'10CFR21-0078 !
l REVISION 0: 1/25/99 l PAGE: 2OF3 l l
- C. Identify the power supply card. ,
i The power supply card is located at the bottom of the cover and is unique because it has ;
. "fingers"which restin a slotin the switch housing. l ll D. Identify the suspect resistor.
, i i The suspect resistoris the only component mountedin a spnng clip. This resistorshould be 1200 ohms. ' If the resistor markings are not readable, connect an ohmmeter across the resistor (use exposed leads) to venfy resistance (1200 ohms +/- 2%). ,
E. Reinstall cover in housing, making sure that the " fingers" of the power supply card rest in the slot at the bottom of the housing. Install four cover mounting screws and tighten hand (snug) tight.
i i
- 2. Switches with incorrect resistors should be retumed to Engine Systems, Inc., contact our Customer
' Service department.-
- 3. Switches with correct resistors can be retumed to inventory.
+
( ..
(
p
I REPORT NO.10CFR21-0078 i REVISION 0: 1/25/99 PAGE: 3 OF 3 !
l l
l l
l l
i i
EXHIBIT 1 i
l l
OPERATING EXPERIENCE REPORT OE9504 (2 pages) !
. SYNCHROSTART ESSB CATALOG CUT (1 page) 1 l
i l
OPEX oG%04
. i
> > Unit Name: ..................... Hope Creek )
> > Year Commercial: .............. 1986 l
> > NSSS/,A-E: ...... ............. .GE/Bechtel l
> > Rating: ....................... 1117.5
> > Turbine Mfg: ...................GE l
> > Event Date: ................. . 9/23/98
> > Docket No: ........... ........ 50-354
> > EIIS System Code: EK
> > NSSS Applicability: BWR and PWR
> > Maintenance Rule: Yes
> > ABSTRACT:
> > Hope Creek Generating Station has experienced the degradatien of three
> > Synchro-Start speed switches. All three degradations occurred because
> > the switch's internal power supply card contained a wrong sized
> > current limiting resistor. A spare speed switch from inventory was
> >.diso found to contain a wrong resistor. The affected speed switches
> > have different batch numbers, but all contain the same wrong sized
> > current limiting resistor. The cited speed switches were manufactured
> > by Synchro-Start (M/N ESSB-4AT) and purchased through Coltec (P/N
> > 01709876-162).
> > DESCRIPTION:
> > During a planned run of the 'A' emergency diesel generator in
> > September 1998, it was observed that the engine auxiliaries that
> > normally turn on as the engine coasts down cycled on then off 5 to 6
> > times. Corrective maintenance identified several overheated components
> > on the power supply card internal to the speed switch, (Synchro-start,
> > M/N ESSB-4AT). The switch was replaced with a new unit and the
> > degraded switch sent to the original vendor for a root cause
> > determination. A review of the corrective maintenance history
> > indicated that this switch was replaced in March 1998, due to a ground
> > on the 125 VDC control system. Photos of the degraded March 1998
> > switch appear to be identical to that of the degraded September 1998
> > switch.
> > Prior to completion of the vendor evaluation / a planned maintenance
> > outage of the 'D' emergency , diesel generator in October 1998,
> > identified similar evidence of component overheating on the power
> > supply card internal to the switch. The switch calibrated
> > satisfactorily, however based upon the apparent heat related damage,
> > the switch was replaced with a new unit. Following four maintenance
> > test runs and the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> surveillance run, during the hot restart
> > test the analog speed indicators read high. An internal inspection of
> > the switch in the 'D' diesel revealed significant overheating of the
> > power supply components similar to what was observed on the 'A'
> > diesel.
> > The control circuit of each emergency diesel contains an ' electronic
>> speed switch', which controls the sequence / operation of various engine
> > support / auxiliary systems. The diesel speed switch circuitry consists
> > of an engine mounted sensor, a speed switch with four output contacts
> > and two local analog tachometers. Output contacts enable / disable
> > select alarms and control key engine auxiliary components essential
> > for engine and generator operation. (Relays activate functions at 40,
> > 95, 125, and 365 rpm. The analog output is calibrated from 'O' to
> > '750' rpm and normal engine running speed at 514 rpm.)
~_ . - -. ...- - _ . - - - . - _ . - - - _ - . - . - . - - . - . . . . _ - . _ . _ _ , . __
> ' > On-sita b:nch tssting by utility psrsonnsi concludsd that tha cause of
> .> the power supply.degrcdation was an incorrset current limiting
> > resistor installed by the vendor. A portion of the supply consists of
> 2 a 5 VDC circuit which supplies power to the card logic circuits and '
> -> .th'e anal og output control circuit. A current limiting resistor, by
> > design, is suppose to have a value of 1200 ohms. The as found resistor !
> > in the 9/98 and 10/98 degraded speed switches had an 82 ohm resistor. i
>-> A spare switch from the storeroom was also found to have an incorrect
- > v resistor installed.
'> > The cited speed switches have a serial number listed on the name
> > plate; however, this serial number represents a single ' batch' number
> > which is usigned when a group of switches are fabricated. The ' batch'
> > numbers of the degraded switches are 79116 and 81297.
> > CAUSE:
> . > Wrong current limitiag resistor installed on the power supply card
> > internal to the speed switch 'during the manufacturing process. The
- > ' > original manufacture.r, Synchro-Start, has concurred that the 82 ohm
> -> ' resistor is incorrect and causes the power supply to overheat. (Note:
> > the correct current' limiting resistor should be 1200 ohms.)
> > SAFETY SIGNIFICANCE:
> Engineering has' determined that the cited speed switch degradation
> : > does not impact the ability of the diesel generator to perform its
--> > safety function. A reasonable assurance that the emergency diesel
> > will perform its intended design function is based upon the following:
~
> >+ actual degradations to-date have not impacted satisfactory
>. >- monthly testing 1
> >+ an operability determination which analyzed all possible
> > switch functions against potentia:. malfunctions
> . >+ compensatory action taken at the conclusion of each diemel
> > run
- > > HISTORY:
"> > There have been several Operating Experience documents (OE 5008, OE
- > > 5433.ts CE 5919) involving defective speed switches manufactured by
. >- > Synchro-start, which have symptoms similar to those seen here, but
> .> none of the documents indicate that the degra'dation was due to the use
>. > of a wrong sized resistor.
> > CORRECTIVE ACTIONS:
--> > 1). All speed switches will be replaced with units verified to
- > >z have the correct current limiting resistor.
> >:2). Inventory has been checked to insure that replacement
>>- switches have the correct current limiting resistor. t
> > 3) Notification of-the Nuclear Industry has been made via
( > > this OE.
I >
Subject:
OE9504 - Defective EDG Speed Switches l > >
> > INFORMATION. CONTACT: . George S. Daves (609) 339-3071, gdaves@PSEG.COM i
1 l-I
.- - - . . , . - _ s
_ rzAronssl,orrious
. A. eta,ie Sw ,, oi,,te E = Sealed NEMA 4 Enclosure
= = Wansient and Reverse Polarity Protection gy- E e Precies Repetitive Speed Switch Pointe e Automatic, Manual or Remote Manuel Roset e PowerLoes Protection
- = = - . D.C. Output for Model 30 Tech (Ima)
= 8 40VDC;64VDC;100-140VDC;or100-130VACPowe Z = BrokenSignalLeadProtection
_ = StandardorReverseReleyLogic
= LociavireSeal
. VitrationisoistionKit
_ = ConduitCover E m SPECIFICATIONS EE
=
-=
ELECTMCE ya.
mgg '-" ___ -
. -input 8-40 VDC 64 VDC
-100-140 VDC 100-130VAC
.~ _ . . . , .,,- = Reverse Polarity Protection til --- - .,,-. 1000 VDC
. Maximum Current 12 \ bit 24 Volt
~l i~',, _ y _ (2 ch.8-40 VDC) l Operating 200 ma 220 ma
'6 Standby p: @ppp,ggef@ e, i,l $_. il
- -'_[";
=== 3 l k ! tPi d Minimum- 0.7 VRMS
@y- Wlgi3 j I ;i <,e Impedance-2K OHMS R sth, .,, WMssh.,.-M)4 f
sMP &J .EL - --
e Relay Contact Ratings Resistance Load-0.1 to 10 amps 28 VDC
,,,,,,,,,,_j, \ \. ,, Inductive Load- 0.1 to 8 amps 28 VDC
} \__,..,.,,.,., L... L ,,
i
,_ - C a.=n e Response u me
{
=l,;l'",';g , , , , , , , , , , _ 100 Milliseconds Typical L- .,=wm., a Setqpint Roset
'~i
- Automatic- 80% to 90% of Setpoint
- 4. == wum Adjustable-(Variable Automatic) 50% to 98% of Setpoint
= Setpoint stability The model ESSB Electronic Speed Swrtch has many years 0.8% over voltage range and 0.01% per 'F Typical of proven service. it is engineered to prtmde a wide variety of features and options including up to four switch points, adjustable reset, a selection of voltage inputs al.d DC cur-rent for tachometers.
ECEUffCAL/MONAL
= OperatingTemperature The ESSB Speed Switch is molded in a rugged NEMA
-40*C to +85*C (-40*F to +185'F) 4 enclosure which provides iicim,Gvu against the rough a Vitration environmental conditions associated with diesel engines. 4g's 9 to 200 Hz
= Shock 4 Foot Drop Test a Case NEMA 4 High Impact Molded Enclosure
-